I/O MODULE
G4 DIGITAL
DC OUTPUT
Form 254-990215
DATA SHEET
page 1/3
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909) 695-3000 • (800) 321-OPTO • Fax: (909) 695-3095 • Internet: www.opto22.com
Inside Sales: (800) 452-OPTO • Product Support: (800) TEK-OPTO • (909) 695-3080 • Fax: (909) 695-3017 • E-mail: support@opto22.com • FaxBack: (800) 474-OPTO
Opto 22’s G4 DC output modules are used to control or
switch DC loads. Each module provides up to 4,000 Vrms of
optical-isolation between field devices and control logic.
The G4ODC5MA is a special module featuring a manual-
on/manual-off/automatic switch, ideal for diagnostic testing
of control applications.
Typical applications for DC output modules include
switching loads such as DC relays, solenoids, motor starters,
lamps, and indicators.
4,000 Vrms optical-isolation
Built-in LED status indicator
Logic levels of 5, 15, and 24 VDC
Removable fuse
Ability to withstand one-second surge of 5 amps
Operating temperature: -30° C to 70° C
UL recognized, CSA certified, CE approved
Passes NEMA Showering Arc Test (ICS 2-230)
Meets IEEE Surge Withstand Specification (IEEE-472)
Description
Features
Part Number Description
G4ODC5 G4 DC Output 5-60 VDC, 5 VDC L ogic
G4OD C5A G4 DC O utput 5- 200 VDC, 5 V DC Logic
G4ODC5M A G4 DC Output 5-60 VDC, 5 VDC L ogic
With Manual/A uto S wi tch
G4ODC15 G4 DC Output 5-60 VDC, 15 VDC Logic
G4ODC24 G4 DC Output 5-60 VDC, 24 VDC Logic
G4ODC24A G4 DC Output 5-20 0 VDC, 24 VDC Logi c
Dimension and specifications are subject to change. All products and/or company names throughout this data sheet are generally trademarks or registered trademarks of their respective companies.
I/O MODULE
G4 DIGITAL
DC OUTPUT
Form 254-990215
DATA SHEET
page 2/3
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909) 695-3000 • (800) 321-OPTO • Fax: (909) 695-3095 • Internet: www.opto22.com
Inside Sales: (800) 452-OPTO • Product Support: (800) TEK-OPTO • (909) 695-3080 • Fax: (909) 695-3017 • E-mail: support@opto22.com • FaxBack: (800) 474-OPTO
Specifications
Units G4ODC5* G4ODC5A* G4ODC5MA* G4ODC15 G4ODC24 G4ODC24A
Maximum line voltage VDC 60 200 60 60 60 200
Output voltage range VDC 5-60 5-200 5-60 5-60 5-60 5-200
Key feature --- --- Diagnostic
switch --- --- ---
Current ra ting:
at 45°C ambie nt
at 70°C ambie nt A
A3
21
0.55 3
23
23
21
0.55
I solation input-to -output Vrms 4,000 4,000 4,000 4,000 4,000 4,000
Off-state leakage at
ma ximum volt age mA 1 2 1 1 1 2
Control resistance
(RC in schematic) 220 220 220 1K 2.2K 2.2K
One-second sur ge A 5 5 5 5 5 5
Turn -on time µs 50 100 50 50 50 100
Turn-off time µs50 750 50 50 50 750
Output voltage drop
maximum peak V 1.6 1.6 1.6 1.6 1.6 1.6
Nominal logic volt age VDC 5 5 5 15 24 24
Logic voltage r ange VDC 4-8 4-8 4-8 10.5-16 19.5−32 19.5−32
Logic pickup volt age VDC 4 4 4 10.5 19.5 19.5
Logic dropout voltage VDC 1 1 1 1 11
Logic i nput current at
nominal logic voltage mA 12 12 12 15 18 18
Temperature:
Operating
Storage °C
°C -30 to +70
-30 to +85 -30 to +70
-30 to +85 -30 to +70
-30 to +85 -30 to +70
-30 to +85 -30 to +70
-30 to +85 -30 to +70
-30 to +85
I/O MODULE
G4 DIGITAL
DC OUTPUT
Form 254-990215
DATA SHEET
page 3/3
Opto 22 • 43044 Business Park Drive • Temecula, CA 92590 • Phone: (909) 695-3000 • (800) 321-OPTO • Fax: (909) 695-3095 • Internet: www.opto22.com
Inside Sales: (800) 452-OPTO • Product Support: (800) TEK-OPTO • (909) 695-3080 • Fax: (909) 695-3017 • E-mail: support@opto22.com • FaxBack: (800) 474-OPTO
Dimensions
Schematics