DRC Series
7.6 Amp AC Semiconductor Motor Controller
Load voltage range up to 600VAC
Fits standard 35mm DIN Rail
LED input status indicator
AC or DC control
Zero Voltage (resistive loads) or instantaneous (inductive loads) turn-on output
C-UL-US Listed, CCC Certified, IEC Rated, CE & RoHS Compliant, Horsepower Rated
Built-in Overvoltage Protection
Ultra-efficient thermal management design (Patented)
Start / Stop Reversing
Solicon DRC3 Series are Solid State Contactors intended for
frequently switching on and off three phase loads up to 5 HP, 600
VAC 7.6 Amps. They are available in both contactor versions
DRC3P and reversing contactor versions DRC3R.
The Solicon Contactor DRC3P is available in either instantaneous
turn-on (for Motor Control) or zero voltage turn-on (for Resistive
Loads). It is available in either 2 or 3 controlled leg versions. The
2 legs control version is particularly suitable for motor control
circuits where the neutral conductor is not utilized.
The Solicon Reversing Contactor DRC3R includes an interlock
control that allows only off, forward and reverse operation in a
safe mode while providing high space saving; it switches
instantaneously upon application of the control voltage unless an
instantaneous change of direction is commanded, then it will
delay the direction change by 100msec in order to prevent
simultaneous forward and reverse operations.
All the models of Solicon DRC3 Series combine the benefits and
advantages of a solid state contactor with the functionality and
simplicity of use of an electromechanical contactor thanks to the
proprietary thermal management technology (Patented) and
complete electrical insulation (no grounding required); the
embedded auxiliary contacts, normally open and/or normally
closed, are intended to be used at 18-280VAC. Five different
control voltages are available in order to cover most applications.
All models include overvoltage protection.
PRODUCT SELECTION
Control Voltage Without Auxiliary Contact 1 NO+NC Auxiliary Conctat 2 NO Auxiliary Contact
230 VAC DRC3P48A400, DRC3R48A400 DRC3P48A411
120 VAC DRC3P48B400, DRC3R48B400 DRC3P48B411
48 VAC/DC DRC3P48C400, DRC3R48C400 DRC3P48C411
DRC3P48A420, DRC3R48A420
DRC3P48B420, DRC3R48B420
DRC3P48C420, DRC3R48C420
AVAILABLE OPTIONS
Required for valid part number
For options only and not required for valid part number
DRC
Series
Operating Voltage
40: 400 VAC
(3R function only)
48: 480 VAC
60: 600 VAC
(3P function only)
Control Voltage
A: 208-265 VAC
B: 90-140 VAC
C: 36-55 VAC/DC
D: 18-30 VAC/DC
(3P function only)
18-30 VAC
(3R function only)
E: 18-30 VDC
(3R function only)
Function
3P: Contactor
3R: Reversing Contactor
48 D3P
Load Current per Phase
4: 7.6 Amp FLA
(x2 Controlled Legs
& 3R function);
4.8 Amp FLA
(x3 Controlled Legs only)
4
Auxiliary Contacts,
N.O. - N.C.
00: Not included
11: 1 Solid State Auxiliary
Contact, Normally Open;
1 Solid State Auxiliary
Contact, Normally Closed
(3P function only)
20: 2 Solid State Auxiliary
Contacts, Normally Open
00
Switching Mode
(3P function only)
Blank: Zero Voltage Turn-On
R: Instantaneous Turn-On
Controlled Legs
(3P function only)
Blank: 3 Controlled Legs
2: 2 Controlled Legs
R2
24 VAC/DC, 24 VAC DRC3P48D400, DRC3R48D400 DRC3P48D411 DRC3P48D420, DRC3R48D420
24 VDC DRC3R48E400 DRC3R48E420
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
SOLID STATE AUXILIARY CONTACTS(1)
Description
Operating Voltage Range (47-63Hz) [Vrms] (9)
Transient Overvoltage [Vpk]
Maximum Load Current [Arms]
Minimum Load Current [mA]
Maximum Surge Current [Apk] 1 Cycle 60Hz
Maximum Surge Current [Apk] 1 Cycle 50Hz
Maximum I2t for Fusing (8.33msec)[A2sec]
Normally Open Suffix 2x,1x
18-280
600
1
5
40
38
6.7
Normally Closed Suffix x1
18-280
600
1
5
40
38
6.7
Maximum I2t for Fusing (10msec)[A2sec]
Maximum Off-State Leakage Current @ Rated Voltage [mArms]
Minimum Off-State dv/dt @ Maximum Rated Voltage [V/μsec]
Maximum Delay to Turn-On [msec] (6)
Maximum Turn-Off Time [msec] (7)
7.2
0.1
500
30
40
7.2
5 mA
500
80
40
OUTPUT SPECIFICATIONS (1)
DRC3P48x4x2DRC3P48x4xDescription
Load Current, General Use UL508 /AC51 @40°C [Arms] (3) 5 7.6
Load Current, Motor Controller UL508 /AC-53a @480VAC [Arms] (3) 4.8 7.6
Minimum Load Current [Arms] 0.15 0.15
Maximum Surge Current [Apk] 1 Cycle 60Hz 750 750
Maximum Surge Current [Apk] 1 Cycle 50Hz 716 716
Maximum I2t for Fusing (8.33msec)[A2sec] 2330 2330
Maximum I2t for Fusing (10msec)[A2sec] 2560 2560
Maximum On-State Voltage Drop @ Rated Current [Vpk] 1.35 per channel 1.35 per channel
Minimum Power Factor (with Maximum Load) 0.5 0.5
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 240 VAC 1/.75 2/1.5
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 400 VAC 2/1.5 3/2.2
Ratings according to UL 508/IEC60947-4-2 [HP/kW]: 480 VAC 3/2.2 5/3.7
Operating Voltage (47-63Hz) [Vrms] 48-530 48-530
Transient Overvoltage [Vpk] (2) 1200 1200
Maximum Off-State Leakage Current @ Rated Voltage [mArms] 3.0 3.0
Maximum Off-State dv/dt @ Maximum Rated Voltage [V/μsec] 500 500
DRC3P60x4x2DRC3P60x4x
5 7.6
4.8 7.6
0.15 0.15
750 750
716 716
2330 2330
2560 2560
1.35 per channel 1.35 per channel
0.7 0.7
1/.75 2/1.5
2/1.5 3/2.2
3/2.2 5/3.7
48-600 48-600
1200 1200
1.0 1.0
500 500
DRC3R48x4xDRC3R40x4x
7.6 7.6
7.6 7.6
0.15 0.15
750 625
716 597
2330 1621
2560 1779
1.5 per channel 1.5 per channel
0.5 0.5
2/1.5 2/1.5
3/2.2 3/2.2
- 5/3.7
Motor Ratings @ 600 VAC [HP/kW] - - 3/2.2 5/3.7 - -
48-415 48-510
1200 1600
5.5 5.5
500 500
GENERAL SPECIFICATIONS (1)
Description Parameters
Dielectric Strength, Input/Output/Base (50/60Hz) (10) 3750 Vrms
Minimum Insulation Resistance (@ 500 VDC) 109 Ohms
Maximum Capacitance, Input/Output 20 pF
Ambient Operating Temperature Range (11) -30 to 80 °C
Ambient Storage Temperature Range -40 to 100 °C
Weight (typical) 2 Controlled Legs (6.9 oz [197 g]) / 3 Controlled Legs (8.0 oz [228 g])
Housing Material UL94 V-0
Housing Color Black and Light Gray
LED Status Indicator (color) (12) Forward (Green) / Reverse (Amber)
Short Circuit Current Rating (13) 100kA
Control and Auxiliary Contact Terminal Screw Torque Range (in-lb/Nm) 12 / 1.36
Load Terminal Screw Torque Range (in-lb/Nm) 15 / 1.7
Input Terminal Wire Capacity 18-12 AWG (IEC 1-4 mm2) (stranded /solid)
Output Terminal Wire Capacity 18-10 AWG (IEC 1-6 mm2 ) (stranded /solid)
Humidity 85% non-condensing
Protection Degree (15) IP20
Pollution Degree 2
MTBF (Mean Time Between Failures) at 60°C ambient temperature (14) 390,000 hours (44 years)
MTBF (Mean Time Between Failures) at 40°C ambient temperature (14) 1,398,000 hours (159 years)
INPUT SPECIFICATIONS (1)
Description Option B
Control Voltage Range (4) 90-140 VAC
Minimum Turn-On Voltage (5) 90 VAC
Must Turn-Off Voltage 10 VAC
Minimum Input Current (for on-state) [mA] 7.5
Maximum Input Current [mA] 13
Nominal Input Impedance [Ohms] 12.5k
Maximum Delay to Turn-On [msec] (6)(7) 30
Option A
208-265 VAC
208 VAC
40 VAC
6.1
8
33k
30
Option C
36-55 VAC / VDC
36 VAC / VDC
4 VAC / VDC
12
20
3k
30
Maximum Turn-Off Time [msec] (8) 4040 40
Option D
18-30 VAC / VDC
18 VAC / VDC
4 VAC / VDC
12.5
32
0.93k
20
30
Option E
18-30 VDC
18 VDC
4 VDC
12.5
32
0.93k
100
±
30
20
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
MECHANICAL SPECIFICATIONS (1)
Tolerances: ±0.02 in / 0.5 mm
All dimensions are in: inches [millimeters]
(17)
6
5
4
3
2
1
100 203040506070 80
0
Ambient Temperature (ºC)
Load Current (Amps)
THERMAL DERATE INFORMATION
DRC3P (3 controlled legs)
Single unit Multiple units
(17)
Ambient Temperature (ºC)
Load Current (Amps)
DRC3P (2 controlled legs)
& DRC3R
Single unit Multiple units
8
7
6
5
4
3
2
1
02010 30 40 50 60 70 80
0
Top/Bottom view (Fig. 1)
Fig. 1
TERMINAL SCREW TYPE
INPUT
STATUS
XXXX
IND. CONT. EQ.
DRC3
1.23
[31.3]
2.29
[58.3]
2.58
[65.5]
1.68
[42.7]
3.41
[86.7]
1.78
[45.3]
3.76
[95.6]
3.51
[89]
2.91
[73.9]
0.23
[5.8]
A1
A2
A3 2313
2414
(16)
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
SWITCHING FREQUENCY/LOAD CHARACTERISTIC FOR ALL DEVICES
IL : Load Operating Current
IR : Rated Full Load Current [FLA]
ID : Direct-On-Line Inrush Current
tL : Load Operating Current Time
tD : Direct-On-Line Inrush Current Time
tC : Cycle Time
tOn : On Time
tOff : Off Time
Without overload relay (limit given by the contactor itself)
With overload relay (limit given by the overload relay itself)
tD (sec) 0.1 1 10 100
0.05 5000 2700 350 35
0.1 3200 1950 350 35
0.2 950 320 35
0.4 500 280 35
0.8 290 160 35
1.6 110 30
3.2 75 25
tOn (sec)
tD (sec) 0.1 1 10 100
0.05 6000 3550 350 35
0.1 4100 3000 350 35
0.2 1300 350 35
0.4 700 320 35
0.8 400 320 35
1.6 125 35
3.2 90 35
tOn (sec)
tD (sec) 0.1 1 10 100
0.05 7450 3200 350 35
0.1 4050 2100 350 35
0.2 1200 350 35
0.4 650 320 35
0.8 350 280 35
1.6 180 35
3.2 90 35
tOn (sec)
tD (sec) 0.1 1 10 100
0.05 9000 3550 350 35
0.1 5400 3550 350 35
0.2 1700 350 35
0.4 850 350 35
0.8 560 350 35
1.6 240 35
3.2 180 35
tOn (sec)
tD (sec) 0.1 1 10 100
0.05 2200 1650 330 30
0.1 1500 1000 280 28
0.2 550 255 26
0.4 250 150 24
0.8 80 60 20
1.6 40 16
3.2
tOn (sec)
tD (sec) 0.1 1 10 100
0.05 2800 1800 320 35
0.1 1700 1300 310 32
0.2 650 290 30
0.4 300 200 26
0.8 200 90 25
1.6 65 25
3.2
tOn (sec)
tD (sec) 0.1 1 10 100
0.05 5150 2800 260 35
0.1 2850 1920 250 34
0.2 1100 250 33
0.4 600 200 32
0.8 320 200 30
1.6 120 25
3.2 75 20
tOn (sec)
tD (sec) 0.1 1 10 100
0.05 5600 3200 350 35
0.1 3200 2700 350 35
0.2 1400 350 35
0.4 700 350 35
0.8 350 280 35
1.6 170 35
3.2 80 25
tOn (sec)
Table 1
• High inrush current (ID/IR = 4 to 7.2)
• Full load (IL/IR= 1)
Table 2
• High inrush current (ID/IR = 4 to 7.2)
• 60% load (IL/IR= 0.6)
Table 3
• Low inrush current (ID/IR < 4 )
• Full load (IL/IR= 1)
Table 4
• Low inrush current (ID/IR < 4 )
• 60% load (IL/IR= 0.6)
Table 5
• High inrush current (ID/IR = 4 to 7.2)
• Full load (IL/IR= 1)
Table 6
• High inrush current (ID/IR = 4 to 7.2)
• 60% load (IL/IR= 0.6)
Table 7
• Low inrush current (ID/IR < 4 )
• Full load (IL/IR= 1)
Table 8
• Low inrush current (ID/IR < 4 )
• 60% load (IL/IR= 0.6)
ID
IR
IL
tDtL
tC
tOn tOff
MAXIMUM ALLOWABLE NUMBER OF STARTS PER HOUR DEPENDING ON THE STARTING
TIME tD AND THE ON PERIOD tOn (as for standard IEC 60947-4-2) FOR ALL DEVICES
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
---
-
-
-
-
-
-
-
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
SHORT CIRCUIT AND OVERLOAD PROTECTION FOR ALL DEVICES
IEC standard 60947-4-1 make a distinction between two different types of protection, (called “coordination”), which are designated types1” and "2".
Any short-circuit that occurs is cleared safely by either type of coordination.
The only difference between the 2 categories concerns the extent of the SSR damage caused by the short-circuit.
Type "1" coordination requires that in the event of a short-circuit, the Solid State Contactor does not endanger personnel or installations,
but permanent damage to the SSC is permissible. In this case the SSC may need to be replaced. For this type of co-ordination,
the use of fusing or circuit breakers adequate to protect the system and wiring from short circuits, (but not specifically considering SSC protection), can be used.
Type "2" coordination requires that under a short-circuit condition, the circuit is interrupted, the SSC does not endanger persons or installations,
and in addition the SSR will be able to operate after the fault condition is repaired.
Type of coordination 1
Note: All the Schneider Electric Thermal magnetic circuit breakers GV2 family (GV2ME and GV2P) is fully mechanical compatible with the DRC contactor using the GV2AF3 connection block.
Protection by overload relays and fuses
Nominal Motor
Current
Overload Relay
(Schneider Electric)
Class gG fuses
(example from Littlefuse)
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
Solid State Contactor
Reversing
0.40-0.63 A LRD04 CY14X51G16 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
0.63-1 A LRD05 CY14X51G16 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
1-1.6 A LRD06 CY14X51G25 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
1.6-2.5 A LRD07 CY14X51G25 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
2.5-4 A LRD08 CY14X51G25 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
4-6.3 A LRD10 CY14X51G40 DRC3Pxx4x2 DRC3Pxx4x(up to 4.8A) DRC3Rxx4x
6.3-10 A LRD14 CY14X51G40 DRC3Pxx4x2 (up to 7.6A) - DRC3Rxx4x (up to 7.6A)
(18)
Type of coordination 2
Protection by overload relays and fuses
Nominal Motor
Current
Overload Relay
(Schneider Electric)
Semiconductor fuses with less than 1621A2S
Littlefuse
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
Solid State Contactor
Reversing
0.40-0.63 A LRD04 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
0.63-1 A LRD05 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
1-1.6 A LRD06 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
1.6-2.5 A LRD07 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
2.5-4 A LRD08 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
4-6.3 A LRD10 LA50QS40-4 DRC3Pxx4x2 DRC3Pxx4x (up to 4.8A) DRC3Rxx4x
6.3-10 A LRD14 LA50QS40-4 DRC3Pxx4x2 (up to 7.6A) - DRC3Rxx4x (up to 7.6A)
(18)
All the Schneider Electric Overload relay LRD family is fully mechanical compatible with the DRC contactor without the need of any adapter.
0.40-0.63 A GV2ME04 / GV2P04 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
0.63-1 A GV2ME05 / GV2P05 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
1-1.6 A GV2ME06 / GV2P06 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
1.6-2.5 A GV2ME07 / GV2P07 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
2.5-4 A GV2ME08 / GV2P08 DRC3Pxx4x2 DRC3Pxx4x DRC3Rxx4x
4-6.3 A GV2ME10 / GV2P10 DRC3Pxx4x2 DRC3Pxx4x (up to 4.8A) DRC3Rxx4x
6.3-10 A GV2ME14 / GV2P14 DRC3Pxx4x2 (up to 7.6A) - DRC3Rxx4x (up to 7.6A)
Nominal Motor
Current
Thermal Magnetic Circuit Breaker
(Schneider Electric)
Solid State Contactor
2 controlled legs
Solid State Contactor
3 controlled legs
Solid State Contactor
Reversing
Protection by Thermal Magnetic Circuit Breaker (18)
(Conforming to the IEC60947-4-2 and UL508)
The DRC Series can accept the LAD7C1 module (pre-wiring kit allowing direct connection of the NC contact of relay LRD to the contactor)
50.058.06.40
50.058.06.40
50.058.06.40
50.058.06.40
50.058.06.40
50.058.06.40
50.058.06.40
A093909
A093909
A093909
A093909
A093909
A093909
A093909
SIBA (Cylindric) Ferraz (Cylindric)
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
WIRING AND BLOCK DIAGRAM
DRC3P CONTACTOR
INPUT
STATUS
A1
A2
L1 L2 L3
T1 T2 T3
XXXX
IND. CONT. EQ.
DRC3PXXX400XX
INPUT
STATUS
13 21 A1
14 22 A2
L1 L2 L3
T1 T2 T3
XXXX
IND. CONT. EQ.
DRC3PXXX411XX
INPUT
STATUS
13 23 A1
14 24 A2
L1 L2 L3
T1 T2 T3
XXXX
IND. CONT. EQ.
DRC3PXXX420XX
L1
L2
L3
L1
L2
L3
DRC3Pxx400 DRC3Pxx411 DRC3Pxx420
48-530 VAC, 50-60 Hz
48-600 VAC, 50-60 Hz
CONTROL
INPUT
/ > / > / >
CONTROL
INPUT
/ > / > / >
1st Auxiliary Contact (18 - 280 VAC) Normally Open
2nd Auxiliary Contact (18 - 280 VAC) Normally Closed
CONTROL
INPUT
/ > / > / >
1st Auxiliary Contact (18 - 280 VAC) Normally Open
2nd Auxiliary Contact (18 - 280 VAC) Normally Open
Short circuit and overload
current protection (see page 5)
T1 T2 T3
General Use /
AC-51 Application
T1 T2 T3 T1 T2 T3 T1 T2 T3
T1 T2 T3
M
3
Motor Controller /
AC-53a Application
DRC3P
(3 controlled legs model)
Main Circuit
L1
T1
L2
T2
L3
T3
A1
A2
13
14
23
24
DRC3Pxx420
(2 Normally Open)
Auxiliary Contacts
DRC3Pxx400
Without Auxiliary Contacts
DRC3P
(2 controlled legs model)
Main Circuit
L1
T1
L2
T2
L3
T3
A1
A2
13
14
21
22
DRC3Pxx411
(1 Normally Open - 1 Normally Closed)
Auxiliary Contacts
(19)
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
DRC3R REVERSING CONTACTOR
(20)
L1
T1
L2
T2
L3
T3
DRC3R
A1
A2
13
14
Forward
23
24
L1
T1
L2
T2
L3
T3
A3
A2
Reverse
DRC3Rxx420
models only
INPUT
STATUS
A1
A2
L1 L2 L3
T1 T2 T3
XXXX
IND. CONT. EQ.
DRC3RXXX400XX
INPUT
STATUS
13 23 A1
14 24 A2
L1 L2 L3
T1 T2 T3
XXXX
IND. CONT. EQ.
DRC3RXXX420XX
L1
L2
L3
L1
L2
L3
DRC3Rxx400 DRC3Rxx420
48-415 VAC, 50 - 60 Hz
48-510 VAC, 50 - 60 Hz
CONTROL
INPUT
(Forward)
CONTROL
INPUT
(Common)
CONTROL
INPUT
(Reverse)
CONTROL
INPUT
(Reverse)
/ > / > / > / > / > / >
1st Auxiliary Contact (18 - 280 VAC) Normally Open
2nd Auxiliary Contact (18 - 280 VAC) Normally Open
Short circuit and overload current
protection (see page 5)
T1 T2 T3T1 T2 T3
T1 T2 T3
M
3
Motor Controller /
AC-53a Application
Overload current
protection needs to
be considered
CONTROL
INPUT
(Forward)
CONTROL
INPUT
(Common)
A3 A3
Reverse
Forward
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
AGENCY APPROVALS
Certification in accordance with:
United States Standard for Industrial Control Equipment - UL 508 and
Canadian Standard Association for Industrial Control Equipment – C22.2 No. 14.
China Compulsory Certification for AC Semiconductor Motor Controller-GB14048.6-2008
DRC3 series conforms to the harmonized EN standard EN/IEC 60947-4-2
Electromagnetic Compatibility:
IEC 61000-4-2 : Electrostatic Discharge – Level 3
IEC 61000-4-4 : Electrically Fast Transients – Level 3
IEC 61000-4-5 : Electrical Surges – Level 3
Vibration Resistance:
IEC 60068-2-6 : Amplitude Range 10-55 Hz, Displacement 0.75mm
Shock Resistance:
IEC 60068-2-27 : Peak Acceleration 15g, Duration11msec.
E116949 (Only DRCx40x4x & DRCx48x4x)
FWD REV
Open
Close
Open
Close
Input A1 Input A3
Open
Open
Close
Close
Off
On
Off
Off
Off
Off
On
Off
TIMING DIAGRAM
1, 4, 10
3, 9
4
5
STEP DESCRIPTION
A1 is activated, FWD Output waits for 100msec
FWD direction is activated
A1 changes to off. FWD Output is disabled at the same time
A3 is activated. REV Outputs waits for 100msec
2
6 REV direction is On
8 A3 is open, A1 is closed, activation delayed 100msec
7 Interlock fuction is activated. REV is disabled due to A1 & A3 both being active
Initial Condition. A1 & A3 open
Input/Output 1 2 3 4 5 6 7 8 9 10
Input A1
Input A3
FWD Direction 100 msec 100 msec
REV Direction 100 msec
TIMING DIAGRAM FOR DRC3R
interlock
s
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
ACCESSORIES FOR ALL DEVICES
Recommended Accessories
Motor Nominal
Current
Thermal Magnetic Circuit
Breaker (Push Button)
Thermal Magnetic Circuit
Breaker (Selector)
0.40 - 0.63 A
0.63 - 1 A
1 - 1.6 A
1.6 - 2.5 A
2.5 - 4 A
4 - 6.3 A
6.3 - 10 A
Fully compatible with
Schneider Electric
thermal overload
relays &
thermal magnetic
circuit breakers
LRD04
LRD05
LRD06
LRD07
LRD08
LRD10
LRD14
GV2ME04
GV2ME05
GV2ME06
GV2ME07
GV2ME08
GV2ME10
GV2ME14
GV2P04
GV2P05
GV2P06
GV2P07
GV2P08
GV2P10
GV2P14
LR97 D015xx
LR97 D015xx
LR97 D07xx
LR97 D07xx
LR97 D07xx
LR97 D25xx
LR97 D25xx
Bimetal
Overload Relay
Electronic
Overload Relay
ID Marker Strips
CNLB, CNLN, CNL2
Packages of 10 plastic strips comprising 10
individual markers which can be placed for easy
identification during the use of multiple units.
Blank Strips
Part no.: CNLB
Numbered 1 to 10 Strips
Part no.: CNLN Numbered 11 to 20 Strips
Part no.: CNL2
Note: All the Schneider Electric Thermal magnetic circuit breakers GV2 family (GV2ME and GV2P) is fully mechanical compatible with the DRC contactor using the GV2AF3 connection block.
All the Schneider Electric Overload relay LRD family is fully mechanical compatible with the DRC contactor without the need of any adapter.
The DRC Series can accept the LAD7C1 module (pre-wiring kit allowing direct connection of the NC contact of relay LRD to the contactor)
When the LAD7C1 module is used, the common terminal for the control input is not anymore the ”A2” terminal of DRC but it is the “96” terminal of the overload relay.
Nbd110Si
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
GENERAL NOTES
(1) All parameters at 25°C unless otherwise specified.
(2) For DRC3P relay will self trigger between 900-1200V, Not suitable for capacitive loads.
(3) Mounted in the Vertical position.
(4) On DRC3R models the range for option D is 18-30 VAC.
(5) For low temperature operation consider nominal control voltage.
(6) For DRC3R the turn-on time is 100msec ± 30msec.
(7) For DRC3P Instantaneous Turn-on, Option D, turn-on time is 4 msec.
(8) When is complete removed the control signal. For DRC3R the turn-off time is 20msec.
(9) Operating voltage range 18-30 VDC is also valid when used to latch the DRC contactor control input.
(10) For input to auxiliary output the dielectric strength is 2.5kV.
(11) UL approval up to 40°C surrounding temperature.
(12) Reverse Amber Indicator is for DRC3R models only.
(13) 100kA, 480VAC, when protected with CC class fuses rated 600VAC, 20A or equivalent.
(14) All parameters at 50% power rating and 100% duty cycle (contact Crydom tech support for detailed report).
(15) IP20 rating is not associated with the UL approval.
(16) Derate information is valid when DCR contactors are used with or without accessories, installed on top and/or bottom.
(17) Minimum spacing to obtain max. current is 22mm between adjacent units.
(18) Combinations of these Protective Devices and Solid State Contactor have not been evaluated by UL.
(19) For DRC3P models external loads can be connected in parallel to the control input.
(20) DRC3R internal safety interlock circuit prevents the product to work if any leakage current is present in the control input currently not enabled.
Rev. 020916
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
WARNING / AVERTISSEMENT / WARNUNG /ADVERTENCIA / AVVERTENZA / 警告
RISK OF MATERIAL DAMAGE AND HOT
ENCLOSURE
The product's side panels may be hot, allow
the product to cool before touching.
Follow proper mounting instructions including
torque values.
Do not allow liquids or foreign objects to enter
this product.
Failure to follow these instructions can result in
serious injury, or equipment damage.
RISQUE DE DOMMAGE MATERIEL ET DE
SURCHAUFFE DU BOITIER
Les panneaux latéraux du produit peuvent être
chauds. Laisser le produit refroidir avant de le
toucher.
Respecter les consignes de montage, et
notamment les couples de serrage.
Ne pas laisser pénétrer de liquide ni de corps
étrangers à l'intérieur du produit.
Le non-respect de cette directive peut entraîner,
des lésions corporelles graves ou des
dommages matériels.
Die Nichtbeachtung dieser Anweisung kann
Körperverletzung oder Materialschäden
zur Folge haben.
GEFAHR VON MATERIALSCHÄDEN UND
GEHÄUSEERHITZUNG
Die Seitenwände können heiß sein. Lassen Sie
das Produkt abkühlen, bevor Sie es berühren.
Beachten Sie die Montageanweisungen,
Führen Sie keine Flüssigkeiten oder
Fremdkörper in das Produkt ein.
Si no se respetan estas precauciones pueden
producirse graves lesiones, daños materiales.
RIESGO DE DAÑOS MATERIALES Y DE
SOBRECALENTAMIENTO DE LA UNIDAD
Los paneles laterales del producto pueden
estar calientes. Esperar que el producto se
enfríe antes de tocarlo.
Respetar las instrucciones de montaje, y en
particular los pares de apretado.
No dejar que penetren líquidos o cuerpos
extraños en el producto.
La mancata osservanza di questa precauzione può
causare gravi rischi per l'incolumità personale o
danni alle apparecchiature.
RISCHIO DI DANNI MATERIALI E D'INVOLUCRO
CALDO
I pannelli laterali dell'apparecchio possono
scottare; lasciar quindi raffreddare il prodotto
prima di toccarlo.
Seguire le istruzioni di montaggio corrette.
Non far entrare liquidi o oggetti estranei in questo
apparecchio.
සփీኟඓኴႜኄၵ֡ፕຫ௽Lj
ᆶీሰׯჹዘට༹ฅ࡞ኁยԢڦ໦࣋ă
֌ଙ໦࣋ࢅߛ࿒ྔڦླ၃Ⴀ
!ׂ೗ڦᅃ֨௬ӱీ࢔ඤLjሞഄૐඐമ൩
!փᄲةಸă
!ፏቷኟඓڦҾጎຫ௽LjԈઔ౦ኵă
!൩ကඟᅂ༹ഄ໱ᅴ࿿৊෇Ԩׂ೗ă
DANGER / PELIGRO / DANGER /GEFAHR / PERICOLO / ླ၃
HAZARD OF
ELECTRIC
SHOCK,
EXPLOSION,
OR ARC FLASH.
xDisconnect all
power before
installing or
working with
this equipment.
xVerify all
connections
and replace all
covers before
turning on
power.
Failure to follow
these
instructions will
result in death
or serious injury.
RIESGO DE
DESCARGA
ELECTRICA O
EXPLOSION.
xDesconectar
todos los
suministros de
energia a este
equipo antes
de trabajar
con este equipo.
xVerificar todas
las conexiones
y colocar todas
las tapas antes
de energizer
el equipo.
El
incumplimiento
de estas
instrucciones
puede provocar
la muerte o
lesiones serias.
RISQUE DE
DESCHARGE
ELECTRIQUE
OU EXPLOSION
xEteindre
toutes les
sources
d'énergie de
cet appareil
avant de
travailler
dessus de cet
appareil
xVérifier tous
connections, et
remettre tous
couverts en
olace avant de
mettre sous
De non-suivi de
ces instructions
provoquera la
mort ou des
lésions sérieuses
sérieuses.
GEF AHR EINES
ELEKTRISCHE
N SCHLAGES
ODER EINER
EXPLOSION.
xStellen Sie
jeglichen
Strom ab, der
dieses Gerät
versorgt, bevor
Sie an dem
Gerät Arbeiten
durchführen
xVor dem
Drehen auf
Energie alle
Anschlüsse
überprüfen
und alle
Abdeckungen
ersetzen.
Unterlassung
dieser
Anweisungen
können zum
Tode oder zu
schweren
Verletzungen
führen.
RISCHIO DI
SCOSSA
ELETTRICA O
DELL’ESPLOSIONE.
xSpenga tutta
l'alimentazione
che fornisce
questa
apparecchiatura
prima di lavorare
a questa
apparecchiatura
xVerificare tutti
i collegamenti
e sostituire
tutte le coperture
prima
dell’accensione
L'omissione di
queste istruzioni
provocherà la
morte o
lesioni serie
٪ሞۉĂ
Ԗቊۉࢷ
෻ຮླ၃
x
ሞ֡ፕُย
Ԣኮമ൩ံ
࠲Կۉᇸă
ැփፏ๰ኄၵຫ௽Lj
ీࣷڞዂჹዘڦ
ටวฅ࡞ฯ዁ຶྨă
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
ANNEX - ENVIROMENTAL INFORMATION
The environmental information disclosed in this annex including the EIP Pollution logo are in compliance with People’s Republic of China
Electronic Industry Standard SJ/T11364 – 2006, Marking for Control of Pollution Caused by Electronic Information Products.
Part
Name
Toxic or hazardous Substance and Elements
Lead Mercury Cadmium Hexavalent Polybrominated Polybrominated
(Pb) (Hg) (Cd) Chromium
(Cr (VI))
biphenyls
(PBB)
diphenyl ethers
(PBDE)
Semiconductor die
Solder
䱴Ԧ⧟؍ؑ᚟
此附件所标示的包括电子信息产品污染图标的环保信息符合中华人民共和国电子行业标准 SJ/T11364 - 2006,
电子信息产品污染控制标识要求。
ᴹ∂ᴹᇣ⢙䍘ᡆݳ㍐Ԧ
〠 䫵 ⊎ 䭹 ޝԧ䬜 ཊⓤ㚄㤟 ཊⓤҼ㤟䟊
(Pb) (Hg) (Cd) (Cr (VI)) (PBB) (PBDE)
ሬփ㣟⡷
✺᧕⛩
50
Do not forget to visit us at: www.crydom.com
Copyright © 2016 Crydom Inc. Specifications subject to change without notice.
'DWDVKHHW
DIN Rail Mount
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Crydom:
DRC3R40D400 DRC3P48B400R2 DRC3R48A420 DRC3P48B400R DRC3R40B400 DRC3R40A400
DRC3P48A400R2 DRC3P48A400R DRC3P48D411R2 DRC3P48D400R2 DRC3P48D420R2 DRC3R48D420
DRC3P48D400R DRC3R48B420 DRC3P48D420 DRC3P48D4202 DRC3P48D420R DRC3R40A420
DRC3R40B420 DRC3R40D420 DRC3R48A400 DRC3R48B400 DRC3R48D400 DRC3P48A400 DRC3P48A4002
DRC3P48A411 DRC3P48A4112 DRC3P48A411R DRC3P48A411R2 DRC3P48A420 DRC3P48A4202
DRC3P48A420R DRC3P48A420R2 DRC3P48B400 DRC3P48B4002 DRC3P48B411 DRC3P48B4112
DRC3P48B411R DRC3P48B411R2 DRC3P48B420 DRC3P48B4202 DRC3P48B420R DRC3P48B420R2
DRC3P48D400 DRC3P48D4002 DRC3P48D411 DRC3P48D4112 DRC3P48D411R