SIMATIC WinAC MP 2008
_
_____________
_
_____________
_
_____________
_
_____________
_
_____________
_
_____________
_
_____________
_
_____________
Preface 1
Product overview
2
Steps for installing and
removing
3
STEP 7 configuration and
communication options
4
Controlling a process with
WinAC MP
5
Setting up WinAC MP for
your application
6
Examples of configuring
objects
7
Performance features and
technical specifications
A
SIMATIC
WinAC MP 2008
Operating Instructions
03/2009
A5E00981151-02
Legal information
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken.
CAUTION
without a safety alert symbol, indicates that property damage can result if proper precautions are not taken.
NOTICE
indicates that an unintended result or situation can occur if the corresponding information is not taken into
account.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The device/system may only be set up and used in conjunction with this documentation. Commissioning and
operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes
in this documentation qualified persons are defined as persons who are authorized to commission, ground and
label devices, systems and circuits in accordance with established safety practices and standards.
Proper use of Siemens products
Note the following:
WARNING
Siemens products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be adhered to. The information in the relevant documentation must be observed.
Trademarks
All names identified by ® are registered trademarks of the Siemens AG. The remaining trademarks in this
publication may be trademarks whose use by third parties for their own purposes could violate the rights of the
owner.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
Siemens AG
Industry Sector
Postfach 48 48
90026 NÜRNBERG
GERMANY
A5E00981151-02
Ⓟ 02/2009
Copyright © Siemens AG 2009.
Technical data subject to change
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 3
Table of contents
1 Preface ...................................................................................................................................................... 5
2 Product overview ..................................................................................................................................... 11
2.1 Product overview .........................................................................................................................11
2.2 Scope of delivery .........................................................................................................................13
2.3 Essential system characteristics of WinAC MP 2008 ..................................................................14
3 Steps for installing and removing............................................................................................................. 15
3.1 Requirements for installation .......................................................................................................15
3.2 Hardware and software requirements..........................................................................................16
3.3 Installation steps ..........................................................................................................................18
3.3.1 Installing WinAC MP ....................................................................................................................18
3.3.2 Connecting the configuration computer to the HMI device..........................................................20
3.3.2.1 Basics of transfers .......................................................................................................................20
3.3.2.2 Transfer over Industrial Ethernet .................................................................................................21
3.3.2.3 Transfer over PROFIBUS ............................................................................................................23
3.3.2.4 Transfer via USB..........................................................................................................................24
3.3.2.5 Transfer using automatic transfer detection ................................................................................25
3.3.3 Transferring WinAC MP to the HMI device..................................................................................26
3.3.4 Licensing WinAC MP on the HMI device .....................................................................................27
3.4 Steps when removing ..................................................................................................................29
3.4.1 Retransferring license keys..........................................................................................................29
3.4.2 Uninstalling WinAC MP on the HMI device..................................................................................31
3.4.3 Uninstalling WinAC MP on the configuration PC.........................................................................31
4 STEP 7 configuration and communication options................................................................................... 33
4.1 Standard procedure for communication with WinAC MP ............................................................33
4.2 Creating a STEP 7 project for WinAC MP ...................................................................................34
4.2.1 Configuring the SIMATIC HMI station and the PROFIBUS-DP network .....................................34
4.2.2 Creating a connection between WinAC MP and WinCC flexible Runtime on the HMI
device...........................................................................................................................................39
4.2.3 Time synchronization WinAC MP ................................................................................................41
4.2.4 Configuring retentive data............................................................................................................42
4.2.5 WinCC flexible direct keys in WinAC MP.....................................................................................44
4.3 Configuring an Ethernet connection for routing functionality over the HMI device......................47
4.3.1 Setting the communication functions for the configuration PC ....................................................47
4.4 Checking and downloading a STEP 7 project to WinAC MP.......................................................49
4.4.1 Checking the WinAC MP online connection ................................................................................49
4.4.2 Downloading the configurations...................................................................................................50
4.5 Communication options with WinAC MP .....................................................................................53
Table of contents
WinAC MP 2008
4 Operating Instructions, 03/2009, A5E00981151-02
5 Controlling a process with WinAC MP ..................................................................................................... 57
5.1 Integrating the WinAC MP System Library ................................................................................. 57
5.2 Description of the Home Screen and the Tuning Screen ........................................................... 59
5.2.1 Description of the Home screen.................................................................................................. 59
5.2.2 Description of the Tuning screen ................................................................................................ 61
5.3 Function key assignment based on the WinAC system library................................................... 63
5.3.1 Operating the WinAC MP with hotkeys....................................................................................... 63
5.3.2 Starting WinAC MP - Start .......................................................................................................... 64
5.3.3 Automatic WinAC MP startup - Autostart.................................................................................... 64
5.3.4 Automatic WinAC MP start when the HMI device boots - StartAtBoot ....................................... 65
5.3.5 RUN and STOP modes............................................................................................................... 67
5.3.6 Memory reset with MRES ........................................................................................................... 69
5.3.7 Status indicators.......................................................................................................................... 70
5.3.8 Composition of the cycle time ..................................................................................................... 72
5.3.9 Setting the "HMI enable time" ..................................................................................................... 73
5.4 Archiving and restoring STEP 7 user programs.......................................................................... 74
5.4.1 Conditions for archiving and restoring ........................................................................................ 74
5.4.2 Creating an archive file - Archive ................................................................................................ 76
5.4.3 Restoring an archive file - Restore.............................................................................................. 77
5.5 Exit WinAC MP on the HMI device - Shutdown .......................................................................... 77
6 Setting up WinAC MP for your application ............................................................................................... 79
6.1 Working with WinCC flexible....................................................................................................... 79
6.2 WinAC MP functions ................................................................................................................... 80
7 Examples of configuring objects .............................................................................................................. 83
7.1 Configuration of the RUN button with corresponding LED display using WinCC flexible........... 83
7.2 Configuring a histogram.............................................................................................................. 86
A Performance features and technical specifications .................................................................................. 93
A.1 Performance features.................................................................................................................. 93
A.2 Specifications .............................................................................................................................. 93
A.2.1 Order numbers ............................................................................................................................ 93
A.2.2 Technical specifications .............................................................................................................. 94
A.3 Supported OBs............................................................................................................................ 98
A.3.1 OBs for the main cycle of the program and for cold and warm restarts ..................................... 98
A.3.2 Supported organization blocks (OBs) ......................................................................................... 99
A.4 Supported SFCs........................................................................................................................ 100
A.5 Supported SFBs........................................................................................................................ 103
A.6 System status list (SSL) ............................................................................................................ 104
Glossary ................................................................................................................................................ 109
Index...................................................................................................................................................... 119
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 5
Preface 1
Purpose of this documentation
This documentation provides you with detailed information on the Windows Automation
Center 2008 for Multi Panel or simply WinAC MP 2008.
Tip
In the following pages WINAC MP 2008 will be referred to as WINAC MP.
WinAC MP is an S7 software PLC for the MP 177, MP 277 and MP 377 Multi Panels.
WinAC MP runs under Windows CE.
WinAC MP can be operated on the following Multi Panel HMI device types:
MP 177 6" Touch
MP 277 8" Touch and Key
MP 277 10" Touch and Key
MP 377 12" Touch and Key
MP 377 15" Touch
MP 377 19" Touch
Required basic knowledge
General knowledge about automation engineering and process communication is needed to
understand this documentation.
In addition, the following knowledge is required:
Comprehensive knowledge of WinCC flexible
Comprehensive knowledge of STEP 7
Validity of the documentation
This documentation is valid for WinAC MP 2008.
Requirement for installation
WinCC flexible 2008 SP1 should be installed.
Location of documentation
When you install WinAC MP, the documentation is stored on the configuration PC.
The PDF file: You can open the WinAC_MP_en.pdf file on the configuration PC with the
menu command: Start > SIMATIC > Documentation > English > WinAC MP 2008
Preface
WinAC MP 2008
6 Operating Instructions, 03/2009, A5E00981151-02
Upgrade from WinAC MP 2007 to WinAC MP 2008
If you already have WinAC MP 2007 you can download a free upgrade from the Internet.
To confirm that you are authorized to download this free upgrade, please state the license
number of your original WIN MP 2007 (customs and shipping costs may arise outside the
EU). For details of the license number valid for your product, please refer to your software
product certificate.
For additional information about this upgrade, refer to Internet
(http://support.automation.siemens.com/WW/view/en/31929448):
Getting Started Video with image and sound, duration: approx. 6 minutes (D/E)
The Getting Started Video shows:
the advantages of the WinAC MP software PLC
how easy it is to configure WinAC MP
You will find the Getting Started Video on the Internet
(http://support.automation.siemens.com/WW/view/en/32010673)
Conventions
Configuration and runtime software have different names as follows:
"WinCC flexible 2008 SP1" denotes the configuration software.
The term "WinCC flexible" is used in a general context. The full name, for example,
"WinCC flexible 2008 SP1", is always used when it is necessary to differentiate between
different versions of the configuration software.
"WinCC flexible Runtime" refers to the runtime software that can run on the HMI device.
Please observe notes labeled as follows:
Note
Notes contain important information concerning the product, its use or a specific section of
the documentation to which you should pay particular attention.
"WinAC MP" is the name of a software PLC that can run on the Multi Panel HMI device
types listed above along with WinCC flexible 2008 SP1.
Preface
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 7
Registered trademarks
Names labeled with a ® symbol are registered trademarks of the Siemens AG. Other names
used in this documentation may be trademarks, the use of which by third parties for their
own purposes could violate the rights of the owner.
SIMATIC®
STEP 7®
WinAC®
HMI®
SIMATIC HMI®
SIMATIC ProTool®
SIMATIC WinCC®
SIMATIC WinCC flexible®
SIMATIC MP 177®
SIMATIC MP 277®
SIMATIC MP 377®
SIMATIC Multi Panel®
Standards
WinAC MP complies with the requirements and criteria of IEC 61131-3.
Preface
WinAC MP 2008
8 Operating Instructions, 03/2009, A5E00981151-02
Position in the information landscape
This documentation is part of the SIMATIC and SIMATIC HMI documentation. This
documentation describes all the information specifically relating to WinAC MP. You will find
more information in the following manuals:
STEP 7 - Programming with STEP 7
Provides basic information on designing and programming a STEP 7 user program. This
manual is available on a PC with STEP 7.
STEP 7 - System and Standard Functions for S7-300 and S7-400
Describes the system functions, organization blocks and loadable standard functions
available for programming a STEP 7 user program. This manual is available on a PC with
STEP 7.
STEP 7 - Getting Started with STEP 7
Explains the use and functions of the STEP 7 automation software, the procedures during
configuration and the development of STEP 7 user programs. This manual is available on
a PC with STEP 7.
STEP 7 - Statement List for S7-300 and S7-400
Provides a full list of the statements that can be used for WinAC MP. This manual is
available on a PC with STEP 7.
Operating instructions for SIMATIC HMI devices
MP 177
MP 277
MP 377
WinCC flexible Compact/Standard/Advanced User's Manual
Describes basic principles of configuration using the WinCC flexible Compact
/WinCC flexible Standard/WinCC flexible Advanced engineering systems.
WinCC flexible Runtime User Manual
Describes how to commission and operate your runtime project on a PC.
WinCC flexible Migration User's Manual
Describes how to convert an existing ProTool project to WinCC flexible.
Describes how to convert an existing WinCC project to WinCC flexible.
Describes how to convert an existing ProTool project including a change of HMI
device, for example, from OP3 to OP 73.
Describes how to convert an existing ProTool project including a change from a
graphics device to a Windows CE device.
Communication User's Manual
Communication Part 1 describes the connection of the HMI device to SIMATIC PLCs.
Communication Part 2 describes the connection of the HMI device to third-party PLCs.
Getting started
WinCC flexible, Getting Started - First Time User
Based on an example project, this is a step-by-step introduction to the basics of
configuring screens, alarms, recipes and screen navigation.
WinCC flexible, Getting Started - Power User
Based on an example project, this is a step-by-step introduction to the basics of
configuring logs, project reports, scripts, user management, multilingual projects and
integration in STEP 7.
WinCC flexible, Getting Started - Options
Based on an example project, this is a step-by-step introduction to the basics of
configuring the WinCC flexible Sm@rtService, Sm@rtAccess and OPC server options.
Preface
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 9
Guide to the manual
This documentation contains the following aids that will allow you to find the specific
information you need quickly:
At the beginning of the documentation you will find a full table of contents.
Following the appendix, you will find a glossary with definitions of the most important
terminology.
At the end of the documentation, there is a comprehensive index with which you can
locate the information you are looking for.
Additional support
If you have any questions about the products described in this manual, please contact your
Siemens representative.
You will find your contact person (http://www.siemens.com/automation/partner) here.
You will find a guide to the technical documents for the various SIMATIC products and
systems (http://www.siemens.com/simatic-tech-doku-portal) on the Internet.
Here, you will find the online catalog and the online ordering system
(https://mall.automation.siemens.com/en/guest/).
Training center
We offer various courses for newcomers to the SIMATIC S7 automation system. Contact
your regional Training Center, or the central Training Center in D-90327 Nuremberg,
Germany.
Additional information can be found on the Internet (http://www.sitrain.com)
Technical support
You can contact Technical Support for all A&D products by means of the Web form
(http://www.siemens.com/automation/service)
You can find more information on our technical support
(http://www.siemens.com/automation/service) on the Internet.
Service & Support on the Internet
In addition to our documentation, we offer our complete knowledge base at the Internet
address (http://www.siemens.com/automation/service&support).
There you can find:
Our newsletter containing up-to-date information on your products.
The documents you need via our Search function in Service & Support.
A forum for global information exchange by users and specialists.
Your local Automation & Drives representative.
Information about on-site service, repairs, spare parts, and more.
Preface
WinAC MP 2008
10 Operating Instructions, 03/2009, A5E00981151-02
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 11
Product overview 2
2.1 Product overview
Definition of embedded
An embedded system:
is a combination of hardware and software providing the flexibility of software with the
performance of rugged hardware.
has precisely defined tasks; it forms a functional software and hardware unit that only
performs predefined tasks.
Embedded automation with WinAC MP
SIMATIC Embedded Automation combines SIMATIC control technology
(WinAC MP) and WinCC flexible visualization on the Multi Panels.
These are based on Windows CE and have no hard disks, making them extremely rugged
platforms.
The Multi Panels have an operating system intended for embedded applications that needs
little user memory and meets real-time and deterministic demands.
WinAC MP is the cost-effective solution for small and medium-sized applications and
automation tasks
The Multi Panels are ideal for use in harsh industrial environments thanks to their
ruggedness and compact design.
'ULYHV
6&38 ,VODYH 'ULYHV 'ULYHV
:LQ&&IOH[LEOH
67(3
:LQ$&03
,QGXVWULDO(WKHUQHW
(7
352),%86'3
Figure 2-1 Embedded automation with WinAC MP 2008
Product overview
2.1 Product overview
WinAC MP 2008
12 Operating Instructions, 03/2009, A5E00981151-02
Programming
WinAC MP is programmed and configured with STEP 7 and the SIMATIC engineering tools
for production engineering. This means that all SIMATIC programming languages are also
available for WinAC MP.
Note
Program modules programmed for SIMATIC S7 controllers can be reused for WinAC MP
without any changes being necessary, provided they have not been tailored to specific
properties of a SIMATIC S7 CPU.
Visualization with WinCC flexible
WinCC flexible projects for the Multi Panels are edited with WinCC flexible integrated in
STEP 7. In integrated projects, you access the configuration data of STEP 7 and can use the
SIMATIC Manager as the central coordinator for creating, editing and managing WinAC in
the SIMATIC HMI station and the WinCC Flexible projects for the Multi Panels.
Communication
Communication with the I/O is handled via the integrated PROFIBUS-DP master that allows
the connection of DP slaves.
Information from the automation level is acquired over the PROFIBUS-DP interface and
forwarded by WinAC MP 2008 via the Industrial Ethernet interface integrated in the HMI
device. Data are transferred via Industrial Ethernet and S7 communication to a central PC,
for example, to WinCC, WinCC flexible, or to the SIMATIC NET OPC server.
Released FM modules for communication on the PROFIBUS
The following FM modules are released, in addition to standard I/O modules, on PROFIBUS
on an ET 200M.
FM 350-1 function module
FM 350-2, 8-channel counter module
FM 351 positioning module
FM 352 electronic cam controller
FM 353 positioning module - stepdrive
FM 354 positioning module - servodrive
FM 355 control module - PID controller
FM 355-2 temperature controller
FM 352-5 boolean processor
Product overview
2.2 Scope of delivery
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 13
2.2 Scope of delivery
Overview of the components supplied
The following components ship with the product:
CD with:
WinAC MP 2008
Electronic operating instructions in PDF format
Languages: German, English, French
USB stick with:
Single license for WinAC MP 2008
Software Product (Certificate of License)
WinCC flexible System Library
The WinAC MP scope of delivery includes a WinCC flexible system library that contains two
screens. These screens are taken over during the installation in the WinCC flexible system
library and are available for use there.
The WinCC flexible system library includes the following Screens:
Home Screen
Tuning Screen
Further Information
The following sections of the manual provide you with a detailed description of the screens:
Description of the Home Screen (Page 59)
Description of the Tuning Screen (Page 61)
Product overview
2.3 Essential system characteristics of WinAC MP 2008
WinAC MP 2008
14 Operating Instructions, 03/2009, A5E00981151-02
2.3 Essential system characteristics of WinAC MP 2008
New software PLC WinAC MP 177 for MP 177 6'' Touch
Improved time behavior through conversion to "HMI Enable Time"
With WinAC MP, you can configure retentive data for bit memory, S7 timers, S7 counters
and data blocks.
Even if there is a power down while WinAC MP is running, the current values of the
retentive DBs or bit memory, timers and counters are not lost. When you restart WinAC
MP again, you can access the last saved values of these retentive memory bits, timers,
counters and DBs.
B-Send / B-Receive now available in WinAC MP 2008.
The performance during online monitoring via PROFINET has been improved for WinAC
MP 2008.
New screen forms integrated into WinCC flexible system library.
A new parameter has been added in WinAC MP 2008 to specify the file path for system
functions Archive and Restore.
WinAC MP supports time synchronization between the HMI device and the WinAC MP
installed on it.
Routing with S7 communication is possible with WinAC MP.
You configure WinAC MP in STEP 7 as an HMI station and not as a PC station.
WinAC MP supports only the OB 35 as cyclic interrupt.
Expansion of the IO address area from 2k to 4k for MP 277
SCL / CFC programming
Additional technical specifications are available in the in the section "Technical specifications
(Page 93)" in the operating instructions for WinAC MP 2008.
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 15
Steps for installing and removing 3
3.1 Requirements for installation
Installing and working with WinAC MP
Before you can use WinAC MP, there are several installation and development steps you
need to work through on the configuration PC prior to transferring the required components
to the HMI device. You will need to perform the following tasks:
Step Task For more information, refer to the
section ...
1 Check that your HMI and configuration device
meets the system requirements.
Hardware and software
requirements (Page 16)
2 Install WinAC MP on the configuration PC. Installing WinAC MP (Page 18)
3 Transfer the WinAC MP Runtime files from the
configuration PC to the HMI device with ProSave.
Transferring WinAC MP to the HMI
device (Page 26)
4 Transfer the License Key to the HMI device. Licensing WinAC MP on the HMI
device (Page 27)
5 Develop a STEP 7 user program to control your
process with WinAC MP on the HMI device.
Creating a STEP 7 project for
WinAC MP (Page 34)
6 Develop a WinCC flexible project so that the HMI
device is available as the interface to WinAC MP
and to your process. You have the following
options:
Use the supplied WinCC flexible System Library
Create your own WinCC flexible sample project
for your application.
Working with WinCC flexible
(Page 79)
You will find information on using the functions of WinAC MP with WinCC flexible in the
section WinAC MP functions (Page 80).
See also
Setting the communication functions for the configuration PC (Page 47)
Integrating the WinAC MP System Library (Page 57)
Steps for installing and removing
3.2 Hardware and software requirements
WinAC MP 2008
16 Operating Instructions, 03/2009, A5E00981151-02
3.2 Hardware and software requirements
Installation sequence
To be able to use WinAC MP on the HMI device, it is mandatory that you keep to the
following sequence during installation on the configuration PC:
1. Install STEP 7 V5.4 SP 4 or higher
2. Install WinCC flexible 2008 SP1
3. Install WinAC MP 2008
Tip
If older versions of STEP7, WinCC flexible and WinAC MP have already been installed,
you will have to uninstall them first.
Once the programs have been uninstalled, you will have to observe the installation
sequence listed above.
HMI device hardware requirements
WinAC MP is installed on a reserved area of the flash memory. The
memory area reserved for HMI applications is not reduced by this.
WinAC MP runs on the following HMI devices:
SIMATIC MP 177 6" Touch (6AV6 642-0EA01-3AX0)
SIMATIC MP 277 8" Touch (6AV6 643-0CB01-1AX1)
SIMATIC MP 277 8" Key (6AV6 643-0DB01-1AX1)
SIMATIC MP 277 10" Touch (6AV6 643-0CD01-1AX1)
SIMATIC MP 277 10" Key (6AV6 643-0DD01-1AX1)
SIMATIC MP 377 12" Touch (6AV6 644-0AA01-2AX0)
SIMATIC MP 377 12" Key (6AV6 644-0BA01-2AX0)
SIMATIC MP 377 15" Touch (6AV6 644-0AB01-2AX0)
SIMATIC MP 377 19" Touch (6AV6 644-0AC01-2AX0)
To find out if successor Multi Panels are supported, refer to the Internet
(http://www.siemens.com/automation/service&support).
HMI device software requirements
To install WinAC MP 2008 on the HMI device, you require:
WinCC flexible runtime 2008 SP1
current image of the HMI device from WinCC flexible 2008 SP1
Notes on updating the HMI device image are available in the respective documentation.
Steps for installing and removing
3.2 Hardware and software requirements
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 17
Configuration PC hardware requirements
To install WinAC MP on the configuration PC, you require
At least 40 MB of free space on the hard disk
The requirements of STEP 7 and WinCC flexible must also be supported
Configuration PC software requirements
To install WinAC MP on the configuration PC, you require
Microsoft Windows XP Professional, Service Pack 2 or higher
STEP 7 V 5.4 with Service Pack 4 or higher
WinCC flexible 2008 SP1
And...
You need:
An Ethernet or PROFIBUS connection between the configuration PC and HMI device
or a Serial RS232/PPI Multi Master cable for serial transfer (for example to load the
MP 177 and MP 277 the first time) between the configuration PC and HMI device (order
no. of the cable: 6ES7 9013CB30-0XA0).
SIMATIC NET if you want to use Ethernet communication (SIMATIC NET CD V7.0 or
V7.1).
Devices necessary for process control connected to your HMI device using
PROFIBUS DP (for example, ET 200).
The Adobe Reader, to read the supplied electronic manuals. You can obtain the latest
version of Acrobat Reader at www .Adobe.com.
Steps for installing and removing
3.3 Installation steps
WinAC MP 2008
18 Operating Instructions, 03/2009, A5E00981151-02
3.3 Installation steps
3.3.1 Installing WinAC MP
Requirements
Prior to installing WinAC MP, read the requirements in the section: Hardware and software
requirements (Page 16)
Note
You must first uninstall any already installed WinAC MP version.
Installing WinAC MP on the configuration PC
The WinAC MP software includes a setup program that automatically performs the
installation.
The installation program leads you step by step through the installation operation. You can
go to the next step or back to the previous step at any time.
To start the installation program, proceed as follows:
1. Insert the CD "WinAC MP 2008" in the CD drive of the configuration PC.
2. Double-click on the "setup.exe" file in the "\WinAC" folder.
3. Follow the instructions that appear on the next screen.
4. Confirm the dialog and follow the instructions on the screen.
Result: A message is displayed when the installation is completed successfully.
5. You should restart your computer after installation has completed.
Steps for installing and removing
3.3 Installation steps
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 19
Installing WinAC MP on the HMI device
1. Installing the options by means of ProSave.
2. Installing the product-specific license (License Key) using Automation Single License
Manager.
Further installation
Install SIMATIC NET if you want to use Industrial Ethernet communication.
See also
Hardware and software requirements (Page 16)
Steps for installing and removing
3.3 Installation steps
WinAC MP 2008
20 Operating Instructions, 03/2009, A5E00981151-02
3.3.2 Connecting the configuration computer to the HMI device
3.3.2.1 Basics of transfers
Transfer
Transfer is the process of sending the installation and project files between the configuration
PC and the HMI device.
The HMI devices must be connected to the configuration PC to transfer the installation and
project files.
Basic procedure
There are several ways in which you can transfer installation and project files:
Transfer over Industrial Ethernet (direct or networked connection)
Transfer via PROFIBUS DP
Transfer over USB (no STEP 7 user program)
Note
USB connection parameters
To use the USB connection, you require a master-master cable. Install the supplied
"BULK driver" and not "Standard".
You will find information on installing the "BULK driver" under the entry ID
(http://support.automation.siemens.com/WW/view/en/19142034)
Figure 3-1 WinAC MP transfer
Steps for installing and removing
3.3 Installation steps
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 21
3.3.2.2 Transfer over Industrial Ethernet
Connection over Industrial Ethernet
Direct connection: Connect the configuration PC to the HMI device using a crossover cable.
Networked connection over LAN: Connect the configuration PC and the HMI device to the
LAN with a 1:1 or direct cable.
Settings on the HMI device
1. Open the Control Panel to set the network configuration. You can open the Control Panel
either in the Loader or with Start > Settings > Control Panel.
2. Double-click "Network and Dial-up Connections".
3. Double-click on:
LAN9115 for MP 177
LAN90001 for MP 277
ERTEC400 for MP 377
Enter the IP address and, if necessary, the subnet mask of the HMI device. Confirm with
"OK".
Note
Specifying a gateway address
If you need to specify a gateway address, contact your network administrator.
1. Then double-click "Transfer".
2. Under Channel 2, select the "Ethernet" option in the list box, select "Enable Channel" and
confirm with "OK".
WARNING
Entering a static IP address
Do not use DHCP (Dynamic Host Configuration Protocol) to assign the TCP/IP address
on the HMI device.
With DHCP, there is no guarantee that the same IP address will always be assigned
when a node is turned on. If the IP address is changed, nodes in Industrial Ethernet may
lose their connection or be connected to the wrong node. This can result in unexpected
process and machine behavior that can cause death, serious injury and/or damage to
equipment.
Always enter a static IP address for the HMI device or if you use DHCP, make sure that
there are at least lease reservations. Contact your network administrator when
assigning addresses.
Steps for installing and removing
3.3 Installation steps
WinAC MP 2008
22 Operating Instructions, 03/2009, A5E00981151-02
Setting on the configuration PC
Take the following steps on the configuration PC either in ProSave or in WinCC flexible:
Step Connecting ProSave Connecting WinCC flexible
1 Open the "General" tab in ProSave. Open the project you want to transfer in
WinCC flexible.
2 Select your HMI device from the "Device
type" list box.
Select your HMI device via Project >
Change Device Type.
3 -- Change to Project > Transfer > Transfer
Settings in WinCC flexible.
4 Select the "Ethernet" option in the
"Connection" list box.
Select the "Ethernet" option in the "Mode"
list box.
5 In "Connection Parameters", enter the IP
address or the computer name of the HMI
device.
Under "Computer Name" or "IP Address",
enter the computer name or the IP address
of the HMI device.
6 -- Confirm your entries with "Apply".
7 Close ProSave or change to the "Options"
tab to transfer the WinAC MP runtime files.
Please make sure that the correct path is
set.
Change to Project > Transfer > Options in
WinCC flexible to transfer the WinAC MP
runtime files.
Please make sure that the correct path is
set.
8 Click the ">>" button. Click the ">>" button.
Steps for installing and removing
3.3 Installation steps
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 23
3.3.2.3 Transfer over PROFIBUS
Connection over PROFIBUS
The configuration PC must have a PROFIBUS port, such as a CP 5611, and the relevant
drivers must already be installed.
Connect the configuration PC with the HMI device over the DP interface using a PROFIBUS
cable.
Requirements
WinAC MP must be running when you transfer data over PROFIBUS to WinCC flexible
Runtime.
Settings on the HMI device
1. Open the Control Panel in the Loader.
2. Double-click "Transfer".
3. Go to "Channel 2", select "MPI/PROFIBUS/S7 Ethernet" and select "Enable Channel".
4. Click "OK" to close the "Transfer Settings" dialog.
Note
You set the PROFIBUS address of the HMI device in STEP 7 HW Config and not on the
HMI device! The default PROFIBUS address after installing WinAC is 2.
Setting on the configuration PC
Take the following steps on the configuration PC either in ProSave or in WinCC flexible:
Step Connecting ProSave Connecting WinCC flexible
1 Open the "General" tab in ProSave. Open the project you want to transfer in
WinCC flexible.
2 Select your HMI device from the "Device
type" list box.
Select your HMI device via Project >
Change Device Type.
3 -- Change to Project > Transfer > Transfer
Settings in WinCC flexible.
4 Select the "MPI / PROFIBUS-DP" option in
the "Connection" list box.
Select the "MPI/DP" option in the "Mode"
list box.
5 In "Connection Parameters", enter the OP
address of the HMI device.
(The OP address is the PROFIBUS address
of the HMI device).
Enter the station address of the HMI
device.
(The OP address is the PROFIBUS
address of the HMI device).
6 -- Confirm your entries with "Apply".
7 Close ProSave or change to the "Options"
tab to transfer the WinAC MP runtime files.
Please make sure that the correct path is
set.
Change to Project > Transfer > Options in
WinCC flexible to transfer the WinAC MP
runtime files.
Make sure that the correct path is set.
8 Click the ">>" button. Click the ">>" button.
Steps for installing and removing
3.3 Installation steps
WinAC MP 2008
24 Operating Instructions, 03/2009, A5E00981151-02
3.3.2.4 Transfer via USB
Connecting over USB
Connect the USB port of the configuration PC with the USB port of the HMI device using a
USB cable.
Note
USB connection parameters
To use the USB connection, you require a master-master cable. Install the included "BULK
driver" and not "Standard".
You will find information on installing the "BULK driver" under the entry ID
(http://support.automation.siemens.com/WW/view/en/19142034)
Settings on the HMI device
1. Open the Control Panel in the Loader.
2. Double-click "Transfer".
3. Under Channel 2, select "USB", select "Enable Channel" and
confirm with "OK".
Setting on the configuration PC
Take the following steps on the configuration PC either in ProSave or in WinCC flexible:
Step Connecting ProSave Connecting WinCC flexible
1 Open the "General" tab in ProSave. Open the project you want to transfer in
WinCC flexible.
2 Select your HMI device from the "Device
type" list box.
Select your HMI device by selecting
Project > Change Device Type.
3 -- Change to Project > Transfer > Transfer
Settings in WinCC flexible.
4 Select the "USB" option in the "Connection"
list box.
Select the "USB" option in the "Mode" list
box.
5 -- Confirm your entries with "Apply".
6 Close ProSave or change to the "Options"
tab to transfer the WinAC MP Runtime files.
Make sure that the correct path is set.
Change to Project > Transfer > Options in
WinCC flexible to transfer the WinAC MP
Runtime files.
Make sure that the correct path is set.
7 Click the ">>" button. Click the ">>" button.
Steps for installing and removing
3.3 Installation steps
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 25
3.3.2.5 Transfer using automatic transfer detection
Application
Using automatic transfer detection, you can transfer projects from the configuration computer
to the HMI device without needing to change the HMI device to transfer mode. Automatic
transfer detection is useful when the configuration computer and the HMI device are located
at some distance apart.
WARNING
Death, serious injury and/or damage to equipment possible
If you select "Automatic transfer detection", you transfer the files while WinAC MP is
operating!
If WinAC MP is connected to inputs/outputs, an interruption in the operation of WinAC MP
can lead to death, serious injury and/or damage to equipment.
Make sure of the following when transferring:
Only qualified personnel have access to the configuration computer!
All devices must be in a safe state before the transfer is started.
Always install an EMERGENCY STOP circuit for your machine or process.
Prerequisites for automatic transfer detection
WinCC flexible Runtime must be running on the HMI device. The HMI device cannot
automatically toggle to "automatic transfer detection" if WinCC flexible Runtime is not
running.
All dialogs on the HMI device must be closed.
Settings on the HMI device
Make the following settings in the Control Panel on the HMI device:
Step Settings in the Transfer
1 Select "Channel 2", the type of connection, and then select "Enable Channel" and
"Remote Control".
2 Confirm with "OK" and start WinCC flexible Runtime on the HMI device.
3 Start the transfer with WinCC flexible on the configuration computer.
Once the transfer has started, WinCC flexible Runtime is automatically closed on the HMI
device and then restarted.
Further Information
For more information on working with the functions in WinCC flexible, refer to the
documentation on WinCC flexible.
Steps for installing and removing
3.3 Installation steps
WinAC MP 2008
26 Operating Instructions, 03/2009, A5E00981151-02
3.3.3 Transferring WinAC MP to the HMI device
Transferring WinAC MP Runtime files
To be able to operate WinAC MP on the HMI device, you will need to download the
WinAC MP option from the configuration PC to the HMI device.
To do so, follow these steps:
1. Boot your HMI device and press the "Transfer" button in the Loader.
Result: The message "Connecting to host" appears on the HMI device.
NOTICE
In the Control Panel, make sure that you have enabled the transfer for the interface you
intend to use.
This is explained step-by-step in the sections:
Transfer over Industrial Ethernet (Page 21)
Transfer over PROFIBUS (Page 23)
Transfer via USB (Page 24)
Transfer using automatic transfer detection (Page 25)
2. Open ProSave on the configuration PC.
3. Select the type of HMI device in the "General" tab in ProSave.
4. In the "Connection" list box, select the connection type:
Ethernet
MPI/PROFIBUS-DP
USB
5. Enter the connection parameters:
Ethernet: IP address or computer name; recommendation: as the fastest and most
flexible connection
PROFIBUS: OP address (same as the PROFIBUS address)
USB
Note
USB connection parameters
To use the USB connection, you require a master-master cable. Install the included
"BULK driver" and not "Standard".
You will find information on installing the "BULK driver" under the entry ID
(http://support.automation.siemens.com/WW/view/en/19142034)
6. Go to the "Options" tab and click "Device status".
Result: The communication connection is checked.
If "WinAC MP" is not shown in the box with the available options, check the path in
"Selection".
You will find the application in:
...\Programs\Mutual Files\Siemens\PTProSave\AddOn\WinAC MP 2008
7. Select the required folder.
8. Click the download button ">>" to transfer the option to the HMI device (you will see any
options that are already installed in the "Installed Options" box).
9. After the transfer was completed, a dialog opens on the HMI device requesting you to
reboot. Reboot the HMI device.
Result: WinAC MP is now installed on the HMI device.
To obtain an operator interface to the HMI device, you still need to download (transfer) a
WinCC flexible project.
Steps for installing and removing
3.3 Installation steps
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 27
See also
Basics of transfers (Page 20)
3.3.4 Licensing WinAC MP on the HMI device
Software license
WinAC MP requires a product-specific License Key that you install with Automation License
Manager.
Note
The product-specific License Key of WinAC MP 2007 V4.0 is compatible with
WinAC MP 2008 V4.1.
Transferring a License Key
With the Automation License Manager, you can transfer a License Key from a computer to
an HMI device.
When transferring License Keys between different locations (media), you have the following
options:
Transferring the license from the configuration PC to the HMI device with the Automation
License Manager
using drag-and-drop
Cut and paste
The License Key > Transfer menu command.
Transferring the license from the configuration PC to the HMI device with the Automation License
Manager
1. Open the Automation License Manager with Start > SIMATIC > License Management >
Automation License Manager.
Result: The Automation License Manager opens.
2. Select Edit > Connect Target Systems > Connect HMI Device to open the "Connect
Target System" dialog. Select the HMI device and the type of connection.
3. In the Automation License Manager, select the license you want to transfer and
select "Transfer..." with the right mouse button.
4. Select the HMI device to which you want to transfer the license as the target computer.
Result: The license for WinAC MP is on the HMI device
Steps for installing and removing
3.3 Installation steps
WinAC MP 2008
28 Operating Instructions, 03/2009, A5E00981151-02
Transferring a License Key with drag-and-drop
1. Select the view with the View > Manage menu command.
2. Open the storage location on your own computer or on a connected computer from which
you want to remove the License Key.
3. Select the License Key, hold down the left mouse button and drag the License Key to the
target location.
Result: The License Key is transferred.
Transferring the License Key with cut and paste
1. Select the view with the View > Manage menu command.
2. Open the storage location on your own computer or on a connected computer from which
you want to remove the License Key.
3. Select the License Key you want to transfer.
4. Select Edit > Cut.
5. Open the storage location on your own computer or on a connected computer to which
you want to transfer the License Key.
6. Select the Edit > Paste menu command.
Result: The License Key is transferred.
Transferring the License Key with the License Key > Transfer menu command:
1. Select the License Key you want to transfer to another storage location.
2. Open the "Transfer License Key" dialog with the License Key > Transfer menu command.
3. Select the target drive from the drop-down list box.
4. Click "OK" to confirm the selection.
5. Click the "Network..." button if the target drive is on another connected computer.
The "Connect Computer" dialog opens.
6. Enter the computer name or select the required computer from the drop-down list box or
Click the "Browse..." button to access the "Find Computer" dialog.
Click "Entire Network" and then "Microsoft Windows Network".
If the computer is in a domain, select the domain.
Then select the required computer and click "OK" to confirm your selection. Please
remember that the Automation License Manager must also be installed on the
computer you select.
Note
The backup function saves all data of the panel to the specified external storage
medium. The data in retentive memory is excluded.
Steps for installing and removing
3.4 Steps when removing
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 29
Further Information
For more information on this, please refer to the following Online Help:
Automation License Manager
ProSave
3.4 Steps when removing
3.4.1 Retransferring license keys
Transferring a License Key
With the Automation License Manager, you can transfer a License Key from a computer to
an HMI device.
To transfer License Keys between different locations (media), you have the following
options:
using drag-and-drop
Cut and paste
The License Key > Transfer menu command.
Transferring a License Key with drag-and-drop
1. Select the view with the View > Manage menu command.
2. Open the storage location on your own computer or on a connected computer from which
you want to remove the License Key.
3. Select the License Key, hold down the left mouse button and drag the License Key to the
target location.
Result: The License Key is transferred.
Transferring the License Key with cut and paste
1. Select the view using the View > Manage menu command.
2. Open the storage location on your own or on the connected computer from which you
want to remove the License Key.
3. Select the License Key you want to transfer.
4. Select Edit > Cut.
5. Open the storage location on your own computer or on a connected computer to which
you want to transfer the License Key.
6. Select the Edit > Paste menu command.
Result: The License Key is transferred.
Steps for installing and removing
3.4 Steps when removing
WinAC MP 2008
30 Operating Instructions, 03/2009, A5E00981151-02
Transferring the License Key using the License Key > Transfer menu command:
1. Select the License Key you want to transfer to another storage location.
2. Open the "Transfer License Key" dialog by selecting the License Key > Transfer menu
command.
3. Select the target drive from the drop-down list box.
4. Click "OK" to confirm the selection.
5. Click the "Network..." button if the target drive is on another connected computer.
The "Connect Computer" dialog opens.
6. Enter the computer name or select the required computer from the drop-down list box
Or click the "Browse..." button to access the "Find Computer" dialog.
Click "Entire Network" and then "Microsoft Windows Network".
If the computer is in a domain, select the domain.
Select the required computer and click "OK" to confirm your selection. Please
remember that the Automation License Manager must also be installed on the
computer you select.
7. Click "OK" to confirm your selection and to close the dialogs.
Retrieving the License Key if the hard disk is defective
If a fault has occurred on the hard disk or the USB containing your License Key file, contact
your Siemens representative (http://support.automation.siemens.com). Make sure you have
your license certificate to hand when you contact this representative.
Steps for installing and removing
3.4 Steps when removing
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 31
3.4.2 Uninstalling WinAC MP on the HMI device
Notes on removing
After having removed WinAC MP, you must reboot the HMI device.
Removing
To uninstall WinAC MP Runtime files on the HMI device, follow the steps below:
1. Exit WinCC flexible Runtime.
2. Select transfer mode in the "Loader" dialog box on the HMI device.
3. Open the "Options" tab in ProSave on the configuration PC.
4. Select the "Device Status" button in the "Options" tab to read the WinAC MP Runtime
files on the HMI device. The Runtime files are displayed in the right-hand pane "Installed
Options".
5. In the right-hand pane "Available Options", select the WinAC MP option and click the "<<"
button to remove the WinAC MP Runtime files from the installed options for the HMI
device. The WinAC MP Runtime files are then deleted on the HMI device.
6. Answer the prompt to restart on the HMI device (select "Yes" if you want to restart
immediately, select "No" if you want to restart later).
Once you have uninstalled the WinAC MP Runtime files on the HMI device, you can exit
ProSave.
Note
WinAC MP cannot be removed from the HMI device via PROFIBUS.
3.4.3 Uninstalling WinAC MP on the configuration PC
Removing
To uninstall WinAC MP on the configuration PC, follow these steps:
1. Open the Control Panel with Start > Settings > Control Panel in the Start menu of the
configuration PC.
2. Double-click on "Add or Remove Programs" in the detailed view.
3. Select the "SIMATIC WinAC MP 2008 V4.1.1" entry.
4. Click the "Remove" button.
5. Confirm that you want to uninstall by clicking "Yes".
6. Click "OK when the software has been uninstalled.
Result: WinAC MP has been uninstalled on the configuration PC.
Steps for installing and removing
3.4 Steps when removing
WinAC MP 2008
32 Operating Instructions, 03/2009, A5E00981151-02
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 33
STEP 7 configuration and communication options 4
4.1 Standard procedure for communication with WinAC MP
Overview
The section below shows how to configure WinAC MP in a SIMATIC HMI station using a
configuration PC on which STEP 7 and WinCC flexible are installed.
The configuration PC and WinAC MP in a SIMATIC HMI station are interconnected via
PROFIBUS DP. Configuration via Ethernet is also possible. You will find the description of
the procedure in the section Configuring an Ethernet connection for routing functionality over
the HMI device (Page 47).
You can integrate DP slaves for WinAC MP in the STEP 7 project as shown in the figure.
:LQ&&
IOH[LEOH :LQ$&03
(7
352),%86'3
:LQ&&
IOH[LEOH57
23
67(3b
,VODYH
'ULYH
&RQILJXUDWLRQFRPSXWHU +0,GHYLFH
Procedure
The basic steps are as follows:
1. Configuring WinAC MP in STEP 7
2. Creating a connection between WinAC MP and WinCC flexible Runtime
3. In STEP 7, download the configuration to the WinAC MP
4. Configuring (visualization) HMI objects with WinCC flexible.
5. Download the visualization configuration (for example, visualization with histogram) from
WinCC flexible to the HMI device.
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
34 Operating Instructions, 03/2009, A5E00981151-02
See also
Setting the communication functions for the configuration PC (Page 47)
4.2 Creating a STEP 7 project for WinAC MP
4.2.1 Configuring the SIMATIC HMI station and the PROFIBUS-DP network
To see how easy it is to configure WinAC MP, view the short info film on the Internet
(http://support.automation.siemens.com/WW/view/en/32010673).
Configuring a SIMATIC HMI station
To create a new project for WinAC MP, proceed as follows:
1. Select File > New in the SIMATIC Manager and enter a project name.
2. Select your project and create an HMI station with Insert > Station > SIMATIC HMI
Station.
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 35
3. In the "Properties - WinCC flexible RT" dialog box that then opens, select the Multi Panel
you are using and confirm with "OK".
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
36 Operating Instructions, 03/2009, A5E00981151-02
4. Double-click the SIMATIC HMI station in the SIMATIC Manager. The configuration is then
displayed in the right-hand pane.
5. Double-click "Configuration". Result: HW Config opens.
6. Delete "HMI IE" and "IF1B MPI/DP".
7. In the hardware catalog, go to the SIMATIC HMI Station > Controller > WinAC MP folder
and, depending on the Multi Panel selected under item 3, select:
WinAC MP 177->6ES7 671-4EE00-0YA0->V4.1 for WinAC MP 177, or
WinAC MP 277->6ES7 671-5EF01-0YA0->V4.1 for WinAC MP 277, or
WinAC MP 377->6ES7 671-7EG01-0YA0->V4.1 for WinAC MP 377
8. Drag WinAC MP to slot 2.
Result: The "Properties - Ethernet Interface" dialog opens.
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 37
9. Enter the IP address and subnet mask.
10. Create a new subnet and close the dialogs.
Result: The "Properties – PROFIBUS interface DP" dialog opens.
11. If necessary, change the PROFIBUS address of WinAC MP and create a new subnet.
12. Set the transmission speed in the network settings. Close the dialogs.
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
38 Operating Instructions, 03/2009, A5E00981151-02
13. Save in HW Config with Station > Save and Compile.
14. Close HW Config.
You have now created the SIMATIC HMI station with WinAC MP in your STEP 7 project.
See also
Communication options with WinAC MP (Page 53)
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 39
4.2.2 Creating a connection between WinAC MP and WinCC flexible Runtime on the
HMI device
Creating a connection between WinAC MP and WinCC flexible RT
Follow the steps outlined below to create a connection between WinAC MP and WinCC
flexible Runtime:
1. Right-click WinCC flexible RT in SIMATIC Manager and select: Object > Open
Result: WinCC flexible opens.
2. Double-click "Connections" in the WinCC flexible project window.
Result: The "Connections" editor opens.
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
40 Operating Instructions, 03/2009, A5E00981151-02
3. Change the value to "On" in the "Active" column.
Result: A local connection between WinCC flexible RT and WinAC MP is created.
4. Save and compile the WinCC flexible project. Close WinCC flexible.
Note
Always configure the connections (local and routing) between WinCC flexible RT and
WinAC MP or other controllers (e.g. S7-300/400) in the "Connections" editor of
WinCC flexible.
Connections between WinAC MP and other controllers (e.g. S7-300/400) are always
configured in NetPro of SIMATIC Manager.
See also
Transferring WinAC MP to the HMI device (Page 26)
Licensing WinAC MP on the HMI device (Page 27)
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 41
4.2.3 Time synchronization WinAC MP
Time synchronization
You can synchronize the WinAC MP time with the operating system of the HMI device.
How to set time synchronization in HW Config:
1. Select WinAC MP x77 in the SIMATIC HMI station.
2. Open the object properties with the right mouse button.
3. Go to the "Diagnostics/Clock" tab.
4. To synchronize the WinAC MP time with the HMI device, set the synchronization mode
on the AS to "As slave".
5. Confirm with "OK".
Note
When synchronization is enabled, the time is compared at a fixed interval of one second.
If the difference between the Panel time and the WinAC MP time is more than 0.5
seconds, WinAC MP takes the time of the Panel.
Further Information
For more information on the tabs, refer to the STEP 7 online help and the documentation on
the standard CPUs.
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
42 Operating Instructions, 03/2009, A5E00981151-02
4.2.4 Configuring retentive data
Retentive data
Data is kept in retentive memory following POWER OFF and restart or a warm restart.
You can set the retentivity of bit memory, timers, counters and data blocks. The next time
you start WinAC MP or following a power outage on the HMI device, the buffered data is
available again.
Behavior following image update
After an OS update or backup/restore on the MP 177, MP 277, or MP 377 with
WinAC MP installed, the retentive data areas of WinAC MP are completely deleted.
Configuring retentivity for memory bytes, S7 timers, S7 counters
Note
With MP 177, MP 277 and MP 377, all bit memories, timers and counters can be saved
retentively.
Follow the steps below to configure the retentive data for WinAC MP:
1. Select WinAC MP x77 in the SIMATIC HMI station.
2. Open the object properties with the right mouse button.
3. Go to the "Retentive Memory" tab.
4. Enter the number of memory bytes starting at MB 0, S7 timers starting at T0 and S7
counters starting at C0 that you want to be retentive.
5. Confirm with "OK".
Figure 4-1 Properties of memory bytes, S7 timers, S7 counters
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 43
Configuring retentivity for data blocks
Note
With MP 177, MP 277 and MP 377, you have the following memory available for retentive
DBs:
MP 177: 64 KB
MP 277: 128 KB
MP 377: 256 KB
The content of data blocks is always retentive unless it was created with SFC 85.
You can change the retentivity in the properties of the data block in STEP 7 using the "Non-
Retain" check box. A data block with the "Non-Retain" property is not stored in the retentive
memory and is therefore reset to the initial load values following every power cycle and cold
or warm restart and following every change from STOP to RUN.
A data block with the "Non-Retain" property occupies work memory as usual but takes up no
retentive memory.
Figure 4-2 Data block properties
Further Information
For more information on the tabs, refer to the STEP 7 online help and the documentation on
the standard CPUs.
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
44 Operating Instructions, 03/2009, A5E00981151-02
4.2.5 WinCC flexible direct keys in WinAC MP
Definition
Direct keys on the HMI device are used to set bits in the I/O area of the controller.
WinCC flexible direct keys in WinAC MP 2008
WinCC flexible supports:
Direct keys for key input, required, for example for inching mode
LED displays with short reaction times
It is not necessary to configure the direct keys for WinAC MP.
The direct key bits are always available through I/O direct accesses to the I/O area,
beginning with address 4000H or 16384D.
The following table lists the direct key ranges:
Input range
Hexadecimal
Input range
decimal
Output range
Hexadecimal
Output range
decimal
MP 177 6"Touch 4000H – 4003H 16384 - 16387 -- --
MP 277 8" Key 4000H – 4004H 16384 - 16388 4000H – 4004H 16384 - 16388
MP 277 8" Touch 4000H – 4004H 16384 - 16388 -- --
MP 277 10" Key 4000H – 4004H 16384 - 16388 4000H – 4004H 16384 - 16388
MP 277 10" Touch 4000H – 4004H 16384 - 16388 -- --
MP 377 12" Key 4000H – 4004H 16384 - 16388 4000H – 4004H 16384 - 16388
MP 377 12" Touch 4000H – 4004H 16384 - 16388 -- --
MP 377 15" Touch 4000H – 4004H 16384 - 16388 -- --
MP 377 19" Touch 4000H – 4004H 16384 - 16388 -- --
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 45
Input/output assignment for MP 277-8" (key)
Input/output assignment for MP 277-10" (key)
Input/output assignment for MP 377 (key)
Input/output assignment for MP 177 6" Touch
STEP 7 configuration and communication options
4.2 Creating a STEP 7 project for WinAC MP
WinAC MP 2008
46 Operating Instructions, 03/2009, A5E00981151-02
Input/output assignment for MP 277 8" touch, MP 277 10" touch, MP 377 touch
WARNING
Triggering the system function "DirectKey" by mistake leads to the endangerment of
persons or damage to the machine.
In order to avoid this danger, the following must be observed:
When configuring the process screen, the button with the system function "DirectKey" must
not be covered by a screen object.
The dynamic positioning or display (enable) of a screen object dependent on process
values must not lead to the button with the system function "DirectKey" being overlapped in
runtime.
Please observe this guideline during configuration. Check also existing configurations and
adjust them immediately.
WARNING
If you set the connection to WinAC MP "offline" using the "SetConnectionMode" system
function, the communication connection to WinAC MP is disconnected. The DP direct keys
are still active in this case. If you press a key with the "DirectKey" system function in
"offline" mode or press the direct key on a key device, the corresponding bit is set in WinAC
MP.
Further Information
Further information:
You can find more information in the
Operating Instructions
of the MP 177, MP 277 and
MP 377 HMI devices in the section: Bit assignment of the direct keys
in the
User Manual Communication Part 1
in the STEP 7 online help
STEP 7 configuration and communication options
4.3 Configuring an Ethernet connection for routing functionality over the HMI device
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 47
4.3 Configuring an Ethernet connection for routing functionality over the
HMI device
4.3.1 Setting the communication functions for the configuration PC
Communication settings
You have the following communication options for connecting STEP 7 on the configuration
computer with the HMI device:
Industrial Ethernet
PROFIBUS
No serial communication or USB communication is possible with STEP 7.
See also
Transfer over Industrial Ethernet (Page 21)
Transfer over PROFIBUS (Page 23)
The following settings are necessary if you want to use routing.
Configuring hardware
If you work with an Ethernet connection (TCP/IP), you will need to take additional steps in
HW Config. Follow the steps below to set a static IP address for TCP/IP communication
between STEP 7 and the HMI device:
1. Click on your project in the SIMATIC Manager and select Insert > Station > PG/PC.
Result: A new PG/PC station is inserted.
2. Double-click on "PG/PC".
Result: The "Properties PG/PC" dialog opens.
3. Click the "Interface" tab to open it and click on "New".
Result: The "New Interface - Type Selection" dialog opens.
STEP 7 configuration and communication options
4.3 Configuring an Ethernet connection for routing functionality over the HMI device
WinAC MP 2008
48 Operating Instructions, 03/2009, A5E00981151-02
4. In the "New Interface - Type Selection" dialog, select the type "Industrial Ethernet" and
confirm with "OK".
Result: The "Properties - Ethernet Interface" dialog is displayed.
5. Enter the IP address of the configuration PC in the "IP address" box.
6. Select an Ethernet subnet as the subnet. If this does not already exist, select "New". The
"Properties - New subnet Industrial Ethernet" dialog box opens. Select "OK". A new
Ethernet subnet is created.
7. Select "OK" to complete the configuration of the Ethernet interface.
Result: The subnet is now selected in the "Properties - Ethernet Interface" dialog.
STEP 7 configuration and communication options
4.4 Checking and downloading a STEP 7 project to WinAC MP
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 49
8. Confirm with "OK".
Result: The "Properties - PG/PC" dialog appears again.
9. Click "OK" to close the "Properties PG/PC" dialog.
Further Information
For more information on Ethernet communication and setting up Ethernet networks, refer to
the
SIMATIC NET Ethernet
User Manual.
4.4 Checking and downloading a STEP 7 project to WinAC MP
4.4.1 Checking the WinAC MP online connection
Checking the connection with STEP 7
Once you have completed the network configuration, check whether the connection between
STEP 7 and WinAC MP is functioning. You can do this by selecting View > Online or PLC >
Display Accessible Nodes in the SIMATIC Manager.
If the network configuration is not online, review the network configuration steps described in
the sections above and correct any errors you may have made.
STEP 7 configuration and communication options
4.4 Checking and downloading a STEP 7 project to WinAC MP
WinAC MP 2008
50 Operating Instructions, 03/2009, A5E00981151-02
4.4.2 Downloading the configurations
Downloading hardware configuration
To download the hardware configuration to WinAC MP, you first set the PG/PC interface
for the connection on the configuration PC:
PROFIBUS or Ethernet (TCP/IP).
Setting the PG/PC interface
Follow the steps outlined below to set the PG/PC interface:
1. In the SIMATIC Manager, select Options > Set PG/PC Interface from the menu.
2. Check that the required type of connection is entered in the "Interface parameter
assignment used" box. If necessary, select the required interface from the list box. You
can choose between the TCP/IP option or a CP with a PROFIBUS DP bus profile (for
example CP5611).
3. Set the properties for the interface parameter assignment to match your type of
connection:
Industrial Ethernet (TCP/IP): Recommendation: the fastest and most flexible
connection
PROFIBUS: Set the transmission rate for the first download to 1.5 Mbps and use a DP
interface. This is the default for the HMI device.
4. Confirm the setting with "OK".
Check the following points before you download the configuration:
Make sure that WinAC MP has started on the HMI device. Start
WinCC flexible Runtime and WinAC MP.
Setting up a subnet for Industrial Ethernet
Before WinAC MP can communicate over Industrial Ethernet, you will need to set up a
subnet.
You do this by configuring the SIMATIC HMI station, as follows:
1. In the "Parameters" tab of the "Properties - PROFIBUS Ind. Ethernet" dialog, enter the
IP address. The subnet mask is preset.
Note
Closed "Properties - Ind. Ethernet" dialog
If this dialog is closed, double-click the "Ind. Ethernet" field in the SIMATIC station. Click
the "Properties" button to open the "Properties Ethernet Interface" dialog box.
2. Click "New" in the "Parameters" tab.
3. Click "OK" three times to confirm.
STEP 7 configuration and communication options
4.4 Checking and downloading a STEP 7 project to WinAC MP
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 51
Setting up a subnet for PROFIBUS DP
To allow WinAC MP to communicate with the distributed I/O, you will need to set up a
PROFIBUS/DP subnet. Configure the SIMATIC HMI station as a
DP master:
1. In the "Parameters" tab of the "Properties - PROFIBUS Interface DP" dialog, enter the
node address for WinAC MP. The default address for the DP master is 2. Each node in
the network must have a unique node address between 1 and 126.
Note
Closed "Properties - PROFIBUS Interface DP" dialog
STEP 7 displayed the "Properties - PROFIBUS interface DP" dialog when you dragged
WinAC MP to slot 2.
If this dialog is closed, double-click the "DP" field in the SIMATIC station. Click the
"Properties" button to open the "Properties DP" dialog box.
2. Click "New" in the "Parameters" tab.
3. Open the "Network Settings" tab. Check the following settings and make any changes
necessary:
Highest PROFIBUS address: This can be set lower to increase the query rate if you
are sure that you will not exceed a certain number of stations.
Transmission rate: The default is 1.5 Mbps, but up to 12 Mbps are possible depending
on the requirements and application.
Profile: The default is DP.
4. Click "OK" three times to confirm.
Downloading WinAC MP
To download the WinAC MP configuration to the HMI device, follow these steps:
1. Select PLC > Download to Module in HW Config on the configuration PC to download the
configuration of the STEP 7 project.
2. In the "Select target module" dialog box, select WinAC MP x77 and confirm with "OK".
3. Select the station address.
4. When using PROFIBUS connections, enter the node address of the HMI device: The
default address of the HMI device is PROFIBUS 2.
If you are using Ethernet connections, make sure that the IP address of the HMI device is
correct and confirm with "OK".
Result: STEP 7 downloads the hardware configuration to WinAC MP and sets
PROFIBUS DP on the HMI device for the PROFIBUS interface. A dialog box is displayed
indicating whether or not the download was successful.
If you have used an Industrial Ethernet connection to the HMI device, you can continue to
download to the HMI device over Ethernet and do not need to make any changes in
"Set PG/PC interface" in STEP 7.
STEP 7 configuration and communication options
4.4 Checking and downloading a STEP 7 project to WinAC MP
WinAC MP 2008
52 Operating Instructions, 03/2009, A5E00981151-02
Downloading WinCC flexible Runtime
To download the WinCC flexible runtime configuration to the HMI device, follow the steps
below:
1. Click on your project in WinCC flexible.
2. Select Project > Transfer > Transfer Settings.
3. Select the target and communication connection and confirm with "Transfer".
Figure 4-3 Selecting transfer
Further Information
For more information on PROFIBUS communication and setting up
PROFIBUS networks, refer to the
SIMATIC NET PROFIBUS User Manual
.
STEP 7 configuration and communication options
4.5 Communication options with WinAC MP
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 53
4.5 Communication options with WinAC MP
Definition of routing
If there are stations in an automation system that are not connected to the same bus, these
stations cannot be accessed directly online. To establish a connection to these devices, a
router must be included between them.
An MP x77 HMI device with WinAC MP can function as the router. As a router, it connects
the Ethernet and PROFIBUS networks.
You can use routing, for example, to do the following:
Download STEP 7 user programs
Download a hardware configuration
Run debugging and diagnostic functions.
Definition: Softbus
Virtual bus that allows a data exchange between WinCC flexible runtime and WinAC MP.
This bus is installed when you install WinCC flexible. After installing WinAC MP, S7
connections from WinCC flexible Runtime to external stations on PROFIBUS or Ethernet are
routed over Softbus.
Prior to installation of WinAC MP (without Softbus)
+0,57
352),%86 352),1(7
2SHUDWLQJV\VWHP
STEP 7 configuration and communication options
4.5 Communication options with WinAC MP
WinAC MP 2008
54 Operating Instructions, 03/2009, A5E00981151-02
After installation of WinAC MP (with Softbus)
+0,57 :LQ$&03
352),%86 352),1(7
6RIWEXV
2SHUDWLQJV\VWHP
Routing from Ethernet to PROFIBUS DP with WinAC MP
With STEP 7 on Industrial Ethernet, you can access all nodes on PROFIBUS DP from the
HMI device.
With WinCC flexible, you can access the HMI device but not the nodes connected over
PROFIBUS DP.
If the configuration PC is not connected directly to PROFIBUS DP, the nodes on PROFIBUS
can nevertheless be reached because the MP x77 HMI device serves as a router.
,VODYH
:LQ&&IOH[LEOH
:LQ$&03
,QGXVWULDO(WKHUQHW
(7
352),%86'3
67(3
:LQ&&IOH[LEOH57
6&38
Figure 4-4 Routing from Ethernet to PROFIBUS DP with WinAC MP
STEP 7 configuration and communication options
4.5 Communication options with WinAC MP
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 55
Routing from PROFIBUS DP to Ethernet with WinAC MP
With STEP 7 on PROFIBUS DP, you can access all nodes on Industrial Ethernet from the
HMI device. With WinCC flexible on PROFIBUS DP, you have access to the HMI device and
to OPs connected over PROFIBUS DP.
,VODYH
'ULYH
23
:LQ&&
IOH[LEOH :LQ$&03
,QGXVWULDO(WKHUQHW
(7
352),%86'3
67(3 :LQ&&
IOH[LEOH57
6&38
Figure 4-5 Routing with WinAC MP over PROFIBUS
Visualization over WinAC MP
Visualization over the HMI device between Industrial Ethernet and PROFIBUS DP is
possible with WinCC flexible.
It is not necessary to program the communication links. A PC serves as the visualization
platform.
,VODYH
'ULYH
23
352),%86'3
:LQ$&03 :LQ$&03
,QGXVWULDO(WKHUQHW
(7
:LQ&&
IOH[LEOH57
6&38
:LQ&&
IOH[LEOH57 6&38
Figure 4-6 Visualization over WinAC MP
STEP 7 configuration and communication options
4.5 Communication options with WinAC MP
WinAC MP 2008
56 Operating Instructions, 03/2009, A5E00981151-02
CPU-CPU communication over WinAC MP
CPU-CPU communication is possible with the HMI device.
,VODYH
'ULYH
23
:LQ$&03
387*(7
%6(1'%5&9
6&38
,QGXVWULDO(WKHUQHW
(7
352),%86'3
:LQ&&
IOH[LEOH57
6&38
Figure 4-7 CPU-CPU communication over WinAC MP
See also
Configuring the SIMATIC HMI station and the PROFIBUS-DP network (Page 34)
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 57
Controlling a process with WinAC MP 5
5.1 Integrating the WinAC MP System Library
Note
The screens from the system library are optimized for 6'' displays with a resolution of 320 x
240. If using a display with a different size you can adjust the screens accordingly in WinCC
flexible.
Integrating the new WinAC System Library
To create a WinACMP project with the help of WinAC MP System Library you must take the
following steps:
1. Configure the SIMATIC HMI station and the PROFIBUS-DP network.
Corresponding procedures is described in chapter: Configuring the SIMATIC HMI station
and the PROFIBUS-DP network (Page 34)
2. Open the project in STEP 7 by selecting File > Open
3. To open WinCC flexible, go to SIMATIC Manager, select "WinCC flexible RT" and right-
click "Open Object".
4. Open Tools > Library.
5. In the work space of the library window, right-click: Library... > Open
6. The "Open global library" dialog box opens.
Controlling a process with WinAC MP
5.1 Integrating the WinAC MP System Library
WinAC MP 2008
58 Operating Instructions, 03/2009, A5E00981151-02
7. Navigate to the following path:
C:\Programs\SIEMENS\SIMATIC WinCC flexible\WinCC flexible Support\Libraries\
system libraries or click the system libraries icon on the left side in order to access the
directory.
8. Select the WinCC flexible library "WinAC_MP_2008.wlf".
Result: The library objects "WinAC_MP_Home" and WinAC_MP_Tuning" were created
within Library -> View tools.
9. Drag the library object from the work space of the library window to the position where
you want to insert it in the work space.
10. To open the screen for editing, go to the WinCC flexible project window.
11. Select a project: Project > Screens > WinAC_MP_Home or
Project > Screens > WinAC_MP_Tuning
12. Double-click the screen or select "Open editor" from the shortcut menu.
Result: The screen is opened for editing in the work space.
Controlling a process with WinAC MP
5.2 Description of the Home Screen and the Tuning Screen
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 59
5.2 Description of the Home Screen and the Tuning Screen
5.2.1 Description of the Home screen
Display of the Home Screens
Figure 5-1 Home Screen
Controlling a process with WinAC MP
5.2 Description of the Home Screen and the Tuning Screen
WinAC MP 2008
60 Operating Instructions, 03/2009, A5E00981151-02
The Home Screen contains the following elements:
Buttons for the operating functions of the WinAC MP
Start: Start
Shutdown: Closing and exiting
Autostart: if the autostart function is enabled, WinAC MP changes after startup (e.g.
the start-up of the HMI device) to the RUN or STOP mode where it was prior to closing
StartAtBoot: autostart at the startup of the MP device
Restore: Restore
Archive: archiving the STEP 7 user program and WinAC MP system configuration
Buttons for functions
Tuning >>: Changing to the Tuning screen
Exit: is freely configurable with WinCC flexible functions (e.g. hotkeys), e.g. return to
start screen
Mode selector switch (RUN, STOP)
Status indicators for WinAC MP
MRES button for CPU memory reset
Display of the WinAC MP version
Multi Panel variants
MP x77 Touch: You work in the screen by pressing the buttons in the display.
MP x77 Key: Each function key can be configured with a hotkey.
Further information
For more detailed information on the buttons, refer to the Assignment of the function keys
(Page 63) section
For information on how to configure the Hotkeys for WINAC MP, refer to the Operating
WinAC MP with hotkeys (Page 63) section.
Controlling a process with WinAC MP
5.2 Description of the Home Screen and the Tuning Screen
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 61
5.2.2 Description of the Tuning screen
Tuning Screen
You can find histogram information on the cycle time of WinAC MP in the Tuning Screen
screen. The histogram shows the percentage distribution of the measured cycle times. To
acquire these values, WinAC MP measures the cycle time after each cycle and counts the
frequency with which the individual values occur. Each measured cycle time is displayed as
a percentage relative to the total number of measured cycle times. The range around the
average cycle time is always displayed.
Based on the histogram, you can see the extent of the jitter. Multiple bars mean high jitter
and indicate unsuitable settings for the HMI Enable Time. A bar with 100% is ideal.
Figure 5-2 Tuning Screen
Controlling a process with WinAC MP
5.2 Description of the Home Screen and the Tuning Screen
WinAC MP 2008
62 Operating Instructions, 03/2009, A5E00981151-02
Tuning screen
The Tuning Screen contains the following elements:
Buttons for the operating functions of WinAC MP
Clear: the recording of the cycle times is restarted
Buttons for functions
Home >>: Changing to the Home screen
Exit: freely configurable with WinCC flexible functions (e.g. hotkeys), e.g. return to
start screen
Setting the HMI Enable Time in ms for the HMI device - HMI Enable Time
Default setting: 50 ms
Display of the cycle time - Cycle Time [ms]
Last: Last cycle time
Avg: Average cycle time
Max: Maximum cycle time
Min: Minimum cycle time
Cycle time information (histogram)
Further information
For information on how to configure the Hotkeys for WINAC MP, refer to the Operating
WinAC MP with hotkeys (Page 63) section.
See also
Composition of the cycle time (Page 72)
Setting the "HMI enable time" (Page 73)
Controlling a process with WinAC MP
5.3 Function key assignment based on the WinAC system library
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 63
5.3 Function key assignment based on the WinAC system library
5.3.1 Operating the WinAC MP with hotkeys
Introduction
A hotkey specifies a key or key combination that can be used to actuate the button.
You can assign different functions to the hotkeys for each one of the screens. This
assignment applies only to the screen in which you have defined the button.
NOTICE
If a screen of an alarm view or an alarm window is overlapped, then the function keys are
still active in runtime.
Requirement
The screen in which you want to assign a button is open.
The Properties window in WinCC flexible is open.
Specify hotkey
To do so, follow these steps:
1. Select the desired button, for example STOP.
2. Click on the "General" group in the Properties window.
3. In the selection list in the "Hotkey" area, select a key or key combination for the hotkey
with which the button will be actuated.
4. If necessary, configure the button in the Properties window:
Result: The button is assigned accordingly in the selected screen.
Controlling a process with WinAC MP
5.3 Function key assignment based on the WinAC system library
WinAC MP 2008
64 Operating Instructions, 03/2009, A5E00981151-02
5.3.2 Starting WinAC MP - Start
Requirements
The following conditions must be met to start WinAC MP on the HMI device:
You have transferred the WinCC flexible Runtime project from the configuration PC to the
HMI device and the project contains the two screens from the WinAC MP system library.
You have the option of transferring WinAC MP and the License Key from the
configuration PC to the HMI device.
Starting WinCC flexible Runtime on the HMI device
1. Check that the HMI device is turned on.
2. Press "Start" in the Loader.
Result: WinCC flexible Runtime opens with the Home Screen on the HMI device.
Starting WinAC MP
The "StartAtBoot" function is enabled by default for WinAC MP and WinAC MP starts
automatically after startup of the HMI device.
If the "StartAtBoot" function is not selected, start WinAC MP as follows:
1. To start WinAC MP, press "Start".
Result: WinAC MP is running.
5.3.3 Automatic WinAC MP startup - Autostart
WinAC MP provides you with an Autostart function. When this is enabled, it allows the
controller to be started in the same mode it was in before it was shut down:
Autostart = blue: Function activated: After WinAC MP starts up, WinAC MP changes to
mode it was in before it was shut down.
Autostart = gray: Function not activated: WinAC MP remains in STOP when it starts up.
WinAC MP mode on shut down Autostart Mode after starting
No (gray) STOP STOP
Yes (blue) STOP
No (gray) STOP RUN
Yes (blue) RUN
Controlling a process with WinAC MP
5.3 Function key assignment based on the WinAC system library
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 65
5.3.4 Automatic WinAC MP start when the HMI device boots - StartAtBoot
Sequence from switching on the HMI device until WinAC MP changes to RUN
The following screens show the sequence between power on of the HMI device and
WinAC MP entering the RUN state.
Note
Note on the "Autostart" function for the successive screen
If autostart is enabled WinAC MP changes after startup either to RUN, or to STOP mode,
wherever it was prior to closing.
Basic sequence after turning on the HMI device
6WDUW$W%RRW
6WDUW
&OLFN581RU
$XWRVWDUW
&OLFN6723
6KXWGRZQ
3RZHURII
+0,GHYLFHRII +RPHVFUHHQORDGHG+0,GHYLFH:LQGRZV
&(UXQQLQJ
:LQ$&03VWDUWHG :LQ$&03LQ581
3RZHURQ
Controlling a process with WinAC MP
5.3 Function key assignment based on the WinAC system library
WinAC MP 2008
66 Operating Instructions, 03/2009, A5E00981151-02
Detailed sequence after turning on the HMI device
WR21
<
<
1
1
$XWRVWDUWWR
21
6723NH\
SUHVVHG"
67$57NH\
SUHVVHG"
581NH\
SUHVVHG"
3RZHURII"
6+87
'2:1NH\
SUHVVHG"
<
3RZHURII"
1
3RZHURQ
6WDUWRIWKH
:LQ$&03H[H
3RZHU21/('RQ
6WRSWKH
:LQ$&03H[H
3RZHU21/('RII
3/&LQ581
581/('RQ
3/&LQ6723
581/('RII
1
<
<
<
<
<
1
1
1
1
3UHUHTXLVLWH3/&ZDVLQ581EHIRUHFORVLQJ
ಱ6WDUW$W%RRWಯ
Controlling a process with WinAC MP
5.3 Function key assignment based on the WinAC system library
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 67
Automatic WinAC MP start when the HMI device boots (StartAtBoot)
You can configure WinAC MP so that it starts automatically once the HMI device has booted.
To do this, click StartAtBoot.
StartAtBoot = blue: WinAC MP is started automatically when the HMI device boots
StartAtBoot = gray: WinAC MP is not started automatically when the HMI device boots
To start WinAC MP manually, you first start the WinCC flexible project on the HMI device
so that the Home Screenopens. Then click "Start" to confirm.
See also
Automatic WinAC MP startup - Autostart (Page 64)
5.3.5 RUN and STOP modes
Mode selectorh
You can switch operating modes as follows using the mode selector:
RUN
STOP
The mode selector switch on the WinAC MP Home Screen works similar to the manual
mode selector switch on an S7 hardware controller.
Control operating mode
The mode describes the state of the CPU at any point of time.
To control the operating mode, you have the following options:
Mode selector switch
Operation using STEP 7
Note
Status indicator shows a different mode than the mode selector switch
Just as with a hardware CPU, the status indicators RUN and STOP show the current
mode of WinAC MP.
Controlling a process with WinAC MP
5.3 Function key assignment based on the WinAC system library
WinAC MP 2008
68 Operating Instructions, 03/2009, A5E00981151-02
Permissible functions during RUN or STOP
The following table shows which functions are permitted during RUN or STOP:
Switch setting
RUN Downloading a STEP 7 user program to WinAC MP
Downloading individual blocks to WinAC MP.
Using STEP 7 to modify program variables.
Changing the operating state using STEP 7.
Memory reset using the Home Screen or using STEP 7
(if you reset WinAC MP memory, WinAC MP automatically changes to
STOP).
STOP Downloading a STEP 7 user program to WinAC MP
Downloading individual blocks to WinAC MP.
Using STEP 7 to modify program variables.
Memory reset using the Home Screen or using STEP 7.
Archiving and restoring a STEP 7 user program.
Prohibited functions during RUN or STOP
The following table shows which functions are prohibited during RUN or STOP:
Switch setting
RUN Archiving and restoring a STEP 7 user program.
STOP It is not possible to change the operating mode with STEP 7. The mode
selector switch has highest priority.
NOTICE
Priority of the operating modes
If the mode selector switch has been used to change the mode to "STOP", you cannot use
STEP 7 to change the mode to "RUN".
⇒ The mode selector switch in "STOP" has highest priority.
If the mode selector switch has been used to change the mode to "RUN", you can use
STEP 7 to change the mode to "STOP".
⇒ The "STOP" mode has highest priority.
Controlling a process with WinAC MP
5.3 Function key assignment based on the WinAC system library
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 69
5.3.6 Memory reset with MRES
How a memory reset works
MRES works in the same way as a memory reset of a hardware CPU - all the WinAC MP
settings are reset to the defaults:
The STEP 7 user program is deleted in the work memory and the load memory (OBs,
DBs, FCs, FBs and system data).
The content of the memory areas (I, Q, M, T, and C) is reset to 0.
System settings are reset to their default values (for example, the size of process image
areas and the size of the diagnostic buffer).
Deletes all active communications jobs and all open communications.
All online connections are disconnected, for example, STEP 7, WinCC, WinCC flexible,
PROFIBUS or S7 communication.
When do you need to reset memory?
You should reset WinAC MP memory before you download a new STEP 7 user program to
WinAC MP.
You must perform a memory reset if the STOP indicator in the Home Screen is flashing.
Possible causes are:
Errors have been detected in the work memory, for example, the size of the STEP 7 user
program exceeds that of the work memory.
WinAC MP was turned off and on again as a result of an error.
How do I reset memory?
There are several ways of resetting WinAC MP memory:
In the "Home Screen", press the "MRES" button .
Note
After having pressed the MRES button on the HMI device, you are requested confirm the
CPU memory reset. Confirm this dialog.
Reset memory from the SIMATIC Manager of STEP 7.
The STOP display flashes during the memory reset.
Result: WinAC MP has been reset to its initial status.
Controlling a process with WinAC MP
5.3 Function key assignment based on the WinAC system library
WinAC MP 2008
70 Operating Instructions, 03/2009, A5E00981151-02
5.3.7 Status indicators
Meaning of the status indicators
The status displays on the Home Screen indicate the current operating state and support
troubleshooting. These status indicators correspond to the LED displays on an S7 hardware
PLC.
You cannot change the status of WinAC MP by touching the status indicators.
Status indicators
Display Description
ON Lit when WinAC MP has started up (Start).
Not lit if WinAC MP was switched off (Shutdown).
INTF Internal error
This display lights up when an error condition occurs in WinAC MP, for example, a
programming error, arithmetic error, timer error or counter error.
If the STEP 7 user program handles the error by executing OB 80 or OB 121, the INTF
indicator goes off after 3 seconds if there is no follow-on error condition.
EXTF External fault.
This display lights up when a fault or error condition occurs outside of WinAC MP, for
example, a hardware fault, parameter error, communication error or I/O fault.
If the STEP 7 user program handles the error by executing OB 122, the EXTF indicator
goes off after 3 seconds if there is no follow-on error condition.
BUSF Bus fault
This indicator flashes if there is an error in communication with the distributed
PROFIBUS I/O.
RUN Lights up according to the operating mode (RUN or STOP).
STOP When RUN is flashing and STOP is lit (steady), the control program has reached a
breakpoint (RUN flashes) or the control is starting up.
Note: The displays RUN and STOP show the actual operating mode of the controller.
The RUN and STOP mode selector positions show the selected mode (similar to the
mode selector position on an S7 CPU front panel). This can differ from the current
operating mode. Example: Changing the operating mode with STEP 7 causes the
status indicators to change, but the mode selector does not change.
Controlling a process with WinAC MP
5.3 Function key assignment based on the WinAC system library
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 71
Flashing RUN and STOP status indicators
Display Description
RUN STOP
Flashes Flashes WinAC MP is in DEFECT mode. All status indicators flash (see next
paragraph)
Flashes On The STEP 7 user program has stopped at a breakpoint.
A warm restart or cold restart is in progress. RUN flashes until startup
has been completed. The time required for the restart operation
depends on the time required to execute the startup OB.
OFF Flashes WinAC MP memory reset is required (MRES button).
A WinAC MP memory reset is active.
All status indicators flash
If all the status indicators flash at the same time, WinAC MP is in an error status that cannot
be eliminated by resetting memory with MRES.
To recover from this condition, you must perform the following steps:
1. Turn off WinAC MP (Shutdown)
2. Restart WinAC MP (Start).
Result: The STOP status indicator flashes, RUN is off.
3. Reset WinAC MP memory by pressing the MRES button.
4. Download the hardware configuration with STEP 7 and the STEP 7 user program or
restore an archived user STEP 7 user program.
If the problem is not eliminated by turning WinAC MP off and on again, restart the HMI
device.
Controlling a process with WinAC MP
5.3 Function key assignment based on the WinAC system library
WinAC MP 2008
72 Operating Instructions, 03/2009, A5E00981151-02
5.3.8 Composition of the cycle time
Composition of the cycle time
The cycle time is comprised of the following execution times:
OB1 execution time
HMI Enable Time
HMI runtime
Communication
Options
The OB1 execution time is executed with highest priority. When the execution has been
completed, a configurable "HMI Enable Time" is available to the HMI device. You can use
this to control how much HMI runtime execution time is available to the communication and
the options.
Time data on configurable "HMI Enable Time":
Default setting: 50 ms
Minimum: 1 ms
Time-critical applications
When they occur, interrupt OBs (OB 35 and OB 40) interrupt the execution of the OB 1 or
the HMI Enable Time.
The following screen shows an example of the events triggering interrupt OB 35 and OB 40.
&\FOH7LPH
2%H[HFXWLRQWLPH +0,(QDEOH7LPH
57 &RPPXQLFDWLRQ 2SWLRQV

:ULWH3,4 5HDG3,, :ULWH
3,4
2%
2%
2%
2%
2%
2%
57
57+0,UXQWLPH
How the "HMI Enable Time" influences the cycle time
A small "HMI Enable Time" shortens the cycle time The next call OB 1 takes less time.
Note
"Selecting a sufficiently large HMI Enable Time"
Long interruptions of the HMI Enable Time reduce performance of the HMI device. The
execution times of the interrupt OBs reduce the HMI Enable Time(1:1). For this reason you
have to select a sufficiently large "HMI Enable Time".
Controlling a process with WinAC MP
5.3 Function key assignment based on the WinAC system library
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 73
5.3.9 Setting the "HMI enable time"
Options for setting the "HMI Enable Time"
1. Using the supplied user interface in the figure "Tuning Screen" to set the HMI enable
time:
You can set the HMI Enable Time in the range from 1 ms to 5999 ms in the
"HMI Enable Time" input field of the tuning screen. The default is 50 ms.
2. Configuring the "HMI Enable Time" with a system function:
The "HMI Enable Time" can be configured in WinCC flexible using the
"SetHMIEnableTime" system function.
3. For additional information, refer to the chapters: Examples of configuring objects
(Page 83) and WinAC MP functions (Page 80)
Note
Selecting a sufficiently large HMI Enable Time
Set an appropriate HMI Enable Time at the beginning of your configuration and
commissioning phase. Observe the screen change and refresh times during operation of
the panel.
Reduce the HMI Enable Time in small steps and continue to observe the screen change
and refresh times. If the screen change and refresh times deteriorate, increase the HMI
Enable Time again. Application-related time interrupts (e.g. 0B35) or block calls can lead
to other negative effects which can be corrected by extending the HMI Enable Time .
Controlling a process with WinAC MP
5.4 Archiving and restoring STEP 7 user programs
WinAC MP 2008
74 Operating Instructions, 03/2009, A5E00981151-02
5.4 Archiving and restoring STEP 7 user programs
5.4.1 Conditions for archiving and restoring
Definition: Archive file
The archive for WINAC MP functions like a S7-CPU micro memory card.
You use an archive file to archive the STEP 7 user program of WinAC MP or to restore the
STEP 7 user program after a WinAC MP memory reset.
WinAC MP uses two types of archive file:
The archive file has the ending .wld. The file is created generated using the "Archive" call
and restored with "Restore". The path name of the file is specified as a parameter at both
calls.
The actual values of the project in Runtime are saved to the archive file:
Current STEP 7 user program
Current system configuration
Current values of the DBs
WinAC MP saves the current user program, including the initial values and configuration
data, to a file with the ending .waf .
The file is saved with device backup and restored with "restore":
with ProSave on the configuration PC
with backup/restore in the Control Panel on the HMI device
Note
WinAC is closed automatically for the backup. After backup it is necessary to restart
WinAC, e.g. with reboot.
Controlling a process with WinAC MP
5.4 Archiving and restoring STEP 7 user programs
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 75
Additional information
For more information about the backup and restore functions, refer to the Multi Panels
MPx77 and WinCC flexible manuals.
%DFNXS
5HVWRUH
$UFKLYH
5HVWRUH
00&6'&DUG
RGHU86%6WLFN
:$)
:/'
$FWXDOYDOXHV ,QLWLDOYDOXHV
Q
Q
Q
Q
Q
Q
 
 
 
 
$%%$ $))(
 
Requirements
The following constraints apply to WLD archive files:
The WinAC MP system functions "Archive"" and "Restore" can only be used with S7 user
programs requiring up to a specific size of load memory.
To archive or restore an archive file, WinAC MP must be in STOP mode.
An archive file works similar to the memory card of an S7-CPU.
Only exception: After a memory reset, WinAC MP does not load the archive file
automatically and must be loaded manually.
For information about the sizes of the various characteristics, refer to section Technical
specifications (Page 94).
Note
Retentive data are not archived.
Controlling a process with WinAC MP
5.4 Archiving and restoring STEP 7 user programs
WinAC MP 2008
76 Operating Instructions, 03/2009, A5E00981151-02
5.4.2 Creating an archive file - Archive
Requirement
The Archive system function is assigned a valid file name and storage location for the
archive file at the "FilePath:" parameter.
Optional storage locations for the archive file
MP 177: internal Flash memory, Storage Card MMC, Storage Card USB and Network
MP 277: internal Flash memory, Storage Card MMC, Storage Card USB and Network
MP 377: internal Flash memory, Storage Card MMC, Storage Card USB, Storage Card
CF and Network
Creating an archive file on the HMI device
1. Press STOP to set WinAC MP to STOP mode.
2. Press the Archive button.
Result: The archive file is set up with the default name Default.wld in the default path:
\Flash\AddOn\WinACMP\.
Creating an archive file in SIMATIC Manager
As an alternative, you can also create the archive file in SIMATIC Manager in STEP 7:
1. Select File > Memory Card File > New in SIMATIC Manager.
2. Enter a name for the archive file.
3. Select the storage location for the archive file and confirm with "OK":
Result: The archive file is created with the *.wld extension.
Controlling a process with WinAC MP
5.5 Exit WinAC MP on the HMI device - Shutdown
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 77
5.4.3 Restoring an archive file - Restore
Requirements
The storage medium (MMC, USB, ...) with the archive file is plugged in.
The Restore system function is assigned a valid file name and storage location for the
archive file at the "FilePath:" parameter.
Restoring configuration data from WLD archive file
1. Press the "STOP" button to change WinAC MP to STOP mode.
2. Press the Restore button.
3. Wait until the archive file "Restore" has been restored.
4. Switch WinAC MP to RUN to start the STEP 7 user program.
Result
WinAC MP starts with the new project data at the next RUN command.
5.5 Exit WinAC MP on the HMI device - Shutdown
Exiting WinAC MP
To exit WinAC MP, press the "Shutdown WinAC MP" button.
Result: WinAC MP is closed and all status indicators are reset. WinCC flexible Runtime
remains active.
Controlling a process with WinAC MP
5.5 Exit WinAC MP on the HMI device - Shutdown
WinAC MP 2008
78 Operating Instructions, 03/2009, A5E00981151-02
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 79
Setting up WinAC MP for your application 6
6.1 Working with WinCC flexible
WinCC flexible
The WinCC flexible configuration software is used to create your configuration on the
configuration PC (PC or PG) operating on a Windows platform.
WinCC flexible Runtime
WinCC flexible Runtime is an easy-to-use, high-performance software for the visualization of
processes in projects you created with the WinCC flexible configuration software.
WinCC flexible Runtime is designed for visualization and control of machines and small
plants. The Runtime software has a window-based pixel-graphics user interface. Due to its
short response times, the software features secure process operation, jogging at the
machine and secure data acquisition.
WinAC MP system library
Tip
To use all the functions of WinAC MP, make sure that the WinAC MP option is installed on
the configuration PC.
The WinAC system library for the Multi Panels are included in the scope of delivery of
WinAC MP. The library contains the follows screens: Home Screen and Tuning Screen.
You can use the screens without needing to make any changes. You can, however, also
adapt the screens to your needs in WinCC flexible or create a new project.
When you install WinAC MP, all WinAC MP functions are integrated in WinCC flexible. In
WinCC flexible, you can copy pictures and picture objects to other projects.
Open WinCC flexible with Start > SIMATIC > WinCC flexible 2008 > WinCC flexible.
Further information
For information on Integrating a WinAC system library, refer to the WinAC system library
(Page 57) section.
For more information on creating pictures and working with the functions in WinCC flexible,
refer to the documentation on WinCC flexible.
Setting up WinAC MP for your application
6.2 WinAC MP functions
WinAC MP 2008
80 Operating Instructions, 03/2009, A5E00981151-02
6.2 WinAC MP functions
The following table shows all functions and objects with which functions can be configured
that are available for visualization of WinAC MP in WinCC flexible.
System functions WinCC flexible
Use the following system functions in WinCC flexible:
UpdateTags, to read or update values
SetValue, to set or change values in WinAC MP
Overview of Objects
The objects whose functions can be parameterized are organized as follows:
Abbreviatio
n
Object Event
Variable Variable Changed value, High limit violation, Low limit violation
Screen Screen Loaded, Cleared
Scr obj Screen object Press, Release, Click, Change, Switch on, Switch off, Activate, Deactivate
Function Function key global/local Press, Release
System System key global/local Press, Release
Script * Usable in the script
* Abbreviation "Script" is not available for the configuring for MP 177
Overview of the additional objects for WinAC MP 2008
Function name Description Parameters Action Abbreviati
on
SetHMIEnableTime Sets the value of the
HMIEnableTimeof WinAC MP
(in ms).
HMIEnableTime : (input) - Variable
Scr obj
Function
System
UpdateHMIEnableTime *) Updates the value of the
HMIEnableTime of WinAC MP
(in ms)
HMIEnableTime : (output) Switch off
Switch on
Screen
*) For explanation, see the end of the next table.
Setting up WinAC MP for your application
6.2 WinAC MP functions
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 81
Overview of Objects
Function name Description Parameters Action Abbreviati
on
Archive Stores the current STEP 7 user
program, the current system
configuration and the current
values of the DBs in an archive
file.
File path: - Scr obj
Function
System
ClearCycleTimeBuffer Deletes the cycle time data of
the histogram.
- - Variable
Scr obj
Function
System
ControlWinACMP Starts or closes WinAC MP. WinAC : (input)
0 = Shutdown WinACMP
1 = Start WinACMP
- Variable
Scr obj
Function
System
GetWinACMPStartMode *) Reads the WinAC MP 'desired'
operating mode after the HMI
device has started up.
StartMode: (output) Switch off
Switch on
Variable
Screen
Scr obj
Function
System
GetWinACMPVersion *) Reads the value of the version
number from WinAC MP.
Version : (output) Switch off
Switch on
Variable
Screen
Scr obj
Function
System
Script
Restore Loads the STEP 7 user
program, system configuration
and DBs from an archive file.
File path: - Scr obj
Function
System
SetKeySwitch Sets the mode selector switch to
RUN or STOP and is also used
for memory reset.
Key Switch : (input)
0 = MRES
1 = STOP
3 = RUN
- Variable
Scr obj
Function
System
SetRestartMethod Sets the restart mode, either
cold restart (CRST) or warm
start (WRST)
Action : (input)
0 = WarmRestart
1= ColdRestart
Variable
Scr obj
Function
System
SetSleepTime Sets the value of the
HMIEnableTimeof WinAC MP (in
ms).
SleepTime : (input) - Variable
Scr obj
Function
System
SetWinACStartAtBoot Sets whether WinAC MP starts
automatically after the HMI
device boots.
StartAtBoot : (input)
0 = StartAtBootOff
1 = StartAtBootOn
- Variable
Scr obj
Function
System
Script
SetWinACMPStartMode Sets WinAC MP to the 'desired'
operating mode after the HMI
device has started up.
Action : (input)
0 = AutoStartOff
1 = AutoStartOn
Variable
Scr obj
Function
System
Script
StartHistogramm *) Starts the cyclic sending of
histogram values. (this function
is called in WinCC flexible with
Events > Loaded)
Percent[n]: (output)
CycleTime[n]: (output)
Y-Axis bounds[n]: (output)
RegisterID[n]: (output)
Switch off
Switch on
Screen
Scr obj
Function
System
Setting up WinAC MP for your application
6.2 WinAC MP functions
WinAC MP 2008
82 Operating Instructions, 03/2009, A5E00981151-02
Function name Description Parameters Action Abbreviati
on
StopHistogramm Stops the cyclic sending of
histogram data (this function is
called in WinCC flexible with
Events > Cleared)
RegisterID: (input) - Screen
Scr obj
Function
System
UpdateAverageCycleTime *) Updates the display of the
average cycle time (in ms).
CycleTime : (output) Switch off
Switch on
Screen
UpdateAverageExecTime *) Updates the display of the
average OB 1 execution time (in
ms).
CycleTime : (output) Switch off
Switch on
Screen
UpdateBUSF1LEDVariable *) Updates the status indicator of
the LED variable BUSF1.
BUSF1 : (output)
Switch off
Switch on
Screen
UpdateBUSF2LEDVariable *)
No function in WinAC MP V4.0/4.1.1
Updates the status indicator of
the LED variable BUSF2.
BUSF2 : (output) Switch off
Switch on
Screen
UpdateControllerForStartAtBoot *) Reads whether WinAC MP has
started automatically after the
HMI device booted.
StartAtBoot : (output) Switch off
Switch on
Screen
UpdateEXTFLEDVariable *) Updates the status indicator of
the LED variable EXTF.
EXTF : (output) Switch off
Switch on
Screen
UpdateINTFLEDVariable *) Updates the status indicator of
the LED variable INTF.
INTF : (output) Switch off
Switch on
Screen
UpdateKeySwitchSetting *) Updates the status indicator for
the position of the mode selector
switch.
KeySwitch : (output)
0= MRES
1 = STOP
2 = RUN
Switch off
Switch on
Screen
UpdateLastCycleTime *) Updates the display of the last
cycle time (in ms).
CycleTime : (output) Switch off
Switch on
Screen
UpdateMaximumCycleTime *) Updates the display of the
longest cycle time (in ms).
CycleTime : (output) Switch off
Switch on
Screen
UpdateMinimumCycleTime *) Updates the display of the
shortest cycle time (in ms).
CycleTime : (output) Switch off
Switch on
Screen
UpdatePowerLEDVariable *) Updates the status indicator of
the LED variable ON.
Power : (output) Switch off
Switch on
Screen
UpdateRUNLEDVariable *) Updates the status indicator of
the LED variable RUN.
Run : (output) Switch off
Switch on
Screen
UpdateSleep Time *) Updates the value of the
HMIEnableTime of WinAC MP
(in ms)
SleepTime : (output) Switch off
Switch on
Screen
UpdateSTOPLEDVariable *) Updates the status indicator of
the LED variable STOP.
STOP : (output) Switch off
Switch on
Screen
*) The configuration of all WinAC MP update functions is permitted only once per screen.
The WinAC MP update function must be configured for the "Screen loaded" event with the
Action parameter "SwitchOn". The WinAC MP update function must be configured for the
"Screen unloaded" event with the Action parameter "SwitchOff". If a function is called more
than once with different variables in one screen, only the variable activated last is updated.
You should therefore only use identical variables as parameters of the functions within a
screen.
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 83
Examples of configuring objects 7
7.1 Configuration of the RUN button with corresponding LED display using
WinCC flexible
Introduction
The following example shows you how to configure a RUN button with integrated LED
indicator.
Objective:
The button "RUN" will change WinAC MP to RUN mode. The vector graphic shows an
"LED". The color will always represent the current mode RUN or STOP.
Basic design
Step 1 Click Events > "SetKeySwitch" function, "KeySwitch" parameter. RUN > RUN WinAC MP
Step 2 Internal variable "RUNLED" data type INT < UpdateRUNLEDVariable function, Action: Switch ON < events
loaded (screen object) < feedback: Value 3 = RUN ; Value 0 = STOP
Step 3 UpdateRUNLEDVariable function, Action: Switch OFF < events cleared (screen object)
Step 4 Internal variable "RUNLED" data type INT > Animations background color Value 3 = Green;
Value 0 = Red
Examples of configuring objects
7.1 Configuration of the RUN button with corresponding LED display using WinCC flexible
WinAC MP 2008
84 Operating Instructions, 03/2009, A5E00981151-02
Configuration
1. Create a new project in WinCC flexible with the option Create an empty project.
2. In the next dialog "Device selection", select the Multi Panel you are using. In our example,
we are using the MP 277 10" Key. Confirm with "OK".
3. Open Toolbox > Simple Objects and design the "RUN" button and LED as a "circle"
vector graphic as shown in the figure below.
4. Assign a switching function to the RUN button: Select the RUN button and click on
Events > Click in the lower area of WinCC flexible.
5. Configure System Functions > WinAC MP > SetKeySwitch.
6. Select "RUN" as the function for "KeySwitch".
7. Click on an empty position in the screen object.
Examples of configuring objects
7.1 Configuration of the RUN button with corresponding LED display using WinCC flexible
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 85
8. Select the events > Loaded > UpdateRUNLEDVariable
9. For the parameter "RUN: (output)" of the "UpdateRUNLEDVariable" function, configure
the internal variable "RUNLED" of the data type INT.
10. For the "Action" parameter of the "UpdateRUNLEDVariable" function, select the value
"Switch On".
11. Click on an empty position in the screen object.
12. Select Events > Cleared > UpdateRUNLEDVariable.
13. For the parameter "RUN: (output)" of the "UpdateRUNLEDVariable" function, configure
the internal variable "RUNLED" of the data type INT.
14. For the "Action" parameter of the "UpdateRUNLEDVariable" function, select the value
"Switch OFF".
Examples of configuring objects
7.2 Configuring a histogram
WinAC MP 2008
86 Operating Instructions, 03/2009, A5E00981151-02
15. Configure the variable with the "circle" vector graphic in Animations > Appearance.
16. Save your project with Project > Save.
17. Download your project to the Multi Panel with Project > Transfer.
7.2 Configuring a histogram
Introduction
The following example shows you how to configure a histogram:
Examples of configuring objects
7.2 Configuring a histogram
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 87
Basic design
Step 1 Events loaded (screen object) > "StartHistogramm" function with parameter Action: SwitchON
> WinAC MP supplies histogram data
Step 2 Internal array variable PERCENT, CYCLE_TIME, Y_AXIS and REGISTER_ID < feedback
Step 3 StopHistogramm parameter "RegisterID" < events cleared (screen object)
Step 4 Internal array variable CYCLE_TIME[0] to [6] > IO field_1 to IO field_7> Process > Variable
Step 5 Internal array variable Y_AXIS[1] > Bar_1 > maximum value > variable and internal
array variable PERCENT[0] > Bar_1 > Process > Variable
Step 6 Internal array variable Y_AXIS[0] > Bar_2 to Bar_8 > maximum value > variable and internal array variable
PERCENT[0] to [6] > Bar_2 to Bar_8 > Process > Variable
Creating the objects
1. Create a new project in WinCC flexible with Create an empty project.
2. In the next dialog "Device selection", select the Multi Panel you are using. In our example,
we are using the MP 277 10" Key. Confirm with "OK".
Examples of configuring objects
7.2 Configuring a histogram
WinAC MP 2008
88 Operating Instructions, 03/2009, A5E00981151-02
3. Open Toolbox > Simple Objects and define the area using a rectangle.
4. You create the Y axis with a bar (Bar_1) from the simple objects:
5. You create the bars (Bar_2 to Bar_8) in the histogram display with a total of 7 bars
from the simple objects:
Examples of configuring objects
7.2 Configuring a histogram
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 89
6. Disable the "Display scale" property for the seven bars.
7. Below the 7 bars, configure an IO field with the "Output" property.
Assigning the tags
1. In WinCC flexible, click on Project >HMI Station > Communication > Tags.
2. Create the tags based on the figure below using the right mouse button and "Add Tag".
Examples of configuring objects
7.2 Configuring a histogram
WinAC MP 2008
90 Operating Instructions, 03/2009, A5E00981151-02
Assigning the events
1. In WinCC flexible, click on Project >HMI Station > Screens > Bild_1.
2. Complete the function list for Events > Loaded based on the following figure:
3. Complete the function list for Events > Cleared based on the following figure:
Examples of configuring objects
7.2 Configuring a histogram
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 91
Assign limits and tags to the X axis, Y axis and bars
1. Click on the first I/O field on the X axis and assign the tags based on the following figure:
2. In the same way, assign the elements of the array variable CYCLE_TIME to the
remaining 6 IO fields. Make sure that the CYCLE_TIME variable is incremented by 1 in
each case.
Process variable = CYCLE_TIME [n]; n = 0 ...
3. Click on the Y axis and assign the variables based on the following figure:
Examples of configuring objects
7.2 Configuring a histogram
WinAC MP 2008
92 Operating Instructions, 03/2009, A5E00981151-02
4. Click on the first bar in the histogram (Bar_2) and assign the variables based on the
following figure:
Maximum value variable = Y_AXIS[0]
Process variable = PERCENT[n]; n = 0 ...
5. In the same way, assign the tags to the remaining 6 bars. Make sure that each element of
the PERCENT array variable is incremented by the count of 1.
Saving and transferring a project
1. Save your project with Project > Save.
2. Download your project to the Multi Panel with Project > Transfer.
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 93
Performance features and technical specifications A
A.1 Performance features
Summary of the performance features of WinAC MP
Below, you will find a brief outline of the main performance features of WinAC MP:
4 accumulators (accumulator 1 to 4)
Communication as PROFIBUS-DP master complying with DPV1
Only distributed I/O - no integrated inputs and outputs
WinAC MP communicates with the distributed I/O as a PROFIBUS-DP master. As a DP
master, WinAC MP can communicate with up to 32 DP slaves.
A.2 Specifications
A.2.1 Order numbers
Order numbers
WinAC MP 177: 6ES7 671-4EE00-0YA0
WinAC MP 277: 6ES7 671-5EF01-0YA0
WinAC MP 377: 6ES7 671-7EG01-0YA0
Performance features and technical specifications
A.2 Specifications
WinAC MP 2008
94 Operating Instructions, 03/2009, A5E00981151-02
A.2.2 Technical specifications
Technical specifications
WinAC MP 177 WinAC MP 277 WinAC MP 377
MLFB 6ES7671-4EE00-0YA0 6ES7671-5EF01-0YA0 6ES7671-7EG01-0YA0
Associated programming package STEP 7 V 5.4 + SP4 STEP 7 V 5.4 + SP4 STEP 7 V 5.4 + SP4
Firmware version V4.1.1 V4.1.1 V4.1.1
Memory
Working memory
Integrated 128 KB 256 KB 512 KB
Expandable No No No
Blocks
DB
Number, max. 512
(FBs+FCs+DBs=512)
1024
(FBs+FCs+DBs=1024)
2048
(FBs+FCs+DBs=2048)
Size, max. 64 KB 64 KB 64 KB
FB
Number, max. 512
(FBs+FCs+DBs=512)
1024
(FBs+FCs+DBs=1024)
2048
(FBs+FCs+DBs=2048)
Size, max. 64 KB 64 KB 64 KB
FC
Number, max. 512
(FBs+FCs+DBs=512)
1024
(FBs+FCs+DBs=1024)
2048
(FBs+FCs+DBs=2048)
Size, max. 64 KB 64 KB 64 KB
OB
Number, max. 18 18 18
Size, max. 64 KB 64 KB 64 KB
Nesting depth
Per Priority Class 8 8 16
Error OBs 2 2 2
Timers /counters / retentivity:
S7 counters
Number 128 256 512
Retentivity
- configurable Yes Yes Yes
- Preset 8 8 8
Counting range
- Lower Limit 0 0 0
- Upper Limit 999 999 999
Performance features and technical specifications
A.2 Specifications
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 95
WinAC MP 177 WinAC MP 277 WinAC MP 377
IEC counters
Included Yes
( SFB 0, SFB 1, SFB 2)
Yes
( SFB 0, SFB 1, SFB 2)
Yes
( SFB 0, SFB 1, SFB 2)
S7 timers
Number 128 256 512
Retentivity
- configurable Yes Yes Yes
- default 0 0 0
Time range
- Lower Limit 10 ms 10 ms 10 ms
- Upper Limit 9990 s 9990 s 9990 s
IEC timers
Included Yes
( SFB 3, SFB 4, SFB 5)
Yes
( SFB 3, SFB 4, SFB 5)
Yes
( SFB 3, SFB 4, SFB 5)
Retentivity
Retentivity total 64 KB 128 KB 256 KB
Bit memories
Number, max. 2 KB 2 KB 4 KB
Retentivitiy present Yes Yes Yes
Data blocks
Number, max. 512 1024 2048
Size, max. 64 KB 64 KB 64 KB
Retentivity configurable Yes (max. 64 KB) Yes (max. 128 KB) Yes (max. 256 KB)
Local data
per priority class, max. configurable, 16384 bytes
for all execution levels
configurable, 16384 bytes
for all execution levels
configurable, 16384 bytes
for all execution levels
Address area
I/O address area
Inputs 2 KB 4 KB 8 KB
Outputs 2 KB 4 KB 8 KB
Distributed of this
- Inputs 2 KB 4 KB 8 KB
- Outputs 2 KB 4 KB 8 KB
Process image
Inputs 1 KB 2 KB 2 KB
Outputs 1 KB 2 KB 2 KB
Inputs, adjustable 1 KB 2 KB 2 KB
Outputs, adjustable 1 KB 2 KB 2 KB
Inputs, preset 512 bytes 512 bytes 512 bytes
Performance features and technical specifications
A.2 Specifications
WinAC MP 2008
96 Operating Instructions, 03/2009, A5E00981151-02
WinAC MP 177 WinAC MP 277 WinAC MP 377
Outputs, preset 512 bytes 512 bytes 512 bytes
Consistent Data, max. 32 bytes 32 bytes 32 bytes
Hardware Configuration
Number of DP masters
Integrated 1 1 1
Time
Operating Hours Counter
Number 8 8 8
Number range 0 to 7 0 to 7 0 to 7
S7 message functions
Process diagnostics messages Yes Yes Yes
Test and startup functions
Status/control
Status/modify variable Yes
(status blocks, single
step, breakpoint)
Yes
(status blocks, single
step, breakpoint)
Yes
(status blocks, single step,
breakpoint)
Force
Force No No No
Diagnostic buffer
Included Yes Yes Yes
No. of entries, max. 1000 1000 1000
Number of entries, preset 120 120 120
Configurable Yes Yes Yes
Communications functions
Number of logical connections 8 16 32
PG/OP communication Yes Yes Yes
Routing Yes Yes Yes
Global data communication
supported No No No
S7 basic communication
supported No No No
S7 Communication
supported Yes (PUT/GET,
BSEND/BRCV,
USEND/URCV)
Yes (PUT/GET,
BSEND/BRCV,
USEND/URCV)
Yes (PUT/GET,
BSEND/BRCV,
USEND/URCV)
As server Yes Yes Yes
As client Yes Yes Yes
User data per job, max. 480 bytes 480 bytes 480 bytes
Number of connections
Total 8 (DP max. 4, remainder
PROFINET)
16 (DP max. 8, remainder
PROFINET)
32 (DP max. 8, remainder
PROFINET)
Performance features and technical specifications
A.2 Specifications
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 97
WinAC MP 177 WinAC MP 277 WinAC MP 377
Reserved for PG communication 1 1 1
Reserved for OP communication 1 1 1
Usable for routing 6 14 30
1st interface
DP master
Maximum number of connections 4 8 8
Services
- PG/OP Communication Yes Yes Yes
- Routing Yes Yes Yes
- Global Data Communication No No No
- S7 basic communication No No No
- S7 Communication Yes Yes Yes
- Equidistant Mode Support No No No
- SYNC / FREEZE Yes Yes Yes
- Activation/deactivation of DP
slaves Yes Yes Yes
- DPV1 Yes Yes Yes
Transmission rates, max. 12 Mbit/s 12 Mbit/s 12 Mbit/s
Number of DP slaves, max. 32 32 32
Address area
- Inputs, max. 2 KB 4 KB 8 KB
- Outputs, max. 2 KB 4 KB 8 KB
CPU/Programming
Configuration software
WinCC flexible Compact Yes No No
WinCC flexible Standard Yes Yes Yes
WinCC flexible Advanced Yes Yes Yes
Programming language
LAD Yes Yes Yes
FBD Yes Yes Yes
STL Yes Yes Yes
SCL Yes Yes Yes
CFC Yes Yes Yes
Operating systems
Windows CE Yes (version 5.0 or
higher)
Yes (version 5.0 or
higher)
Yes (version 5.0 or higher)
Online language
Number 1 (English) 1 (English) 1 (English)
Performance features and technical specifications
A.3 Supported OBs
WinAC MP 2008
98 Operating Instructions, 03/2009, A5E00981151-02
A.3 Supported OBs
A.3.1 OBs for the main cycle of the program and for cold and warm restarts
OB 1
WinAC MP executes OB 1 at cyclic intervals: When OB1 has been executed, the
HMI Enable Time starts. The operating system then starts to execute OB 1 again. Cyclic
execution of OB 1 starts when startup is complete. You can call function blocks (FBs, SFBs)
or functions (FCs, SFCs) in OB 1.
Definition: Warm restart
WinAC MP executes OB 100 before the free cycle (OB 1) is started. A warm restart clears
the inputs of the distributed I/O (PII) and sets the outputs of the distributed I/O (PIQ) to a
predefined safe state (default setting is 0). A warm restart retains the current values of the
retentive memory areas of bit memories (M), timers (T), counters (C), and data blocks (DBs).
All non-retentive memory areas are then set to "0".
Definition: Cold restart
WinAC MP executes OB 102 before the free cycle (OB 1) is started. Like a warm restart, a
cold restart resets the inputs of the distributed I/O (PII) and sets the outputs of the distributed
I/O (POI) to a pre-defined safe state (default is 0). A cold restart resets the retentive memory
(M, T, and C) or sets it to its default setting (DB). All non-retentive memory areas are then
also set to "0".
Performance features and technical specifications
A.3 Supported OBs
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 99
A.3.2 Supported organization blocks (OBs)
Organization blocks (OBs) supported by WinAC MP 2008
OB Description Priority class
OB 1 Cyclic program 1
OB 10 Time-of-day interrupt 2 to 24
OB 20 Time-delay interrupt 2 to 24
OB 35 Cyclic interrupt 2 to 24
OB 40 Hardware interrupt 2 to 24
OB 55 Status interrupt 2 to 24
OB 56 Update interrupt 2 to 24
OB 57 Manufacturer-specific interrupt 2 to 24
OB 80 Time error 26
OB 82 Diagnostic interrupt 24 to 26 (or 28)*
OB 83 Insert/remove interrupt 24 to 26 (or 28)*
OB 85 Program execution error 24 to 26 (or 28)*
OB 86 Rack failure 24 to 26 (or 28)*
OB 88 Processing interrupt 28
OB 100 Warm restart 27
OB 102 Cold restart 27
OB 121 Programming error Priority class of the OB causing the error
OB 122 I/O access error Priority class of the OB that was interrupted
* Priority classes 27 and 28 are valid in the priority class model of the startup.
For detailed information, refer to the STEP 7 Online Help.
Performance features and technical specifications
A.4 Supported SFCs
WinAC MP 2008
100 Operating Instructions, 03/2009, A5E00981151-02
A.4 Supported SFCs
Definition of system function (SFC)
A system function (SFC) is a function that is integrated in the operating system of the CPU
and can be called in the STEP 7 user program, when necessary.
System functions (SFCs)
WinAC MP supports the following SFCs:
SFC Name Description
SFC0 SET_CLK Sets the system clock.
SFC1 READ_CLK Reads the system clock.
SFC2 SET_RTM Sets the runtime meter.
SFC3 CTRL_RTM Starts or stops the runtime meter.
SFC 4 READ_RTM Reads the runtime meter.
SFC 5 GADR_LGC Queries the logical address of a channel.
SFC 6 RD_SINFO Reads the start information of an OB.
SFC 9 EN_MSG Enables block-related and symbol-related messages as well as group
status messages.
SFC 11 DPSYC_FR Synchronizes groups of DP slaves.
SFC 12 D_ACT_DP Deactivates and activates DP slaves.
SFC 13 DPNRM_DG Reads the diagnostic data of a DP slave.
Tested DP configuration: One ET 200M slave with one 8-input/8-output
module and one 16-output module.
SFC 14 DPRD_DAT Reads the consistent data from a DP slave.
SFC 15 DPWR_DAT Writes the consistent data to a DP slave.
SFC 17 ALARM_SQ Generates a block-related message that can be acknowledged.
SFC 18 ALARM_S Generates a block-related message that can be permanently
acknowledged.
SFC 19 ALARM_SC Queries the acknowledgement status for the last message (SFC 17 or
SFC 18).
SFC 20 BLKMOV Copies memory areas.
SFC 21 FILL Initializes a memory area.
1 word
50 words
100 words
SFC 22 CREAT_DB Creates a retentive data block in the work memory.
The current values of the DB are saved after a warm restart.
SFC 23 DEL_DB Deletes a data block.
WinAC MP allows an application to delete a non-sequence-relevant
data block.
SFC 24 TEST_DB Provides information about a data block.
In WinAC MP, SFC 24 can return the DB length and write-protection
flags for non-sequence-relevant data blocks, although it returns error
code 80B2 for non-sequence-relevant data blocks.
SFC 26 UPDAT_PI Updates the process input image.
SFC 27 UPDAT_PO Updates the process output image.
SFC 28 SET_TINT Sets the time-of-day interrupt (OB 10).
Performance features and technical specifications
A.4 Supported SFCs
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 101
SFC Name Description
SFC 29 CAN_TINT Cancels the time-of-day interrupt (OB 10).
SFC 30 ACT_TINT Activates the time-of-day interrupt (OB 10).
SFC 31 QRY_TINT Queries the time-of-day interrupt (OB 10).
SFC 32 SRT_DINT Starts the time-delay interrupt (OB 20).
SFC 33 CAN_DINT Cancels the time-delay interrupt (OB 20).
SFC 34 QRY_DINT Queries the time-delay interrupt (OB 20).
SFC 36 MSK_FLT Masks synchronous errors.
SFC 37 DMSK_FLT Unmasks synchronous errors.
SFC 38 READ_ERR Reads the error register.
SFC 39 DIS_IRT Disables the processing of new interrupt events.
SFC 40 EN_IRT Enables the processing of new interrupt events.
SFC 41 DIS_AIRT Delays higher priority interrupts and asynchronous errors.
SFC 42 EN_AIRT Enables the processing of new interrupt events with higher priority than
the current OB.
SFC 43 RE_TRIGR Retriggers cycle time monitoring.
SFC 44 REPL_VAL Transfers a substitute value to ACCU1 (Accumulator 1).
SFC 46 STP Changes the operating mode to STOP mode.
SFC 47 WAIT Delays the execution of the STEP 7 user program by the specified
number of microseconds, rounded up to the next millisecond.
SFC 49 LGC_GADR Queries the module slot belonging to a logical address.
SFC 50 RD_LGADR Queries all of the logical addresses of a module.
SFC 51 RDSYSST Reads all or part of a system status list.
SFC 52 WR_USMSG Writes a user-defined diagnostic event to the diagnostics buffer.
SFC 54 RD_DPARM Reads the defined parameter.
SFC 55 WR_PARM Writes the dynamic parameters.
SFC 56 WR_DPARM Writes the default parameters.
SFC 57 PARM_MOD Assigns the parameters to a module.
SFC 58 WR_REC Writes a data record.
SFC 59 RD_REC Reads a data record.
SFC 62 CONTROL Checks the connection status of an SFB instance.
SFC 64 TIME_TCK Reads the system time.
SFC 78 OB_RT Reports OB runtime information with a resolution to the nearest
microsecond.
SFC 79 SET Sets a range of outputs.
SFC 80 RESET Resets a range of outputs.
SFC 82 CREA_DBL Creates a data block in the load memory.
SFC 83 READ_DBL Copies data from a block in the load memory.
SFC 84 WRIT_DBL Writes to a load memory block, so that the data are stored
immediately.
Load memory blocks that are used to recover from an abnormal
termination can be updated while the program is running. Use SFC 84
only for larger segments of a database, not for frequent variable
processing.
SFC 85 CREA_DB Creates a retentive or non-retentive DB, depending on the input
parameter:
If retentive, the current values of the DB are retained after a warm
restart (OB100).
If non-retentive, the current values of the DB are reset to their initial
values after a warm restart (OB100).
SFC 87 C_DIAG Determines the current status of all S7 connections.
Performance features and technical specifications
A.4 Supported SFCs
WinAC MP 2008
102 Operating Instructions, 03/2009, A5E00981151-02
Running asynchronous SFCs concurrently
WinAC MP 2008 restricts the number of asynchronous OBs that can be running concurrently
according to the following rules:
A maximum of 5 instances of the asynchronous system function SFC 51 (index B1, B3)
may run in WinAC MP 2008.
A maximum of 20 asynchronous SFCs of the following SFCs may run in WinAC MP 2008:
SFC 11, SFC 13, SFC 55, SFC 56, SFC 57, SFC 58 and SFC 59.
A maximum of 32 asynchronous SFCs in any combination from the following SFCs may
run in WinAC MP 2008: SFC 82, SFC 83 and SFC 84.
SFCs that can cause the cycle time to vary (jitter)
The following SFCs can cause the cycle time to vary (jitter):
SFC 22 (CREAT_DB)
SFC 23 (DEL_DB)
SFC 52 (WR_USMG)
SFC 85 (CREA_DB)
Considerations for SFC 82, SFC 83 and SFC 84
WinAC MP 2008 supports a synchronous interface for SFC 82, SFC 83 and SFC 84 during
startup. WinAC MP 2008 allows both the first call (with REQ = 1) and the second call (with
REQ = 0) in STARTUP so that the action can be completed during STARTUP.
The normal STEP 7 error codes are valid for SFC 82, SFC 83 and SFC 84. The error code
80C3 is also returned. These SFCs return the error code 80C3, if WinAC MP 2008 exceeds
the limit of 32 outstanding SFC 82, SFC 83 and SFC 84 jobs.
Further Information
Detailed information on the SFCs can be found in the STEP 7 online help or in the
STEP 7
System Software for S7-300 and S7-400 System and Standard Functions
Reference
Manual.
Performance features and technical specifications
A.5 Supported SFBs
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 103
A.5 Supported SFBs
Definition of system function block (SFB)
System function blocks (SFB) are integrated in the CPU operating system and can be called
in the STEP 7 user program.
System function blocks (SFBs)
WinAC MP supports the following SFBs:
SFB Name Description
SFB 0 CTU Counts up.
SFB 1 CTD Counts down.
SFB 2 CTUD Counts up/down.
SFB 3 TP Generates a pulse.
SFB 4 TON Generates an ON delay.
SFB 5 TOF Generates an OFF delay.
SFB 8 USEND Sends a data packet of CPU-specific length (two-
way), uncoordinated with receiving partner.
SFB 9 URCV Asynchronously receives a data packet of CPU-
specific length (two-way).
SFB 12 BSEND Sends a segmented data block of up to 64 Kbytes
(two-way).
SFB 13 BRCV Receives a segmented data block of up to 64
Kbytes (two-way).
SFB 14 GET Reads data up to a CPU-specific maximum length
(one-way) from a remote CPU.
SFB 15 PUT Writes data up to a CPU-specific maximum length
(one-way) to a remote CPU.
SFB 22 STATUS Queries the status of a remote device.
SFB 23 USTATUS Receives the status of a remote device.
SFB 32 DRUM Implements a sequencer.
SFB 52 RDREC Reads a data record.
SFB 53 WRREC Writes a data record.
SFB 54 RALRM Receives alarm data for a DP slave.
Further Information
Detailed information on the SFBs can be found in the STEP 7 online help or in the STEP 7
System Software for S7-300/400 System and Standard Functions Reference Manual.
Performance features and technical specifications
A.6 System status list (SSL)
WinAC MP 2008
104 Operating Instructions, 03/2009, A5E00981151-02
A.6 System status list (SSL)
Using SFC 51 to read the system status list (SSL)
STEP 7 stores read-only information about WinAC in the system status list (SSL) as a set of
sublists.
You use SFC 51 (RDSYSST) to access the entries in the SSL. You supply the input
parameters SSL_ID and Index to access the data records in the sublist. SFC 51 returns a
two-word header and a sublist or partial sublist.
The header provides the following information for the sublist:
The first word defines the length (in bytes) of a data record for the sublist.
The second word defines the number of data records in the sublist.
The requested information follows the header. The size of the sublist (in bytes) is the data
record length multiplied by the number of data records.
Note
Representation of the values in the SSL
The SSL_ID and Index values are represented as hexadecimal (16#) numbers.
SSL_ID 0x11 (module identification)
SSL_ID Sublist Index and contents of the data record
W#16#0111 Module-specific information 0001: Order number, module type and version
0007: Firmware version
SSL_ID 0x12 (CPU characteristics )
SSL_ID Sublist Index and contents of the data record
W#16#0012 All characteristics MC7 processor unit, time system, system
response and MC7 language description
W#16#0112 Specific group of characteristics 0000: MC7 processor
0100: Time system
0200: System response
0300: MC7 language description
W#16#0F12 Header information only
Performance features and technical specifications
A.6 System status list (SSL)
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 105
SSL_ID 0x13 (memory areas)
SSL_ID Sublist Index and contents of the data record
W#16#0113 Specific memory area 0001: User memory
0002: Load memory integrated
0003: Load memory inserted
0004: Maximum insertable load memory
0005: Size of backup memory
0006: Peer-to-peer memory (shadow memory)
SSL_ID 0x14 (system areas)
SSL_ID Sublist Index and contents of the data record
W#16#0014 All system areas
W#16#0F14 Header information only
SSL_ID 0x15 (block types)
SSL_ID Sublist Index and contents of the data record
W#16#0015 All block types
SSL_ID 0x19 (LED status)
SSL_ID Sublist Index and contents of the data record
W#16#0019 All LEDs
W#16#0F19 Header information only
SSL_ID 0x1C (component identification)
SSL_ID Sublist Index and contents of the data record
W#16#001C All information of a component
W#16#011C Specific elements for the
component
0001: Name of the controller
0002: Name of the module
0003: Module tag
0004: Copyright entry
0005: Serial number
0007: Module type
0009: Manufacturer and profile identification
000B: Location designation (LID) of a module
W#16#0F1C Header information only
Performance features and technical specifications
A.6 System status list (SSL)
WinAC MP 2008
106 Operating Instructions, 03/2009, A5E00981151-02
SSL_ID 0x22 (interrupt status)
SSL_ID Sublist Index and contents of the data record
W#16#0222 Start event for a specific OB OB number: Start event and time for the
requested OB
SSL_ID 0x25 (process image partition)
SSL_ID Sublist Index and contents of the data record
W#16#25 All process image partitions Process image partitions for all OBs that have
been loaded into the module
W#16#125 Process image partition of a
specific OB
Partition number: for the partition of the
configured OB
W#16#0225 OBs that have been assigned to a
specific process image partition
OB number: Partition that has been assigned to
the OB
W#16#0F25 Header information only
SSL_ID 0x32 (communications status)
SSL_ID Sublist Index and contents of the data record
W#16#0132 Parameters of the specified
communication types
0005: Diagnostics
0008: Time system
W#16#0232 Parameters of a redundant system
(H-CPU)
0004: Protection level and position of the
operator switch settings
SSL_ID 0x74 (LED status)
SSL_ID Sublist Index and contents of the data record
W#16#0174 Specific LED 0002: INTF internal error
0003: EXTF external error
0004: RUN
0005: STOP
0006: Point-to-point status data
0008: Time system
000B: BUSF1 bus fault
Performance features and technical specifications
A.6 System status list (SSL)
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 107
SSL_ID 0x90 (DP master system)
SSL_ID Sublist Index and contents of the data record
W#16#0090 All DP masters configured on the
network and downloaded to the
module
DP master identifier, address and attributes for
all DP masters
W#16#0190 Specific DP master DP master identifier, address and attributes
W#16#0F90 Header information only
SSL_ID 0x91 (module status)
SSL_ID Sublist Index and contents of the data record
W#16#0591 Module status information of all
submodules of the host module
INDEX is irrelevant
W#16#0991 Module status information of a DP
master system
Rack or DP master system ID
W#16#0C91 Specific module, identified by the
logical base address
Logical base address: Functions and
parameters of the specified module
W#16#0D91 Specific station, identified either by
the rack/station, by DP master
identifier or the DP master identifier
with station number
Station identifier: Features and parameters for
all the modules of the specified station
W#16#0E91 Module status information of all
configured modules (central,
distributed, PROFIBUS DP or
PROFINET IO)
INDEX is irrelevant
SSL_ID 0x92 (rack and station status)
SSL_ID Sublist Index and contents of the data record
W#16#0092 Expected status of stations in a DP
master system
0: Local DP master
DP master identifier: Specific DP master
W#16#0192 Activation status of the stations of
an ID of a DP master system
0: Local DP master
DP master identifier: Specific DP master
W#16#0292 Actual status of the stations of a
DP master
0: Local DP master
DP master identifier: Specific DP master
W#16#0692 OK status of the stations of a DP
master
0: Local DP master
DP master identifier: Specific DP master
Performance features and technical specifications
A.6 System status list (SSL)
WinAC MP 2008
108 Operating Instructions, 03/2009, A5E00981151-02
SSL_ID 0x95 (expanded DP master system)
SSL_ID Sublist Index and contents of the data record
W#16#0195 Specific DP master DP master identifier: Properties of the stations
of the specified DP master (for example, DP
mode, equidistant mode and cycle, clock
synchronization and transmission rate)
W#16#0F95 Header information only
SSL_ID 0xA0 (diagnostic buffer)
SSL_ID Sublist Index and contents of the data record
W#16#00A0 All entries in the diagnostic buffer Event information for all events listed in the
diagnostic buffer
W#16#01A0 Most recent entries in the
diagnostic buffer
Number: Event information for the specified
number of entries in the diagnostic buffer
W#16#0FA0 Header information only
SSL_ID 00B1, 00B3, 00B4 (module diagnostics)
SSL_ID Sublist Index and contents of the data record
W#16#00B1 Diagnostic information (4 bytes) for
a specific module identified by the
logical base address
Logical base address: First 4 bytes of the
diagnostic information
W#16#00B3 All diagnostic information for a
specific module identified by the
logical base address
Logical base address: Complete diagnostic
information
W#16#00B4 Specific DP slave identified by the
configured diagnostic address
Diagnostic address: Standard diagnostic
information for a DP station
Further Information
You will find detailed information on the system status lists:
In the STEP 7 online help
In the
System and Standard Functions for S7-300/400
reference manual
If you want to call up the manual on a PC on which STEP 7 is installed, select Start >
SIMATIC > Documentation > English and double-click "STEP 7 - System and standard
functions for S7-300 and S7-400".
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 109
Glossary
"Transfer" mode
"Transfer" mode is the operating mode of the HMI device in which a run-capable project is
transferred from the configuration PC to an HMI device.
Automation system
An automation system is a controller of the SIMATIC S7 series, such as a SIMATIC S7-300
Bit memories
Bit memory is part of the CPU system memory. It is used to store interim results. Bit-, byte-,
word-, or double word-access of bit memory is possible
Boot loader
The boot loader is used to start the operating system and is automatically started when the
HMI device is switched on. After the operating system has been loaded, the Loader opens.
Bootstrapping
Bootstrapping is a function used, for example, when updating the operating system. When a
functional operating system is available, updates can be performed without bootstrapping.
Otherwise, updating with bootstrapping is necessary. In this case, the configuration PC
communicates with the HMI device by means of the HMI device bootloader.
Cold restart
The controller executes OB 102 before the free cycle (OB 1) is started. Like a warm restart,
a cold restart resets the process input image (PII) and places the process output image
(PIQ) into a pre-defined safe state (default is 0). However, retentive memory (M, T, C, or DB)
is reset to defaults during a cold restart.
Configuration
Configuration refers to the combination of individual modules to form an automation system.
Configuration PC
A configuration PC is a programming device or PC on which plant projects are created using
configuration software.
Glossary
WinAC MP 2008
110 Operating Instructions, 03/2009, A5E00981151-02
Control Panel
In the Control Panel, you can make settings on the HMI device.
Controller
A controller is a general term for devices and systems with which the HMI device
communicates, such as SIMATIC S7.
Counter
Counters are part of the CPU system memory. The content of "counter cells" can be
modified by STEP 7 instructions (for example, count up/down).
CP
Communications processor: Communication processors are modules used for point-to-point
and bus topologies.
CPU
A central processing unit is the main processing unit of the automation system with a
processor, arithmetic unit, memory, operating system, and interface for the programming
device.
Cycle
The cycle includes writing to the outputs, reading the inputs, executing OB 1 and all other
OBs, and satisfying the sleep time requirement.
Cycle time
The cycle time includes the OB 1 execution time (S7 user program) and the
HMI Enable Time.
Data Block
Data blocks (DBs) are parts of the user program that contain user data. Global data blocks
can be accessed by all logic blocks while instance data blocks are assigned to a specific FB
call.
Default setting
The default setting is a sensible basic setting that is used whenever no other value is
specified (assigned).
Glossary
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 111
DPV1
The designation DPV1 means extension of the functionality of the acyclical services (to
include new interrupts, for example) provided by the DP protocol. The DPV1 functionality has
been incorporated into IEC 61158/EN 50170, volume 2, PROFIBUS.
Engineering software
The configuration software is used to create projects for process visualization.
WinCC flexible is an example of configuring software.
Flash memory
Flash memory is non-volatile memory with EEPROM chips, used as a mobile storage
medium or as a memory module installed permanently on the motherboard.
Function block
According to IEC 1131-3, a function block (FB) is a logic block containing static data. An FB
allows the user program to pass parameters. Function blocks are therefore suitable for
programming frequently recurring, complex functions, e.g., closed-loop controls, mode
selection.
Function key
A function key is a key on the HMI device that supports user-specific functions. A function is
assigned to the key in the configuration. The assignment of the function keys can vary
according to the displayed screen or be independent of the displayed screen.
Histogram
Graphic representation of the cycle time behavior of WinAC MP.
HMI device
An HMI device is a device used for the operation and monitoring of machines and plants.
The statuses of the machine or plant are indicated by means of graphic elements or by
indicator lamps on the HMI device. The operator controls of the HMI device allow the
operator to intervene in the processes of the machine or plant.
HMI Enable Time
Die HMI Enable Time is a component of the cycle time on WinAC MP.
It includes the execution times for:
HMI runtime
Communication
Options
OBs that are higher priority than OB 1
Glossary
WinAC MP 2008
112 Operating Instructions, 03/2009, A5E00981151-02
HMI station
Representation of a software-based virtual rack that defines a PC-based automation system.
Home screen
The Home Screen provides the same options as the front panel of an S7 hardware CPU.
The Home Screen includes the following elements for operator control and for status
functions:
Buttons for operator control of the WinAC MP (for example, starting and exiting WinAC
MP, automatic startup when booting, autostart and archiving/restoring)
Buttons for functions (changing to the Tuning Screen, returning to the start screen)
Mode selector switch (RUN, STOP)
Status indicators for WinAC MP
MRES button for memory reset
Hotkey
A hotkey specifies a key or key combination that can be used to actuate the button.
Index
In the context of hardware configuration: A numbered slot in the HMI station or virtual rack
that represents a PC-based automation system. The controller occupies one index. Other
components can occupy other index slots.
Industrial Ethernet
Physical communications layer for communication with STEP 7, S7 CPUs, PGs, OPs and S7
applications.
Interface, multi-point
MPI
Jitter
Jitter occurs when there is a delay starting or ending the OB. Example: The execution time
can vary in the millisecond range from cycle to cycle or the start of an interrupt OB can be
delayed.
Load memory
The load memory is part of the CPU and is the memory area (RAM) for all blocks
downloaded from STEP 7 except for the symbol table and comments.
Glossary
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 113
Loader
Transfer, Start, Control Panel and Taskbar can be called in the Loader on the HMI device.
Mains
In terms of communication, a network is the interconnection of several CPUs and other end
devices -- for example, a programming device -- by means of connecting cables. Data
exchange is performed between the connected devices over the network.
Mode
SIMATIC S7 automation systems can adopt the following operating modes: STOP,
STARTUP, RUN, memory reset and STOP.
Mode selector
The mode selector switch is used to set the mode you require on the CPU.
MP
Multi Panel
MPI
Multi-Point Interface is the programming device interface of SIMATIC S7. It allows multiple-
node operation (PGs, text-based displays, OPs) on one or several CPUs. Each station is
identified by its unique (MPI) address.
Nesting depth
A block can be called from another by means of a block call. Nesting depth means the
number of simultaneously called logic blocks.
Node address
The node number represents the "number" of a CPU, the programming device, or other
intelligent I/O module if they communicate with one another over a network. The node
address is assigned with the STEP 7 software.
Object
An object is a component of a project, e.g., a screen or message. Objects are used to view
or enter texts and values on the HMI device.
OP
Operator Panel
Glossary
WinAC MP 2008
114 Operating Instructions, 03/2009, A5E00981151-02
Organization block (OB)
Interface between the operating system and the STEP 7 user program. They are called from
the operating system and control cyclic and interrupt-triggered program execution, the restart
behavior of the controller and error handling.
PG/OP communication
Communication between the controller and other S7 applications such as programming
devices, operator panels, and S7 automation systems. WinAC MP supports PROFIBUS and
Industrial Ethernet for PG/OP communication.
Process image
At the start of a cycle, the signal states at the input modules are written to the process input
image. At the end of the cycle, the process image of the outputs is transferred as a signal
state to the output modules.
Process visualization
Process visualization is the display of technical processes by means of text and graphic
elements. Configured plant screens allow operators to intervene in active plant processes by
inputting and outputting information.
PROFIBUS
Physical communications layer for PROFIBUS-DP communication with inputs/outputs or for
S7 communication with STEP 7, S7 CPUs and S7 applications.
PROFIBUS-DP
Protocol for the communication with the distributed IOs in the network. PROFIBUS-DP
complies with EN 50 170 Volume 2, PROFIBUS.
Programmable (logic) controller
Programmable logic controllers (PLCs) are electronic controllers whose function is saved as
a program in the control unit. Therefore, the configuration and wiring of the device does not
depend on the controller function. The programmable logic controller has the structure of a
computer; it consists of a CPU with memory, I/O modules and an internal bus system. The
I/O and the programming language are oriented to control engineering needs.
Programming device (PG)
Basically speaking, programming devices are compact, portable PCs suitable for industrial
applications. Their distinguishing feature is the special hardware and software for SIMATIC
programmable logic controllers.
Glossary
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 115
Project
A project is the result of a configuration using configuring software. The project normally
contains several screens with embedded system-specific objects, basic settings and alarms.
The project file of a project configured in WinCC flexible is saved under the file name
extension *.hmi.
You need to distinguish between the project on a configuration PC and the run-capable
project on an HMI device. A project may be available in more languages on the configuration
PC than can be managed on the HMI device. The project on the configuration PC can also
be set up for different HMI devices. However, only the run-capable project that has been
generated for the respective HMI device can be transferred to it.
Project file
A project file is a file generated from the executable file for use on the HMI device. The
project file is normally not transferred and remains on the configuration PC.
The file name extension of a project file is *.hmi.
ProSave
The ProSave service tool ships with WinCC flexible. It provides all the functions needed to
transfer data between the configuration PC and HMI device. These include:
Backing up data
Restoring data
Updating the operating system
Load / delete options
Load / delete UCL keys
Restart method
The restart method determines which startup OB is executed whenever the controller
changes from STOP mode to RUN mode. The startup OB allows you to initialize your
STEP 7 user program and variables. The restart methods are: Cold restart (OB 102) and
warm restart (OB 100).
Retentive data
This retentive data is not lost even if the power supply to the HMI device fails. With STEP 7,
you can decide which areas should be retentive. The amount of retentive data is limited for
WinAC MP!
Runtime software
WinCC flexible Runtime refers to the runtime software that can run on the HMI device.
Glossary
WinAC MP 2008
116 Operating Instructions, 03/2009, A5E00981151-02
S7 Communication
Communication between hardware and software controllers on the network using the S7
communication functions.
S7 routing
Communication between S7 automation systems, S7 applications or PC stations in various
subnets using one or more network nodes that act as router. The configuration is created in
NetPro.
Shared data
Shared data can be addressed from any logic block (FC, FB, OB). Specifically, these are bit
memories (M), inputs (I), outputs (Q), timers (T), counters (C) and data blocks (DB). Shared
data can be accessed via absolute or symbolic addressing.
Softbus
Virtual bus that allows a data exchange between WinCC flexible runtime and WinAC MP.
This bus is installed when you install WinAC MP. After installing WinAC MP, S7 connections
from WinCC flexible Runtime to external stations on PROFIBUS or Ethernet are routed over
Softbus.
STARTUP
A STARTUP routine is executed at the transition from STOP to RUN mode. It can be
initiated by the mode selector switch, after a Power On, or through an operator input on the
programming device.
STEP 7 user program
Application program created with STEP 7 and downloaded to the controller for execution. It
includes all organization blocks (e.g., OB 1 or OB 35) and the other logic blocks that are
called, including functions (FCs), system functions (SFCs), function blocks (FBs) and system
function blocks (SFBs).
STEP 7
STEP 7 is the programming software for the SIMATIC S7, SIMATIC C7 and
SIMATIC WinAC controllers.
System function (SFC)
A system function (SFC) is a function that is integrated in the operating system of the CPU
and can be called in the STEP 7 user program, when necessary.
Glossary
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 117
System function block (SFB)
Function block integrated as part of the operating system of the controller and not loaded as
part of the STEP 7 user program. Like a function block (FB), an SFB is a block "with
memory". You must also create an instance data block (DB) for the SFB. The instance DB is
then loaded as part of the STEP 7 user program into the controller.
System memory
The system memory is integrated on the CPU and implemented as RAM. System memory
contains the address areas (for example, timers, counters, bit memories) and data areas that
are required internally by the operating system (for example, communication buffers).
Timer
See
Timers
Timers
Timers are part of the CPU system memory. The content of timer cells is automatically
updated by the operating system, asynchronously to the user program. STEP 7 instructions
are used to define the precise function of the timer cell (for example, ON delay) and to
initiate its execution (for example, Start).
Transfer
Transfer of a run-capable project from the configuration PC to the HMI device.
Tuning screen
In the Tuning screen, you will find histogram information on the cycle time of WinAC MP.
Variable
A tag is a defined memory area for read and write access to values. This access can occur
from the controller or via the HMI device. Based on whether or not the tag is interconnected
with the controller, we distinguish between external tags (process tags) and internal tags.
Warm restart
When the CPU starts up (for example, after changing the mode selector switch from STOP
to RUN or after a Power ON), organization block OB 100 (warm restart) is executed before
cyclic program processing (OB 1). On a warm restart, the process input image is read in and
the STEP 7 user program is executed, starting at the first command in OB 1.
Type of restart where the controller executes OB 100 before the free cycle (OB 1) is started.
A warm restart resets the process input image (PII) and places the process output image
(PIQ) into a predefined safe state (default is 0). During a warm restart, the current values of
the retentive memory areas for the bit memory (M), timers (T), counters (C), and data blocks
(DBs) are retained.
Glossary
WinAC MP 2008
118 Operating Instructions, 03/2009, A5E00981151-02
Working memory
Memory area (RAM) allocated for the blocks used at runtime.
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 119
Index
A
Additional support, 9
Archive file, 74
Restoring, 77
Automation License Manager, 27
Autostart, 64
Function activated, 64
Function not activated, 64
B
Basic knowledge
Required, 5
C
Checking the connection, 49
Checking the online connection, 49
Cold restart, 98
Communication, 12
Configuration PC, 15
Hardware requirements, 17
Software requirements, 17
Configuring, 34
Control panel, 23
Control Panel, 21, 24
Cycle time, 72
D
Direct keys, 44
Direct key ranges, 44
WinCC flexible direct keys in WinAC MP 2008, 44
Display
Avg, 62
Last, 62
Documentation
Purpose, 5
Storage location, 5
Validity, 5
Downloading hardware configuration, 50
Downloading WinAC MP, 51
Downloading WinCC flexible Runtime, 52
E
Embedded
Definition, 11
Embedded automation, 11
Ethernet connection
Configuring hardware, 47
IP address, 47
Exit WinCC flexible, 77
F
Function
Archive, 81
ClearCycleTimeBuffer, 81
ControlWinACMP, 81
GetWinACMPStartMode, 81
GetWinACMPVersion, 81
Restore, 81
SetHMIEnableTime, 80
SetKeySwitch, 81
SetRestartMethod, 81
SetSleepTime, 81
SetWinACMPStartMode, 81
SetWinACStartAtBoot, 81
StartHistogramm, 81
StopHistogramm, 82
UpdateAverageCycleTime, 82
UpdateAverageExecTime, 82
UpdateBUSF1LEDVariable, 82
UpdateBUSF2LEDVariable, 82
UpdateControllerForStartAtBoot, 82
UpdateEXTFLEDVariable, 82
UpdateHMIEnableTime, 80
UpdateINTFLEDVariable, 82
UpdateKeySwitchSetting, 82
UpdateLastCycleTime, 82
UpdateMaximumCycleTime, 82
UpdateMinimumCycleTime, 82
UpdatePowerLEDVariable, 82
UpdateRUNLEDVariable, 82
UpdateSleepTime, 82
UpdateSTOPLEDVariable, 82
Functions, 80
Further information, 8
Index
WinAC MP 2008
120 Operating Instructions, 03/2009, A5E00981151-02
G
Guide to the manual, 9
H
Hardware requirements
Configuration PC, 17
HMI device, 16
Histogram
Configuring, 86
HMI device
Hardware requirements, 16
Software requirements, 16
HMI enable time, 72
HMI station, 34
Home screen
Display, 59
Hotkey, 63
I
Info screen, 61
Information
Further, 8
Information landscape, 8
Installation, 15
WinAC MP, 18
L
License, 27
License Key, 27
Loader, 21, 23, 24
Location of documentation, 5
M
Memory card, 74
Memory reset, 69
Microsoft Windows XP Professional, 17
Mode, 68
Mode selector switch, 67
MP 177, 5
MP 277, 5
MP 377, 5
MRES, 69
N
Naming conventions, 6
O
Objects, 80
Operating mode, 68
Operation, 15
Options
Load, 26
Order numbers
WinAC MP 177, 93
WinAC MP 277, 93
WinAC MP 377, 93
Organization blocks, 99
OB 1, 98
P
PROFIBUS
Transfer, 23
PROFIBUS-DP, 14
Programming, 12
R
Registered trademarks, 7
Removing, 31
Required basic knowledge, 5
Restore, 77
Restoring an archive file, 77
Retentive data
Image update, 42
Retentivity
Data blocks, 43
Memory bytes, 42
S7 counters, 42
S7 timers, 42
Routing, 53
RUN, 68
Runtime software, 6
S
Scope of information, 8
Sequential functions, 100
SetValue, 80
UpdateTag, 80
Setting the PG/PC interface, 50
Shutdown WinAC MP, 77
SIMATIC HMI station, 34
SIMATIC NET, 17
Softbus, 53
Software PLC, 5
Index
WinAC MP 2008
Operating Instructions, 03/2009, A5E00981151-02 121
Software requirements
Configuration PC, 17
HMI device, 16
Standards
IEC 61131-3, 7
Start at Boot, 65
Start WinAC MP, 64
Starting WinAC MP, 64
Status indicator, 70
All status indicators flash, 71
BUSF, 70
EXTF, 70
INTF, 70
ON, 70
RUN, 70
STOP, 70
STEP 7, 17
STEP 7 user program, 74
STOP, 68
Subnet
Industrial Ethernet, 50
PROFIBUS-DP, 51
Support on the Internet, 9
System configuration, 74
System function
Asynchronous SFCs, 102
System status lists, 104
T
Technical support, 9
Time synchronization, 41
Trademark, 7
Training center, 9
Transfer, 20
Automatic transfer detection, 25
PROFIBUS, 23
USB, 24
U
USB
Transfer, 24
V
Validity of the documentation, 5
Visualization, 12
W
Warm restart, 98
WinAC MP 2008, 5
WinAC MP project, 79
WinCC flexible, 6, 17, 79
WinCC flexible project, 15
WinCC flexible Runtime, 6, 79
WinCC flexible system functions, 80