The E-Series hydraulic/magnetic circuit breaker is ideally suited
for higher current and voltage applications. It is UL listed
and CSA certified for branch circuit protection, which does
not require a fuse back up. It is also UL recognized and CSA
certified as a supplementary protector and as a manual motor
controller.
Its physical features include front and back mounting, screw
and stud terminals and heavy duty box wire connectors
for solid wire or a pressure plate connector for standard
wire. The E-series is available with handle actuators and can
be configured as .1-125 amps, up to 600VAC or 125VDC,
with choice of time delays, actuator colors and 1 to 6 poles
configuration. Additionally, a Power Selector device is also
available.
Product Highlights:
UL listed and CSA certified
Certified for circuit branch protection
Recognized as a supplementary protector and as a manual
motor controller
Optional Power Selector Device
Typical Applications:
Ideal for higher current and voltage applications
Renewable energy systems
Military
Industrial controls
Generators
E-Series
Circuit Breaker
Carling Technologies, Inc.
60 Johnson Avenue • Plainville, CT 06062-1177
Phone: (860) 793-9281 • Fax: (860) 793-9231
Email: sales@carlingtech.com • www.carlingtech.com
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
2 |E-Series Circuit Breaker - General Specications
Maximum Voltage
Current Ratings
Auxiliary Switch Rating
Insulation Resistance
Dielectric Strength
Resistance, Impedance
Pulse Tolerance Curves
Environmental
Physical
Mechanical
Electrical
Designed in accordance with requirements of specication
MIL PRF-55629 & MIL-STD-202G as follows:
Shock
Vibration
Moisture Resistance
Salt Spray
Thermal Shock
Operating Temperature
Number of Poles
Mounting
Connectors, Box Type
Internal Circuit
Conguration
Weight
Standard Colors
Endurance
Trip Free
Trip Indication
600VAC 50/60 Hz, 125VDC (Table A)
Standard current coils: 0.100, 0.250,
0.500, 1.00, 2.50, 5.00, 7.50, 10.0, 15.0,
20.0, 25.0, 30.0, 50.0, 60.0, 70.0, 100 &
125 Amp.
SPDT; 10.1A 250VAC, 1.0A 65VDC;
0.5A 80VDC, 0.1A 125VAC (with gold
contacts).
Minimum of 100 Megohms at 500 VDC.
UL, CSA: 2200 V 50/60 Hz for one
minute between all electrically isolated
terminals. E-Series Circuit Breakers
comply with the 8mm spacing and
3750V 50/60 Hz dielectric requirements
from hazardous voltage to operator
accessible surfaces, between adjacent
poles and from main circuits to
auxiliary circuits per Publications EN
60950 and VDE 0805.
Values from Line to Load Terminal -
based on Series Trip Circuit Breaker.
Withstands 100 Gs, 6ms, sawtooth while
carrying rated current per Method 213,
Test Condition “I”.
Withstands 0.060” excursion from
10-55 Hz, and 10 Gs 55-500 Hz, at
rated current per Method 204C, Test
Condition A.
Method 106D, i.e., ten 24-hour cycles @
+ 25°C to +65°C, 80-98% RH.
Method 101, Condition A (90-95% RH @
5% NaCl Solution, 96 hrs).
Method 107D, Condition A (Five cycles
@ -55°C to +25°C to +85°C to +25°C).
-40° C to +85° C
1 - 6
A 3” minimum spacing must be
provided between the circuit breaker
arc venting area on back connected
E-Series circuit breakers and grounded
obstructions. E-Series circuit breakers
must be mounted on a vertical surface.
Front connected E-Series circuit
breakers are supplied with box type
pressure connectors that accept
copper or aluminum conductors
as follows: 1/0-14 Copper, 1/0-12
Aluminum.
Series and Switch Only, (with or without
auxiliary switch). Shunt with current
coils.
Approximately 252 grams/pole
(Approximately 9 ounces/pole)
Housing-Black; Actuator - See Ordering
Scheme.
6,000 ON-OFF operations @ 6 per
minute; with rated Current and Voltage.
Additional 4,000 ON-OFF mechanical.
All E-Series Circuit Breakers will trip on
overload, even when Handle is forcibly
held in the ON position.
The operating Handle moves positively
to the OFF position when an overload
causes the breaker to trip.
*Manufacturer reserves the right to change product specification without prior notice.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
| 3 E-Series Circuit Breaker - General Specications
Electrical Tables
Table A: Lists UL Listed (489) & CSA Certied (C22.2 No. 5) congurations & performance capabilities as a Molded Case Circuit
Breaker.
Table B: Lists UL Recognized & CSA Accepted congurations & performance capabilities as a Component Supplementary
Protector.
80 DC --- 0.10 - 100 5,000 50,000
125 DC --- 0.10 - 100 5,000 10,000
125 DC --- 101 - 125 10,000 ---
120 50 / 60 1 101 - 125 10,000 ---
SERIES 240 50 / 60 10.10 - 30 5,000 10,000
240 50 / 60 1 31 - 100 5,000
120 / 240 50 / 60 10.10 - 30 5,000 10,000
120 / 240 50 / 60 1 31 - 100 5,000 ---
120 / 240 50 / 60 1 101 - 125 10,000 ---
240 50 / 60 30.10 - 100 5,000 ---
E SERIES TABLE A : UL489 LISTED BRANCH CIRCUIT BREAKERS
VOLTAGE INTERRUPTING
CAPACITY (AMPS)
MAX.
RATING FREQUENCY PHASE WITHOUT BACKUP
FUSE
CIRCUIT
CONFIGURATION FULL LOAD AMPS
CURRENT RATING HIGH
INTERRUPTING
CAPACITY
(AMPS)
125 DC --- 0.02 - 100 --- --- 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
125 DC --- --- 101 - 120 --- 5,000 TC1,2, OL0, U1 TC1,2, OL0, U1
150 DC --- --- 0.02 - 125 --- 5,000 TC1, OL0, U3 TC1, OL0, U3
160 DC --- 0.02 - 100 --- --- 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
150 / 300 DC --- 0.02 - 100 --- --- 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
SERIES & 120 / 240 50 / 60 1 --- 0.02 - 100 --- 5,000 TC1,2, OL0, U1 TC1,2, OL0, U1
SHUNT 240 50 / 60 1 0.02 - 100 --- --- 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
250 50 / 60 1 0.02 - 100 --- 10,000 --- TC1,2, OL1, C1 TC1,2, OL1, C1
--- 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
10,000 --- TC1,2, OL1, C1 TC1,2, OL1, C1
480 50 / 60 1 & 3 0.02 - 100 --- 10,000 --- TC1,2, OL1, C1 TC1,2, OL1, C1
480 1 50 / 60 1 & 3 0.02 - 50 --- 10,000 --- TC1,2, OL1, C1 TC1,2, OL1, C1
600 50 / 60 1 & 3 0.02 - 100 --- 10,000 --- TC1,2, OL1, C1 TC1,2, OL1, C1
600 2 DC --- --- 0.02 - 125 --- 5,000 TC1, OL0, U3 TC1, OL0, U3
125 DC --- 0.02 - 120
160 DC --- 0.02 - 100
SWITCH 240 50 / 60 1 0.02 - 100
ONLY 277 50 / 60 1 0.02 - 100
480 50 / 60 1 & 3 0.02 - 100
600 50 / 60 1 & 3 0.02 - 100
277 50 / 60 1 0.02 - 100 ---
CSA
WITH BACKUP
FUSE3
WITHOUT
BACKUP FUSE
E -SERIES TABLE B: COMPONENT SUPPLEMENTARY PROTECTORS
CIRCUIT
CONFIGURATION
VOLTAGE CURRENT RATING SHORT CIRCUIT CAPACITY (AMPS) APPLICATION CODES
MAX.
RATING FREQUENCY PHASE FULL LOAD
AMPS
GENERAL
PURPOSE AMPS
UL/CSA
UL
Table B Notes:
1 Per pole opposite polarity rating - Delta Conguration.
2 4 Poles connected in series
3 Requires branch circuit backup with a UL Listed Type K5 or RK5 fuse
rated 15A minimum and no more than 4 times full load amp rating and
not to exceed 225A.
Agency Certifications
UL Recognized
UL Standard 1077
UL Standard 1500
UL Listed
UL Standard 489
CSA Accepted
CSA Certied
TUV Certied
VDE Certied
Component Recognition Program
as Protectors, Supplementary
(Guide QVNU2, File E75596)
Component Recognition Program
as Manual Motor Controls (Guide
NLRV2, File E135367)
Protectors, Supplementary for
Marine Electrical & Fuel Systems
(Guide PEQZ2, File E75596)
Ignition Protection
Circuit Breakers, Molded Case
(Guide DIVQ, File E129899)
Component Supplementary
Protector (Class 3215 30, File
047848 0 000)
CSA Standard C22.2 No. 235
Circuit Breaker Molded Case
(Class 1432 01, File 093910),
CSA Standard C22.2 No. 5.1 - M
EN60934 under License No.
R72031056
EN60934, VDE 0642 under File
No. 10537
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
4 |E-Series Circuit Breaker - General Specications
Table C: Lists UL Recognized, CSA Accepted and VDE Certied congurations and performance capabilities as a Component
Supplementary Protector.
Table D: Lists UL Recognized, CSA Accepted congurations and performance capabilities as Protectors, Supplementary for
Marine Electrical and Fuel Systems (Guide PEQZ2, File E75596). Ignition Protected per UL 1500. UL Classied Small Craft
Electrical Devices, Marine in accordance with ISO 8846 (Guide UZMK, File MQ1515) as Marine Supplementary Protectors.
CURRENT RATING
VDE (Icn)
CONSTRUCTION NOTES
125 DC --- 0.1 - 100 --- 5,000 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1 1 or 2 Poles
SERIES & 240 50 / 60 1 & 30.1 - 100 --- 5,000 5,000 TC1,2, OL1, U1 TC1,2, OL1, U1
1 - 5 Poles. Up to 4
Current Poles, 1 Voltage
Pole
SHUNT 415 50 / 60 1 & 30.1 - 100 10,000 --- 4,000 TC1,2, OL1, C1 TC1,2, OL1, C1
2 - 5 Poles. Up to 4
Current Poles, 1 Voltage
Pole
125DC --- 0.1 - 125
SWITCH ONLY 240 50 / 60 1 & 30.1 - 100
415 50 / 60 1 & 30.1 - 100
E -SERIES TABLE C: COMPONENT SUPPLEMENTARY PROTECTORS WITH VDE
SHORT CIRCUIT CAPACITY (AMPS)
WITHOUT
BACKUP
FUSE
UL/CSA
UL CSA
WITH BACKUP
FUSE1
WITHOUT
BACKUP
FUSE
CIRCUIT
CONFIGURATION
VOLTAGE APPLICATION CODES
MAX.
RATING FREQUENCY PHASE FULL LOAD AMPS
65 DC --- 0.02 - 1005,000 TC1,2,OL1,U1 TC1,2,OL1,U1
SERIES 125 50 / 60 1 0.02 - 1001,500 TC1,2,OL1,U1 TC1,2,OL1,U1
250 50 / 60 1 0.02 - 1001,500 TC1,2,OL1,U1 TC1,2,OL1,U1
WITHOUT BACKUP
FUSE UL
APPLICATION CODES
E SERIES TABLE D : UL1500 (Marine Ignition Protection)
CSA
CIRCUIT
CONFIGURATION
VOLTAGE
CURRENT RATING SHORT CIRCUIT
CAPACITY (AMPS)
MAX.
RATING FREQUENCY PHASE
FULL LOAD AMPS
Electrical Tables
Table C Notes:
1 Requires branch circuit backup with a UL LISTED Type K5 or RK5 fuse rated 15A minimum and no more than 4
times full load amp rating and not to exceed 225 amps.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
| 5 E-Series Handle UL Recognized – Ordering Scheme
7 CURRENT RATING (AMPERES)7
OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS)5
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
090 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
660 60.000
670 70.000
680 80.000
690 90.000
810 100.000
811 110.000
812 120.000
9128 125.000
CODE AMPERES
A06 6 DC, 5 DC
A12 12 DC, 10 DC
A18 18 DC, 15 DC
A24 24 DC, 20 DC
A32 32 DC, 25 DC
A48 48 DC, 40 DC
A65 65 DC, 55 DC
B25 125 DC, 100 DC
J06 6 AC, 5 AC
J12 12 AC, 10 AC
J18 18 AC, 15 AC
J24 24 AC, 20 AC
J48 48 AC, 40 AC
J65 65 AC, 55 AC
K20 120 AC, 65 AC
L40 240 AC, 130 AC
1
Series
2
Actuator
3
Poles
6
Frequency
& Delay
7
Current Rating
8
Terminal
12
Agency
Approval
4
Circuit
5
Auxiliary
Switch
E A B 0 1 A2 2 BC24 450
1 SERIES
E
2 ACTUATOR
A Handle, one per pole
8 TERMINAL12
BACK CONNECTED (FRONT MOUNTED ONLY) MAX. RATING
19 10-32 Stud (All Terminals) 50 A
29 1/4-20 Stud (All Terminals) 120 A
A9 M5 Stud (Line & Load) 50 A
B9 M6 Stud (Line & Load) 100 A
FRONT CONNECTED (BACK MOUNTED ONLY) MAX. RATING
310 Box Wire Connector (Line & Load) 100 A
C11 Box Wire Connector w/ Pressure Plate (Line & Load) 100 A
4 10-32 Screw (Line & Load) 50 A
D M5 Screw (Line & Load) 50 A
5 10-32 “Bus-Type” Screw (Line), 10-32 Screw (Load) 50 A
E M5 “Bus-Type” Screw (Line), 10-32 Screw (Load) 50 A
610 10-32 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
F11 10-32 “Bus-Type” Screw (Line), Box Wire Connector
w/ Pressure Plate (Load) 100 A
7 1/4-20 Screw (Line & Load) 100 A
G M6 Screw (Line & Load) 100 A
8 1/4-20 “Bus-Type” Screw (Line), 1/4-20 Screw (Load) 100 A
H M6 “Bus-Type” Screw (Line), M6 Screw (Load) 100 A
910 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
J11 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector
w/ Pressure Plate (Load) 100 A
10 MOUNTING/BARRIERS
BACK CONNECTED (FRONT MOUNTED ONLY)
Mounting Inserts
A 6-32
B ISO M3
FRONT CONNECTED (BACK MOUNTED ONLY)14
Back Mounting Foot Type Front Mounting Inserts (Optional Use)
C Short 6-32
D Short ISO M3
E Long 6-32
F Long ISO M3
3 POLES1
1 One
2 Two
3 Three
4 Four
5 Five
6 Six
4 CIRCUIT2
A3 Switch Only (no coil)
B Series Trip (current)
C Series Trip (voltage)
D Shunt Trip (current)
E Shunt Trip (voltage)
F Relay Trip (current)
G Relay Trip (voltage)
5 AUXILIARY SWITCH4
0 without Auxiliary Switch
2 S.P.D.T. 0.110 Q.C. Terminals
3 S.P.D.T. 0.139 Solder Lug
4 S.P.D.T. 0.110 Q.C. Terminals
(Gold Contacts)
6 S.P.D.T. 0.110 Q.C. Terminals
7 S.P.D.T. 0.110 Q.C. Terminals
(Gold Contacts)
8 S.P.D.T. 0.187 Q.C. Terminals
9 S.P.D.T. 0.187 Q.C. Terminals
6 FREQUENCY & DELAY
033 DC 50/60Hz, Switch Only
105 DC Instantaneous
12 DC Short
14 DC Medium
16 DC Long
205 50/60Hz Instantaneous
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
36 DC, 50/60Hz Long
62 50/60Hz Short, Hi-Inrush
64 50/60Hz Medium, Hi-Inrush
66 50/60Hz Long, Hi-Inrush
72 DC, Short,Hi-Inrush
74 DC,Medium, Hi-Inrush
76 DC, Long, Hi-Inrush
926 DC, 50/60Hz Short, Hi-Inrush
946 DC, 50/60Hz Medium,
Hi-Inrush
966 DC, 50/60Hz Long, Hi-Inrush
11 MAXIMUM APPLICATION RATING15
12 AGENCY APPROVAL
B
D
UL 1077 / UL508 Recognized & CSA Accepted
UL 1077 Recognized, CSA Accepted, & VDE Certied
9
Actuator
Color
10
Mounting/
Barriers
11
Maximum
Application
Rating
9 ACTUATOR COLOR & LEGEND13
Acuator Color
White
Black
Red
Green
Blue
Yellow
Gray
Orange
Legend Color
Black
White
White
White
White
Black
Black
Black
I-O
A
C
F
H
K
M
P
R
ON-OFF
B
D
G
J
L
N
Q
S
Dual
1
2
3
4
5
6
7
8
A 65 VDC, 120 A
B 125 VDC, 120 A
C 120/240 VAC, 100 A
D 240 VAC, 100 A
E16 277/480 VAC, 100 A
F 277 VAC, 100 A
G16 600 VAC, 100 A
H16 480 VAC, 100 A
J16 415 VAC, 100 A
L16 160 VDC, 100 A
T 125 VDC/240 VAC, 100 A
W16 125 VDC/415 VAC, 100 A
Notes:
1 VDE approval on 1-5 poles only. Standard multi-pole units identical poles except when
specifying auxiliary switch - (see Note 4). For mixed ratings, consult factory.
2 Switch Only & Series Trip construction available w/either front or back connected terminals.
Shunt construction available w/back connected terminals, (Terminal Codes 1 & 2) only.
Circuit Codes B,C & D are VDE approved.
3 Switch Only construction: 30 amps or less select Current Rating Code 630; 31-70 amps,
select Current Rating code 670; 71-100 amps, select Current Rating Code 810; 101-125
amps Select Current Rating Code 912. Switch Only is VDE approved only if tied to a
protected pole.
4 Auxiliary Switch available on Switch Only and Series Trip units. On multi-pole units, only
one auxiliary switch is normally supplied mounted in the extreme right pole. Back mounted
units require special mounting provisions when auxiliary switch is specied. VDE approval
on Auxilary Switch Codes 0,2,3 & 4 only.
5 Voltage Trip Coils are not rated for continuous duty. Available only with Frequency & Delay
Codes 10 & 20. Series Trip construction with a voltage coil s VDE approved only if tied to
a protected pole.
6 Frequency & Delay Codes 92,94 & 96 are not VDE Certied.
7 Current Coil Ratings 0.100 - 100 ams are VDE Certied.
8 125 A rating (Code 912) available as a Switch Only (Circuit Code A), rated 125 VDC (Code B).
9 An Anti-Flash Over Barrier is supplied between poles on multi-pole units with 10-32 (Terminal
Code 1). 1/4-20 (Code 2), M5 (Code A), and M6 (Code B) terminals per UL requirement.
10 Box Wire Connector will accept #14 through 0 AWG. copper wire or #12 through 0 AWG.
aluminum wire.
11 Box Wire Connector with Pressure Plate for stranded wire, consult factory for details.
12 Terminal Codes A,B,D,E,G & H are not VDE Certied.
13 VDE approvals require Dual (I-O, ON-OFF) or I-O markings on all handles.
14 Back Mounted breakers can also be front mounted by utilizing the proper front panel mounting
inserts normally supplied. However, terminal connections must be made prior to mounting.
15 Application ratings B,D,J,T & W are available with VDE.
16 415, 480 & 600 VAC ratings require 3 or 4 pole break 3Ø and 2 pole break 1Ø.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
6 |E-Series Handle UL Listed – Ordering Scheme
7 CURRENT RATING (AMPERES)7
OR VOLTAGE COIL (MIN. TRIP RATING, VOLTS)5
020 0.020
025 0.025
030 0.030
035 0.035
040 0.040
045 0.045
050 0.050
055 0.055
060 0.060
065 0.065
070 0.070
075 0.075
080 0.080
085 0.085
090 0.090
090 0.095
210 0.100
215 0.150
220 0.200
225 0.250
230 0.300
235 0.350
240 0.400
245 0.450
250 0.500
255 0.550
260 0.600
265 0.650
270 0.700
275 0.750
280 0.800
285 0.850
290 0.900
295 0.950
410 1.000
512 1.250
415 1.500
517 1.750
420 2.000
522 2.250
425 2.500
527 2.750
430 3.000
435 3.500
440 4.000
445 4.500
450 5.000
455 5.500
460 6.000
465 6.500
470 7.000
475 7.500
480 8.000
485 8.500
490 9.000
495 9.500
610 10.000
710 10.500
611 11.000
711 11.500
612 12.000
712 12.500
613 13.000
614 14.000
615 15.000
616 16.000
617 17.000
618 18.000
620 20.000
622 22.000
624 24.000
625 25.000
630 30.000
635 35.000
640 40.000
650 50.000
660 60.000
670 70.000
680 80.000
690 90.000
810 100.000
811 110.000
812 120.000
9128 125.000
CODE AMPERES
A06 6 DC, 5 DC
A12 12 DC, 10 DC
A18 18 DC, 15 DC
A24 24 DC, 20 DC
A32 32 DC, 25 DC
A48 48 DC, 40 DC
A65 65 DC, 55 DC
B25 125 DC, 100 DC
J06 6 AC, 5 AC
J12 12 AC, 10 AC
J18 18 AC, 15 AC
J24 24 AC, 20 AC
J48 48 AC, 40 AC
J65 65 AC, 55 AC
K20 120 AC, 65 AC
L40 240 AC, 130 AC
1
Series
2
Actuator
3
Poles
6
Frequency
& Delay
7
Current Rating
8
Terminal
12
Agency
Approval
4
Circuit
5
Auxiliary
Switch
E A B 0 1 A2 2 CC24 450
1 SERIES
E
2 ACTUATOR
A Handle, one per pole
8 TERMINAL7
BACK CONNECTED (FRONT MOUNTED ONLY) MAX. RATING
18 10-32 Stud (All Terminals) 50 A
28 1/4-20 Stud (All Terminals) 125 A
FRONT CONNECTED (BACK MOUNTED ONLY) MAX. RATING
39 Box Wire Connector (Line & Load) 100 A
C10 Box Wire Connector w/ Pressure Plate (Line & Load) 100 A
4 10-32 Screw (Line & Load) 50 A
5 10-32 “Bus-Type” Screw (Line), 10-32 Screw (Load) 50 A
69 10-32 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
F10 10-32 “Bus-Type” Screw (Line), Box Wire Connector
w/ Pressure Plate (Load) 100 A
7 1/4-20 Screw (Line & Load) 125 A
8 1/4-20 “Bus-Type” Screw (Line), 1/4-20 Screw (Load) 100 A
99 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector (Load) 100 A
J10 1/4-20 “Bus-Type” Screw (Line), Box Wire Connector
w/ Pressure Plate (Load) 100 A
10 MOUNTING/BARRIERS
BACK CONNECTED (FRONT MOUNTED ONLY)
Mounting Inserts
A 6-32
B ISO M3
FRONT CONNECTED (BACK MOUNTED ONLY)11
Back Mounting Foot Type Front Mounting Inserts (Optional Use)
C Short 6-32
D Short ISO M3
E Long 6-32
F Long ISO M3
3 POLES1
1 One
2 Two
3 Three
4 Four
5 Five
6 Six
4 CIRCUIT2
B Series Trip (current)C3 Series Trip (voltage)
5 AUXILIARY SWITCH4
0 without Auxiliary Switch
2 S.P.D.T. 0.110 Q.C. Terminals
3 S.P.D.T. 0.139 Solder Lug
4 S.P.D.T. 0.110 Q.C. Terminals
(Gold Contacts)
6 S.P.D.T. 0.110 Q.C. Terminals
7 S.P.D.T. 0.110 Q.C. Terminals
(Gold Contacts)
8 S.P.D.T. 0.187 Q.C. Terminals
9 S.P.D.T. 0.187 Q.C. Terminals
6 FREQUENCY & DELAY
105 DC Instantaneous
12 DC Short
14 DC Medium
16 DC Long
205 50/60Hz Instantaneous
22 50/60Hz Short
24 50/60Hz Medium
26 50/60Hz Long
30 DC, 50/60Hz Instantaneous
32 DC, 50/60Hz Short
34 DC, 50/60Hz Medium
36 DC, 50/60Hz Long
62 50/60Hz Short, Hi-Inrush
64 50/60Hz Medium, Hi-Inrush
66 50/60Hz Long, Hi-Inrush
72 DC, Short,Hi-Inrush
74 DC,Medium, Hi-Inrush
76 DC, Long, Hi-Inrush
926 DC, 50/60Hz Short, Hi-Inrush
946 DC, 50/60Hz Medium,
Hi-Inrush
966 DC, 50/60Hz Long, Hi-Inrush
11 MAXIMUM APPLICATION RATING
12 AGENCY APPROVAL
C
F
UL 489 Listed & CSA Certied
UL 489 Listed, CSA Certied, & VDE Certied
9
Actuator
Color
10
Mounting/
Barriers
11
Maximum
Application
Rating
9 ACTUATOR COLOR & LEGEND12
Acuator Color
White
Black
Red
Green
Blue
Yellow
Gray
Orange
Legend Color
Black
White
White
White
White
Black
Black
Black
ON-OFF
B
D
G
J
L
N
Q
S
Dual
1
2
3
4
5
6
7
8
1 120 VAC
B 125 VDC, 120 A
C13 120/240 VAC, 100 A
D 240 VAC, 100 A
Notes:
1 Standard multi-pole units identical poles except when specifying auxiliary switch -
(see Note 4). For mixed ratings, consult factory. VDE Certication on 1-5 poles only.
2 Series Trip construction available w/either front or back connected terminals.
3 Series Trip construction with a voltage coil is not available as a single pole unit and must be
tied to a protected pole.
4 On multi-pole units, only one auxiliary switch is normally supplied mounted in the extreme
right pole per Figure A. Back mounted units require special mounting provisions when
auxiliary switch is specied. VDE Certication on auxilary switch codes 0, 2, 3 & 4 only.
5 Voltage Trip Coils are not rated for continuous duty. Available only with Frequency & Delay
Codes 10 & 20.
6 Frequency & Delay Codes 92, 94 & 96 are not VDE Certied.
7 Current Ratings under 0.100 amps are not VDE Certied .
8 An Anti-Flash Over Barrier is supplied between poles on multi-pole units with 10-32 Stud
(Terminal Code 1) or 1/4-20 Stud (Code 2) terminals per UL requirement.
9 Box Wire Connector will accept #14 through 0 AWG. copper wire or #12 through 0 AWG.
aluminum wire.
10 Box Wire Connector with Pressure Plate for stranded wire, consult factory for details.
11 Back Mounted breakers can also be front mounted by utilizing the proper front panel mouning
inserts normally supplied. However, terminal connections must be made prior to mounting.
12 VDE Certication requires dual (I-O , ON-OFF) markings on all handles.
13 Not available with VDE Certication.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
| 7 E-Series Handle – Circuit & Terminal Diagrams
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
3 0-50 amps: 10-32 & M5 Studs .625±.062/15.88±1.574 long.
4 51-120 amps: 1/4-20 & M6 Studs .750±.062/19.05±1.574 long.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
8 |E-Series Handle (Back Connected) – Form & Fit Drawings
Notes:
1 1/4 -20 stud terminal in Series Trip circuit conguration shown.
2 A 3” min spacing must be provided between the circuit breaker arc venting area
of back connected E-Series circuit breaker and grounded obstructions.
3 All dimensions are in inches [millimeters].
4 Tolerance ±.020 [.51] unless otherwise specied.
5 Circuit breakers must be mounted on vertical surface.
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
60 Johnson Avenue • Plainville, CT 06062–1177 • Phone: (860) 793–9281 • Fax: (860) 793–9231
Email: sales@carlingtech.com • www.carlingtech.com
| 9 E-Series Handle (Front Connected) – Form & Fit Drawings
Notes:
1 All dimensions are in inches [millimeters].
2 Tolerance ±.020 [.51] unless otherwise specied.
3 Box wire connector terminal in Series Trip circuit conguration shown.
4 Circuit breakers must be mounted on vertical surface. REV_CB_E_0812