6
Power Entry Modules with Line Filter
FMBC LL www.schurter.com/PG80
EMC Products
Attenuation Loss . . . . . 0.1/100Ω differential mode ........... 100/0.1Ω differential mode - - - - differential mode _____ common mode
Industrial Version
7A 16A 30A 42A
55A 75A 100A 130A
180A
All Variants
Rated Current
@ Ta 50°C (40°C) [A]
Rated Voltage [VAC] Tripped Power
Dissipation [W]
Leakage Cur-
rent [mA] 1)
Weight [kg] Screw clamps
[mm2] 2)
Housing Packaging
unit
Order Number
7 (7.7) 520 1.5 4.4 0.75 kg 6 1U 3 FMBC-R91U-0712
16 (17.5) 520 5.4 4.4 1.2 kg 6 1C 3 FMBC-R91C-1612
30 (32.9) 520 6.6 4.4 9.4 kg 10 1Q 4 FMBC-R91Q-3012
42 (46) 520 10.7 4.4 9.4 kg 10 1R 3 FMBC-R91R-4212
55 (60.2) 520 13.3 4.4 2.4 kg 25 1S 2 FMBC-R91S-5512
75 (82.2) 520 19.6 17.5 4.1 kg 25 1F 1 FMBC-R91F-7512
100 (109.5) 520 26.3 17.5 5.4 kg 50 1G 1 FMBC-R91G-J012
130 (142.4) 520 10 19.3 4.6 kg 50 1G 1 FMBC-R91G-J312
180 (197.1) 520 31 19.3 9.4 kg 95 1V 1 FMBC-R91V-J812
Availability for all products can be searched real-time:http://www.schurter.com/en/Stock-Check/Stock-Check-SCHURTER
1) Nominal leakage current acc. to IEC60950 - 5.2.5. under normal operating conditions. Note: worst case leakage current acc. to IEC60950 - Annex G4 (situation with two
interrupted lines) can be much higher.
2) Maximum conductor cross section (wire gauge) to be used; a comparative table for AWG and mm² values can be found in the general product information www.schurter.
com/emc_info
The specifications, descriptions and illustrations indicated in this document are based on current
information. All content is subject to modifications and amendments. Information furnished is believed
to be accurate and reliable. However, users should independently evaluate the suitability and test each
product selected for their own applications.
28.10.2014