https://www.phoenixcontact.com/us/products/2910348
05/19/2021Page1/9
Type 1 surge protection device-VAL-US-120/40/1+0-FM-2910348
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Surge protective device, single channel with remote indicator contact for 120VAC
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4055626444895
Weight per Piece (excluding packing) 380.000 g
Custom tariff number 85363030
Country of origin Germany
Technical data
Dimensions
Height 98.7 mm
Width 17.8 mm
Depth 65.5 mm
Horizontal pitch 1 Div.
Ambient conditions
Degree of protection IP20 (only when all terminal points are used)
Ambient temperature (operation) -40 °C ... 80 °C
Ambient temperature (storage/transport) -40 °C ... 80 °C
Altitude ≤ 2000 m (amsl (above mean sea level))
Permissible humidity (operation) 5 % ... 95 %
https://www.phoenixcontact.com/us/products/2910348
05/19/2021Page2/9
Type 1 surge protection device-VAL-US-120/40/1+0-FM-2910348
Technical data
Ambient conditions
Shock (operation) 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation) 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
General
IEC test classification II
T2
EN type T2
IEC power supply system TN-C
Mode of protection L-PEN
Mounting type DIN rail: 35 mm
Color jet black RAL 9005
Housing material PA 6.6
PBT
Degree of pollution 2
Flammability rating according to UL 94 V-0
Type DIN rail module, two-section, divisible
Number of positions 1
Surge protection fault message Optical, remote indicator contact
Protective circuit
Nominal voltage UN120VAC (TN-C)
Nominal frequency fN50 Hz (60Hz)
Rated load current IL80 A
Residual current IPE ≤ 0.45 mA
Nominal discharge current In (8/20) µs 20 kA
Maximum discharge current Imax (8/20) µs 40 kA
Short-circuit current rating ISCCR 25 kA
Voltage protection level Up≤ 0.9 kV
Residual voltage Ures ≤ 0.9 kV (at In)
≤ 0.75 kV (at 10 kA)
≤ 0.6 kV (at 5 kA)
≤ 0.55 kV (at 3kA)
TOV behavior at UT208 VAC (5s / withstand mode)
240 VAC (120min / safe failure mode)
Response time tA≤ 25 ns
Max. backup fuse with V-type through wiring 80 A (gG)
Max. backup fuse with branch wiring 125 A (gG)
https://www.phoenixcontact.com/us/products/2910348
05/19/2021Page3/9
Type 1 surge protection device-VAL-US-120/40/1+0-FM-2910348
Technical data
Indicator/remote signaling
Switching function Changeover contact
Operating voltage 5 VAC ... 250 VAC
30 VDC
Operating current 5 mA AC ... 1.5 A AC
1 ADC
Connection method Screw connection
Screw thread M2
Tightening torque 0.25 Nm
Stripping length 7 mm
Conductor cross section flexible 0.14 mm² ... 1.5 mm²
Conductor cross section solid 0.14 mm² ... 1.5 mm²
Conductor cross section AWG 28 ... 16
Connection data
Connection method Screw connection
Screw thread M5
Tightening torque 4.5 Nm (1.5mm² ... 16mm²)
4.5 Nm (25mm²...35mm²)
Stripping length 16 mm
Conductor cross section flexible 1.5 mm² ... 25 mm²
Conductor cross section solid 1.5 mm² ... 35 mm²
Conductor cross section AWG 15 ... 2
UL specifications
SPD Type 1
Maximum continuous operating voltage MCOV 175 VAC
Nom. voltage 120VAC (Single-phase)
Mode of protection L-N
Power distribution system Single phase
Nominal frequency 50/60 Hz
Voltage protection rating VPR 700 V
Nominal discharge current In20 kA
Maximum Surge Current per Phase 40 kA
Short-circuit current rating (SCCR) 200 kA
UL indicator/remote signaling
Operating voltage 125 VAC
Operating current 1 A AC
Tightening torque 2 lbf-in. ... 4 lbf-in.
https://www.phoenixcontact.com/us/products/2910348
05/19/2021Page4/9
Type 1 surge protection device-VAL-US-120/40/1+0-FM-2910348
Technical data
UL indicator/remote signaling
Conductor cross section AWG 30 ... 14
UL connection data
Conductor cross section AWG 10 ... 2
Tightening torque 30 lbf-in.
Standards and Regulations
Standards/regulations IEC61643-11 2011
EN61643-11 2012
Drawings
Dimensional drawing
44
65,7
89,8
96,8
17,6
Circuit diagram
12 14
11
FM
Classifications
eCl@ss
eCl@ss 10.0.1 27130805
eCl@ss 11.0 27130805
eCl@ss 6.0 27130800
eCl@ss 7.0 27130805
eCl@ss 9.0 27130805
ETIM
ETIM 6.0 EC000941
ETIM 7.0 EC000941
Approvals
Approvals
Approvals
UL Listed / cUL Listed / cULus Listed
https://www.phoenixcontact.com/us/products/2910348
05/19/2021Page5/9
Type 1 surge protection device-VAL-US-120/40/1+0-FM-2910348
Approvals
Ex Approvals
Approval details
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330181
cUL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330181
cULus Listed
Accessories
Accessories
Bridge
Wiring bridge-MPB F600X16/ 1GS-2818355
Wiring bridge flexible, diameter: 16 mm², with a fork-type cable lug on one side, length: 600 mm
Wiring bridge-MPB F600X16/ 1GS-2818355
Wiring bridge flexible, diameter: 16 mm², with a fork-type cable lug on one side, length: 600 mm
https://www.phoenixcontact.com/us/products/2910348
05/19/2021Page6/9
Type 1 surge protection device-VAL-US-120/40/1+0-FM-2910348
Accessories
Wiring bridge-MPB F200X16/ 1GS-2818339
Wiring bridge flexible, diameter 16 mm², with a fork-type cable lug on one side, length: 200 mm
Wiring bridge-MPB 18/1-10/1.0.0-2830443
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 10 pitches with contact sequence 1-0-0
Wiring bridge-MPB 18/4-12-2809296
Wiring bridge for modules with connecting pitch 17.5 mm, 4-phase, 12-pos.
Wiring bridge-MPB 18/4- 8-2809283
Wiring bridge for modules with connecting pitch 17.5 mm, 4-phase, 8-pos.
Wiring bridge-MPB 18/3- 6-2809241
Wiring bridge for modules with connecting pitch 17.5 mm, 3-phase, 6-pos.
https://www.phoenixcontact.com/us/products/2910348
05/19/2021Page7/9
Type 1 surge protection device-VAL-US-120/40/1+0-FM-2910348
Accessories
Wiring bridge-MPB 18/1-57-2809238
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 57-pos.
Wiring bridge-MPB 18/1-12-2748593
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 12-pos.
Wiring bridge-MPB 18/1- 9-2748580
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 9-pos.
Wiring bridge-MPB 18/1- 8-2748577
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 8-pos.
Wiring bridge-MPB 18/1- 6-2748564
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 6-pos.
https://www.phoenixcontact.com/us/products/2910348
05/19/2021Page8/9
Type 1 surge protection device-VAL-US-120/40/1+0-FM-2910348
Accessories
Wiring bridge-MPB 18/1- 4-2809225
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 4-pos.
Wiring bridge-MPB 18/1- 3-2809212
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 3-pos.
Wiring bridge-MPB 18/1- 2-2809209
Wiring bridge for modules with connecting pitch 17.5 mm, 1-phase, 2-pos.
Device marking
Zack marker strip-ZBN 18:UNBEDRUCKT-2809128
Zack marker strip, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, mounting type: snap
into tall marker groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
Feed-through terminal block
Feed-through terminal block-DK-BIC-35-2749880
Feed-through terminal block for VAL and FLT applications
https://www.phoenixcontact.com/us/products/2910348
05/19/2021Page9/9
Type 1 surge protection device-VAL-US-120/40/1+0-FM-2910348
Accessories
Labeled device marker
Marker for terminal blocks-ZBN 18,LGS:ERDE-2749589
Marker for terminal blocks, Strip, white, labeled, horizontal: Grounding symbol, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
Marker for terminal blocks-ZBN 18,LGS:L1-N,ERDE-2749576
Marker for terminal blocks, Strip, white, labeled, horizontal: L1, L2, L3, N, GND, mounting type: snap into tall marker
groove, for terminal block width: 18 mm, lettering field size: 18 x 5 mm, Number of individual labels: 5
Marker pen
Marker pen-B-STIFT-1051993
Marker pen, for manual labeling of unprinted Zack strips, smear-proof and waterproof, line thickness 0.5 mm
Spare parts
Type 1 surge protection plug-VAL-US-120/40-P-2910335
UL Recognized type 1 SPD and IEC type 2 surge protection plug with a varistor and thermal disconnect for use with VAL-
US base elements, mechanical and visual fault warning
Phoenix Contact 2021 © - all rights reserved
http://www.phoenixcontact.com