Power Supplies
3
Contact Technical Services at (800) 377-4384 with any questions.
Visit our website at www.solahd.com.
120
SDN-C Specifications (Three Phase)
Description Catalog Number
SDN 5-24-480C SDN 10-24-480C SDN 20-24-480CC SDN 40-24-480C
Input
Nominal Voltage 380 - 480 Vac
Two - phase input Yes 1
-AC Range 2320 - 540 Vac
-DC Range 450 - 760 Vdc 450 - 760 Vdc 450 - 760 Vdc 9N/A
-Frequency 50/60 Hz
Nominal Current 33 x 0.5 or 2 x 0.7 A 3 x 0.8 or 2 x 1.2 A 3 x 0.9 or 2 x 1.3 A 3 x 1.6 A
-Inrush current max. Typ. <25 A Negligible Negligible
Efficiency (Losses 4)> 85% (18 W) 91.2% (23.6 W) 93% (42 W) 94% (78 W)
Power Factor Correction Power factor correction to meet EN61000-3-2 Class A Active Power Factor Correction
Output
Turn on time Typ. 1s
Voltage Rise Time ca. 5-20 ms <100 ms full resistive load (Tamb =+25°C )
Power Back Immunity <35 V
Overvoltage Protection >30.5 but <33 Vdc auto recovery
Nominal Voltage 24 V (24 - 28 Vdc Adjustable)
Voltage Regulation < ±2 % overall
Initial Voltage Setting 24.5 V ± 1%
-Ripple 5<100 mVpp
PARD PARD = 100 mV peak-peak max PARD = 200 mV peak-peak max
Nominal Current 5 A (120 W) 10 A (240 W) 20 A (480 W) (constant power, not
constant current) 40 A (960 W)
-Peak Current 66A, 2×Nominal Current <2sec 12A, 2×Nominal Current <2sec 1.5×Nominal Current for 4 sec minimum while holding voltage > 20Vdc
-Current Limit PowerBoost™
Derating typ. 6 W/oC typ. 12 W/oC typ. 24 W/oC typ. 48 W/oC
Holdup Time >20 ms >15 ms
Voltage Fall Time <150 ms from 95% to 10% rated voltage @ full load (Tamb=+25°C) <50 ms from 95% to 10% rated voltage @ full load (Tamb=+25°C)
Parallel Operation 7Single or Parallel operation selectable via front switch. For redundant
operation, use of external diode module is preferred SDN 40 uses active paralelling
General
Case Fully enclosed metal housing with ne ventilation grid to keep out small parts.
Min. Required 25mm above and below or
15mm in front
25mm above and below or
10mm in front
70mm above and below or
25mm in front and 25mm left & right
70mm above and below, 15mm in
front, 25mm left & right
Free Space
H×W×D inches (mm) 4.85 × 1.97 × 4.36
(123.0 × 50.0 × 111.0)
4.85 × 2.36 × 4.36
(123.0 × 60.0 × 111.0)
4.85 x 3.35 x 4.68
(123.0 x 85.0 x 119.0)
4.85 x 7.09 x 4.66
(123.0 x 180.0 x 119.0)
Weight lbs (kg) 1.2 (.52) 1.5 (0.70) 2.9 (1.30) 5.3 (2.40)
EMC: -Emissions EN61000-6-3:2001, Class B EN55011, EN55022 Radiated and Conducted including Annex. A, EN61000-3-2
-Immunity EN61000-6-1:2001, EN61000-6-2:2001, EN61000-4-2 Level 4, EN61000-4-3 Level 3, EN61000-4-6 Level 3,
EN61000-4-4 Level 4 input and level 3 output. EN61000-4-5 Isolation class 4, EN61000-4-11
Temperature Storage : -40 to + 85oC, Operation -25 to +60oC full power, with linear derating to half power from 60 to 70oC (Convection cooling, no forced air
required). Operation up to 50% load permissible with sideways or front side up mounting orientation.
Humidity < 90% RH, noncondensing; IEC 60068-2-2, 68-2-3
Altitude 0 to 3000 meters (0 to 10,000 feet)
Vibration 2.5(g) RMS, 10-2000 Hz (random); three axes for 20 minutes each - IEC 60068-2-6
Shock 3(g) peak, three axes, 11mseconds for each axis - IEC 60068-2-27
Warranty 5 Year Limited Warranty
MTBF >500,000 hrs MTBF (Nominal voltage, full load, Tamb = 25oC)
General Protection/Safety Protected against short -circuit, overload, open circuit. Protection class 1 (IEC536), degree of protection IP20 (IEC 529)
Safe low voltage: SELV (acc. EN60950)
Over-temperature protection LED Alarm, Output shutdown with automatic restart
Status Indicators Visual: 3 status LEDs (Input, Output, Alarm) Relay: SSR or dry relay contact, signal active when Vout = 18.5 Vdc = +/-5%
Installation
Fusing: -Input Externally fused
-Output Not fused. Output is capable of providing high currents (PowerBoost) for motor load startup.
Mounting Simple snap-on to DIN TS35/7.5 or TS35/15 rail system.
Unit should handle normal shock and vibration of industrial use and transportation without falling off the rail.
Connections 8
Input: screw terminals, Wiring for the connector will be Ground on the left (when looking at the front of the unit),
connector size range: 16-10AWG (1.5-6mm2) for solid conductors. Output: connector size range, wire gauge 6-7 AWG for SDN40;
all other models: 16-10AWG (1.5-6mm2) for solid conductors.
1. SDN 20 will operate at 75% load; SDN 40 will operate at 50% load under loss of 1
phase; SDN 5 and SDN 10 will operate with single phase input power at 100% of load.
Unit will shut down if thermal threshold is exceeded under this condition.
2. Unit passed input voltage overstress test at 600 Vac without failure.
3. Input current ratings are specied with low input, line conditions, worst case ef-
ciency values and power factor spikes. Input current at nominal input settings will
typically be half these values.
4. Losses are heat dissipation in watts at full load, nominal line.
5. Ripple/noise is stated as typical values when measured with a 20 MHZ, bandwidth
scope and 50 Ohm resistor.
6. SDN 20 and 40 unit will go to HICCUP mode. SDN 5 and 10 will maintain min 4
secs to deliver 150% load then drops to almost zero Vout. The output voltage will im-
mediately drop to almost zero when load rises above 150%.
7. All models except the 40amp unit are capable of parallel operation by use of a
jumper pin, accessible by the end user. 40 amp unit will have active current sharing
signal.
8. SDN 40-24-480C only = Output signaling terminal block features (Shut down,
Power Good, Current Monitor, Current Balance, signal GND).
9. 70% maximum rated load.