Universal AC input / Full range
Built-in active PFC function, PF>0.95
Protections: Short circuit / Overload / Over voltage / Over temperature
DC OK signal
emote ON-OFF control
Standby 5V@0.3A
No load power consumption<0.75W (Note.7)
Current sharing up to 2400W (3+1) (24V,36V,48V)
5 years warranty
High efficiency up to 89%
Withstand 300VAC surge input for 5 seconds
Built-in cooling fan ON-OFF control
Built-in
Built-in r
Built-in remote sense function
SPECIFICATION
HRPG-600-3.3 HRPG-600-5 HRPG-600-7.5 HRPG-600-12 HRPG-600-15 HRPG-600-24 HRPG-600-36 HRPG-600-48
MODEL
DCVOLTAGE
RATEDCURRENT
CURRENTRANGE
RATEDPOWER
RIPPLE&NOISE(max.) Note.2
OUTPUT VOLTAGE ADJ.RANGE
VOLTAGETOLERANCE Note.3
LINEREGULATION
LOADREGULATION
SETUP,RISETIME
HOLDUP TIME (Typ.)
VOLTAGERANGE Note.5
FREQUENCY RANGE
POWERFACTOR (Typ.)
EFFICIENCY (Typ.)
INPUT
ENVIRONMENT
INRUSHCURRENT (Typ.)
LEAKAGECURRENT
OVERTEMPERATURE
SAFETY STANDARDS
HARMONICCURRENT
EMICONDUCTION&RADIATION
SAFETY &
FUNCTION
EMSIMMUNITY
EMC
(Note4)
WITHSTANDVOLTAGE
ISOLATIONRESISTANCE
WORKINGTEMP.
DCOKSIGNAL
REMOTECONTROL
WORKINGHUMIDITY
STORAGETEMP.,HUMIDITY
TEMP.COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVERVOLTAGE
PROTECTION
ACCURRENT (Typ.)
3.3V 5V 7.5V 12V 15V 24V 36V 48V
120A 120A 80A 53A 43A 27A 17.5A 13A
0~120A 0~120A 0~80A 0~53A 0~43A 0~27A 0~17.5A 0~13A
396W 600W 600W 636W 645W 648W 630W 624W
100mVp-p 100mVp-p 100mVp-p 120mVp-p 150mVp-p 150mVp-p 200mVp-p 240mVp-p
2.8~3.8V 4.3~5.8V 6.8~9V 10.2~13.8V 13.5~18V 21.6~28.8V 28.8~39.6V 40.8~55.2V
2.0% 2.0% 2.0% 1.0% 1.0% 1.0% 1.0% 1.0%
0.5% 0.5% 0.5% 0.3% 0.3% 0.2% 0.2% 0.2%
1.0% 1.0% 1.0% 0.5% 0.5% 0.5% 0.5% 0.5%
1000ms,50ms/230VAC2500ms,50ms/115VACatfullload
16ms/230VAC16ms/115VACatfullload
85~264VAC120~370VDC
47~63Hz
PF>0.94/230VACPF>0.99/115VACatfullload
78.5% 82%
6~7V 9.4~10.9V 14.4~16.8V 18.8~21.8V 30~34.8V 41.4~48.6V 57.6~67.2V
86% 88% 88% 88% 89% 89%
8.5A/115VAC5A/230VAC
35A/115VAC70A/230VAC
<1.2mA /240VAC
105~135%ratedoutputpower
3.96~4.62V
Protectiontype: Constantcurrentlimiting,recoversautomaticallyafterfaultconditionisremoved
Protectiontype:Shutdowno/pvoltage,re-powerontorecover
Protectiontype:Shutdowno/pvoltage,recoversautomaticallyaftertemperaturegoesdown
80 5 (TSW1)detectonheatsinkofpowertransistor
90 5 (TSW2) for3.3V,5V,7.5V;100 5 (TSW2) power forothersdetectonheatsinkofpowerdoide detectonmain outputchoke
UL60950-1, TUVEN60950-1approved
CompliancetoEN55022(CISPR22)ClassB
Complianceto EN61000-3-2,-3
CompliancetoEN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2, heavyindustrylevel,criteria A
I/P-O/P:3KVACI/P-FG:1.5KVACO/P-FG:0.5KVAC
I/P-O/P,I/P-FG,O/P-FG:100MOhms/500VDC/25 /70%RH
-40~+70 (Refertooutputloadderatingcurve)
RC+/RC-:4~10Voropen=poweron;0~0.8Vorshort=poweroff
PSUturnon:3.3~5.6V;PSUturnoff:0~1V
20~90%RHnon-condensing
-40~+85 ,10~95%RH
0.03%/ (0~50 )
10~500Hz,5G10min./1cycle,60min.eachalongX, Y,Zaxes
147.7Khrsmin.MIL-HDBK-217F(25 )
218*105*63.5mm(L*W*H)
FileName:HRPG-600-SPEC2010-11-29
Features :
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Derating may be needed under low input voltages. Please check the derating curve for more details.
6. Length of set up time is measured at first cold start. Turning ON/OFF the power supply may lead to increase of the set up time.
7. No load power consumption<0.75W when RC+ & RC- (CN100 pin3,4) 0 ~ 8V or short.
For guidance on how to perform these EMC tests, please refer to EMI testing of component power supplies.
(as available on http://www.meanwell.com)
HRPG-600 seri es
600WSingleOutputwithPFCFunction
1.58Kg;8pcs/13.6Kg/1.34CUFT
5VSTANDBY
5VSB:5V@0.3A ;tolerance 5%,ripple:50mVp-p(max.)
FANCONTROL (Typ.)
Load35 15%orRTH2 50 Fanon
http://store.iiic.cc/
MechanicalSpecificationMechanicalSpecification CaseNo.977A Unit:mm
ACInput TerminalPinNo.
Assignment
DCOutput TerminalPinNo.
Assignment
PinNo. PinNo.
1 1~3
3
2 4~6
Assignment Assignment
AC/N +V
AC/L -V
FG
DeratingCurve OutputDeratingVSInputVoltage
INPUTVOLTAGE(V)60Hz
Ta=25
90 100 125 135 155 264
100
90
80
70
60
50
40
LOAD(%)
AMBIENTTEMPERATURE( )
LOAD(%)
-40 0 10 20 30 40 50 60 70
20
50
80
100
125
(HORIZONTAL)
PW fosc:70KHzM
CN100
LED
(Vo ADJ.)SVR1
BlockDiagram
PinNo. PinNo.
7
6,8
5
3
2
1
9
410
Assignment
-S
+S
DC-OK
GND
CS
Assignment
RC-
RC+
AUX
AUXG
MatingHousing Terminal
orequivalent orequivalent
ConnectorPinNo. Assignment(CN100):HRSDF11-10DP-2DS orequivalent
HRSDF11-10DS
HRSDF11-**SC
O.L.P.
O.T.P.
EMI INRUSH
ACTIVE
FILTER CURRENT
LIMITING
RECTIFIERS
&
PFC
I/P
FG
PWM
PFC
CIRCUIT
SHARING
DETECTION
CURRENT
POWER
AUX
SWITCHING
POWER
FILTER
FILTER
&
&
RECTIFIERS
RECTIFIERS
+V
+S
AUX
CONTROL
CONTROL
O.V.P.
O.T.P.
REMOTE
CONTROL
-V
-S
AUXG
RC+
CS
DCOK
RC-
105
18max.
11
9.2
O/P
1
2
3
4
5
6
Airflow
direction
63.5
3
2
1
I/P
4-M4L=6
12max.
8.2
63.5 20.75
10
218
32.8152.4
8-M4L=4(BothSides)
32.8
38.3
12.5
152.4
600WSingleOutputwithPFCFunction
FileName:HRPG-600-SPEC2010-11-29
HRPG-600 serie s
1
2
9
10
http://store.iiic.cc/
Theremotesensingcompensatesvoltagedropon
theloadwiringupto0.5V.
10
10
9
9
CN100
AUX
RC-
GND
GND
-S
AUXG
RC+
CS
DC-OK
+S
2
2
1
1
1.RemoteSense
1
1
9
9
10
10
Senselinesshould
betwistedinpairs
LOAD
-
+
+S -S
(Pin9) (Pin10)
Fig1.1
BetweenDC-OK(pin4)andGND(pin3)
3.3~5.6V
0~1V
OutputStatus
ON
OFF
DC-OKsignalisa TTL levelsignal.HighwhenPSUturnson. CN100
AUX
RC-
GND
GND
-S
AUXG
RC+
CS
DC-OK
+S
2.DC-OKSignal
Fig2.1
CN100
CN100
2
2
5 CS Currentsharingsignal.Whenunitsareconnectedinparallel,theCSpinsoftheunitsshouldbeconnectedtoallowcurrentbalance
betweenunits.
7DC-OK DC-OKsignalisa TTL levelsignal,referencedtopin8(DC-OKGND).HighwhenPSUturnson.
9 +S Positivesensing. The+Ssignalshouldbeconnectedtothepositiveterminaloftheload. The+Sand-Sleadsshouldbetwistedinpairto
minimizenoise pick-upeffect. Themaximumlinedropcompensationis0.5V.
10 -S Negativesensing. The-Ssignalshouldbeconnectedtothenegativeterminaloftheload. The-Sand+Sleadsshouldbetwistedinpairto
minimizenoise pick-upeffect. Themaximumlinedropcompensationis0.5V.
6,8 GND Thispinconnectstothenegativeterminal(-V).ReturnforDC-OKsignaloutput.
600WSingleOutputwithPFCFunction
FileName:HRPG-600-SPEC2010-11-29
HRPG-600 serie s
FunctionDescriptionofCN100
PinNo. Function Description
FunctionManual
3
4
RC+
RC- Remotecontrolground.
Turnstheoutputonandoffbyelectricalordrycontactbetweenpin4(RC-),Short:PowerOFF,Open:PowerON.
2
1
AUX
AUXG
Auxiliaryvoltageoutput,4.75~5.25V,referencedtopin1(AUXG). Themaximumloadcurrentis0.3A. Thisoutputhasthebuilt-inoring
diodesandisnotcontrolledbythe"remoteON/OFFcontrol".
Auxiliaryvoltageoutputground. Thesignalreturnisisolatedfromtheoutputterminals(+V&-V).
http://store.iiic.cc/
10 9
21
1
9
10
CN100
2
600WSingleOutputwithPFCFunction
FileName:HRPG-600-SPEC2010-11-29
HRPG-600 serie s
BetweenRC+(pin3)andRC-(pin4)
SWON(Short)
SWOFF(Open)
OutputStatus
OFF
ON
ThePSUcanbeturnedON/OFFbyusingthe
"RemoteControl"function.
SW
CN100
AUX
RC-
GND
GND
-S
AUXG
RC+
CS
DC-OK
+S
3.RemoteControl
Fig3.1
PSU2PSU1 PSU3 PSU4
Fig4.1
LOAD
Senselinesshould
betwistedinpairs
+V -V
-V-V -V -V
CN100 CN100CN100CN100
+V+V +V +V
10101010
9999
AUXAUX AUX AUXRC-RC- RC- RC-GNDGND GND GNDGNDGND GND GND-S-S -S -S
AUXGAUXG AUXG AUXG
RC+RC+ RC+ RC+CSCS CS CS
DC-OKDC-OK DC-OK DC-OK
+S+S +S +S
2222
CN100CN100
PSU2PSU1 PSU3 PSU4
CN100 CN100
1111
Note:1.Inparallelconnection,maybeonlyoneunit(master)operateifthetotaloutputloadislessthan2%ofratedloadcondition.
TheotherPSU(slave)maygointostandbymodeanditsoutputLEDandrelaywillnotturnon.
2.2%min.ofdummyloadisrequired.
4.CurrentSharingwithRemoteSensing(Onlyfor24V,36Vand48V)
HRPG-600hasthebuilt-inactivecurrentsharingfunctionandcanbeconnectedinparalleltoprovidehigheroutputpower:
(1)Paralleloperationisavailablebyconnectingtheunitsshownasbelow.
(2)Differenceofoutputvoltagesamongparallelunitsshouldbelessthan2%.
(3)Thetotaloutputcurrentmustnotexceedthevaluedeterminedbythefollowingequation.
(4)Inparalleloperation2unitsisthemaximum,pleaseconsultthemanufacturerforapplicationsofmoreconnectinginparallel.
(5)Thepowersuppliesshouldbeparalleledusingshortandlargediameterwiringandthenconnectedtotheload.
(+S,-S,CSandGNDareconnectedmutuallyinparallel).
(outputcurrentatparalleloperation)=(Ratedcurrentperunit) (Numberofunit) 0.9
http://store.iiic.cc/