APPLIED
POWER
SYSTEMS,
INC.
IAP150T120 SixPac™
150A / 1200V 3-phase Bridge IGBT Inverter
IAP150T120 SixPac™ FEATURES INCLUDE
Multi-Function Power Assembly
Compact Size – 9.0” H X 11.0” W X 17.6” D
DC Bus Voltages to 850VDC
Snubber-less operation to 650VDC
Switching frequen cies to over 2 0kHz
Protective circuitry with fail-safe opto-isolated fault
annunciation, including:
Over current
Over voltage
Short circuit
P.S. undervoltage
Over Temperature
Opto-isolated or fiber-optic gate drive and fault signal
output for electrical isolation and noise immunity
Integrated cooling with temp erature sensors and feed back
Many options - Available with IGBTs from 75A to 1200A
Configurable Power
The IAP150T120 SixPac is a flexible, highly integrated
IGBT based power assembly with a wide range of
applications. These include inverters for motor controls,
switch mode power supplies (SMPS), UPS, welders, etc.
The IAP150T120 SixPac can be operated at
frequencies to over 20kHz. The IAP150T120 SixPac is
configured as a three-phase bridge inverter mounted on
an air-cooled or liquid-cooled heat sink. Configurations
include options for (full, half or no control) converter
input circuitry, inverter output circuitry, cooling and a
wide variety of drivers and safety features for the
converter front end and IGBT inverter output stage.
To operate at high switching frequencies, the
IAP150T120 SixPac utilizes a low inductance
laminated bus structure, optically isolated or fiber
optically coupled gate drive interfaces, isolated gate
power supplies and a DC-link capacitor bank.
The IAP150T120 SixPac provides built in protection
features including: overvoltage, undervoltage lockout,
overcurrent, overtemperature, short circuit and optional
airflow or liquid flow indicators.
Flexibility is a key feature of the IAP150T120 SixPac.
Options include: a choice of converter front ends,
rectifier, half or full SCR control, with or without SCR
gate firing boards and soft-start circuitry. A choice of
cooling methods, forced air or liquid is also available.
Customer provided PWM is optically coupled or a fiber
optic link can be provided to the IGBT interface. Current
feedback is provided by Hall effect current transducers.
The IAP150T120 SixPac is rated to maximum input
voltages up to 850 VDC, switching frequencies to over
20kHz, includes many safety features to protect the
IGBTs and output circuitry and can be configured to
meet your application.
Shown with AC-DC Converter
Schematic:
124 Charlotte Avenue Hicksville, NY 1180 1 Ph: 516.935.2230 Fax: 516.935.2603 Website: www.appliedps.com
Page 1 of 6
Rev. 120706-01
APPLIED
POWER
SYSTEMS,
INC.
IAP150T120 SixPac™
150A / 1200V 3-phase Bridge IGBT Inverter
SixPac™ IAP150T120
Absolute Maximum Ratings – TJ=25°C unless otherwise specified
General Symbol Value Units
IGBT Junction Temperature TJ-40 to +150 °C
Storage Temperature TSTG -40 to +125 °C
Operating Temperature TOP -25 to +85 °C
Voltage applied to DC terminals VCC 850 Volts
Isolation voltage, AC 1 minute, 60Hz sinusoidal VISO 2500 Volts
IGBT Inverter
Collector Current (TC=25°C) IC150 Amperes
Peak Collector Current (TJ<150°C) ICM 300 Amperes
Emitter Current IE150 Amperes
Peak Emitter Current IEM 300 Amperes
Maximum Collector Dissipation (TJ<150°C) PCD 520 Watts
Gate Drive Board
Unregulated +24V Power Supply 30 Volts
Regulated +15V Power Supply 18 Volts
PWM Signal Input Voltage 20 Volts
Fault Output Supply Voltage 30 Volts
Fault Output Current 50 mA
IGBT Inverter Electrical Characteristics, TJ=25°C u nless otherwise specified
Parameter Symbol Test Conditions Min Typ Max Units
Collector Cutoff Current ICES VCE=VCES, VGE=0V - - 1 mA
IC=150A, TJ=25°C - 1.8 2.4 Volts
Collector-Emitter Saturation Voltage VCE(sat) IC=150A, TJ=125°C - 1.9 - Volts
Emitter-Collector Voltage VEC IE=100A - - 3.2 Volts
td(on) - - 150 ηs
tr- - 80 ηs
td(off) - - 450 ηs
Inductive Load Switching Times
tr- - 300 ηs
Diode Reverse Recovery Time Trr - - 150 ηs
Diode Reverse Recovery Charge Qrr
VCC=600V
IC=100A
VGE=15V
RG=3.1
- 6.0 - µC
DC Link Capacitance - 3300 - µF
Thermal and Mechanical Parameters
Parameter Symbol Test Conditions Min Typ Max Units
IGBT Thermal Resistance, Junction to Case RΘ(j-c) Per IGBT ½ module - 0.11 0.21 °C/W
FWD Thermal Resistance, Junction to Case RΘ(j-c) Per FWD ½ module - - 0.24 °C/W
Heatsink Thermal Resistance RΘ(s-a) 1500 LFM airflow - .045 - °C/W
Mounting Torque, AC terminals - 75 90 In-lb
Mounting Torque, DC terminals - 130 150 In-lb
Mounting Torque, case mounting - 130 150 In-lb
Weight - 21 - lb
124 Charlotte Avenue Hicksville, NY 1180 1 Ph: 516.935.2230 Fax: 516.935.2603 Website: www.appliedps.com
Page 2 of 6
Rev. 120706-01
APPLIED
POWER
SYSTEMS,
INC.
IAP150T120 SixPac™
150A / 1200V 3-phase Bridge IGBT Inverter
Gate Drive Board Electrical Characteristics
Parameter Min Typ Max Units
Unregulated +24V Power Supply 20 24 30 Volts
Regulated +15V Power Supply 14.4 15 18 Volts
PWM Input On Threshold 12 15 - Volts
PWM Inout Off Threshold - 0 2 Volts
Output Overcurrent Trip - 225 - Amperes
Overtemperature Trip 89 91 93 °C
Overvoltage Trip - 900 - Volts
DC Link Voltage Feedback See Figure Below Volts
Heatsink Temperature Feedback See Figure Below Volts
Output Current Feedback See Figure Below Volts
DC Link Feedback
0
100
200
300
400
500
600
700
800
900
1000
012345678910
Feedback Voltage (Volts)
DC Link Voltage (Volts)
Heatsi nk Temperat ure Feedb ack
0
10
20
30
40
50
60
70
80
90
100
110
120
012345678910
Feedback Voltage (Volts)
Heatsink Temperature (°C)
O ut put Cur
-225
-187.5
-150
-112.5
-75
-37.5
0
37.5
75
112.5
150
187.5
225
-6 -5 -4 -3 -2
Feed
Ou tp u t Cur r en t (Amp s)
re nt Fe edbac k
-1 0 1 2 3 4 5 6
ba ck Voltage (Volts)
124 Charlotte Avenue Hicksville, NY 1180 1 Ph: 516.935.2230 Fax: 516.935.2603 Website: www.appliedps.com
Page 3 of 6
Rev. 120706-01
APPLIED
POWER
SYSTEMS,
INC.
IAP150T120 SixPac™
150A / 1200V 3-phase Bridge IGBT Inverter
Performance Curves
S ixPac™ 150 Am p T h ree Phase
40
50
60
70
80
90
100
110
120
50 60 70 80 90 100 110 120 130 140 150
Ou t p u t Cu r r en t RM S
Heatsi nk T emper atur e
10 KHz
5 KHz
1 KHz
OVT
Conditions Symbol Value Units
Ambient Temperature TA40 °C
DC Bus Voltage VCC 600 Volts
Load Power Factor COS Φ 0.8
IGBT Saturation Voltage VCE(sat) Typical @ TJ=125°C Volts
IGBT Switching Loss ESW Typical @ TJ=125°C mJ
Airflow - 1500 LFM
Switching Conditions 3-phase PWM, 60Hz sinusoidal output
124 Charlotte Avenue Hicksville, NY 1180 1 Ph: 516.935.2230 Fax: 516.935.2603 Website: www.appliedps.com
Page 4 of 6
Rev. 120706-01
APPLIED
POWER
SYSTEMS,
INC.
IAP150T120 SixPac™
150A / 1200V 3-phase Bridge IGBT Inverter
Interface
Pin # Signal Name Description
1 Shield Connected to circuit ground
2 PWM A- 0-15V signal controlling the duty cycle of A- IGBT
3 Phase A Error1Open collector output, external pull-up resistor required.
LOW=No Error; Floating=Phase A overcurrent or short circuit
4 PWM A+ 0-15V signal controlling the duty cycle of A+ IGBT
5 PWM B- 0-15V signal controlling the duty cycle of B- IGBT
6 Phase B Error1Open collector output, external pull-up resistor required.
LOW=No Error; Floating=Phase B overcurrent or short circuit
7 PWM B+ 0-15V signal controlling the duty cycle of B+ IGBT
8 PWM C- 0-15V signal controlling the duty cycle of C- IGBT
9 Phase C Error1Open collector output, external pull-up resistor required.
LOW=No Error; Floating=Phase C overcurrent or short circuit
10 PWM C+ 0-15V signal controlling the duty cycle of C+ IGBT
11 OverTemp1Open collector output, external pull-up resistor required.
LOW=No Error; Floating=Heatsink overtemp
12 Not Connected
13 DC Link Voltage Analog voltage representation of DC link voltage
14 24VDC Input Power220-30VDC input voltage range
15 24VDC Input Power220-30VDC input voltage range
16 15VDC Input Power214.4-18VDC input voltage range
17 15VDC Input Power214.4-18VDC input voltage range
18 GND Ground reference for 15 and 24VDC inputs
19 GND Ground reference for 15 and 24VDC inputs
20 Heatsink Temperature Analog voltage representation of heatsink temperature
21 GND3Tied to pins 18 and 19
22 IOUT Phase A Analog voltage representation of phase A output current
23 GND3Tied to pins 18 and 19
24 IOUT Phase B Analog voltage representation of phase B output current
25 GND3Tied to pins 18 and 19
26 IOUT Phase C Analog voltage representation of phase C output current
NOTES:
1. Open collectors can be pulled up to 30VDC Max and sink 50mA continuous.
2. DO NOT connect a 15VDC and 24VDC source to the unit at the same time. Use one or the other.
3. GND signals to be used for analog feedback signals, i.e. twisted pair with IOUT Phase A.
Gate Drive Interface Connector
Description Symbol Type Manufacturer
Gate Drive Interface Header J1 0.100” x 0.100” latching header, 26 pin 3M #3429-6002 or equivalent
Recommending Mating Socket - 0.100” x 0.100” IDC socket, 26 pin 3M #3399-7600 or equivalent
Recommended Strain Relief - Plastic strain relief 3M #3448-3026 or equivalent
124 Charlotte Avenue Hicksville, NY 1180 1 Ph: 516.935.2230 Fax: 516.935.2603 Website: www.appliedps.com
Page 5 of 6
Rev. 120706-01
APPLIED
POWER
SYSTEMS,
INC.
IAP150T120 SixPac™
150A / 1200V 3-phase Bridge IGBT Inverter
Mechanical Information
124 Charlotte Avenue Hicksville, NY 1180 1 Ph: 516.935.2230 Fax: 516.935.2603 Website: www.appliedps.com
Page 6 of 6
Rev. 120706-01