G2UM300VL20
24-240V
www.tele-online.com
AC/DC voltage monitoring in 1-phase mains
Monitoring relays - GAMMA series
Multifunction
16.6 to 400Hz
Fault latch
Zoom voltage 24 to 240V AC/DC
2 change-over contacts
Width 22.5mm
Industrial design
Technical data
1. Functions
AC/DC voltage monitoring in 1-phase mains with adjustable
thresholds, timing for start-up suppression and tripping delay
separately adjustable and the following functions (selectable by means
of rotary switch)
OVER Overvoltage monitoring
OVER+LATCH Overvoltage monitoring with fault latch
UNDER Undervoltage monitoring
UNDER+LATCH Undervoltage monitoring with fault latch
WIN Monitoring the window between Min and Max
WIN+LATCH Monitoring the window between
Min and Max with fault latch
2. Time ranges
Adjustment range
Start-up suppression time: 0s 10s
Tripping delay: 0.1s 10s
3. Indicators
Green LED ON: indication of supply voltage
Green LED flashes: indication of start-up suppression time
Yellow LED ON/OFF: indication of relay output
Red LED ON/OFF: indication of failure of the corresponding
threshold
Red LED flashes: indication of tripping delay
of the corresponding threshold
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40
Mounted on DIN-Rail TS 35 according to EN 60715
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required),
IP rating IP20
Tightening torque: max. 1Nm
Terminal capacity:
1 x 0.5 to 2.5mm² with/without multicore cable end
1 x 4mm² without multicore cable end
2 x 0.5 to 1.5mm² with/without multicore cable end
2 x 2.5mm² flexible without multicore cable end
5. Input circuit
Supply voltage:
24 to 240V AC/DC terminals A1-A2 (galvanically separated)
Tolerance:
24 to 240V DC -20% to +25%
24 to 240V AC -15% to +10%
Rated frequency:
24 to 240V AC 48 to 400Hz
48 to 240V AC 16 to 48Hz
Rated consumption: 4.5VA (1W)
Duration of operation: 100%
Reset time: 500ms
Wave form for AC: Sinus
Residual ripple for DC: 10%
Drop-out voltage: >15% of the supply voltage
Overvoltage category: III (in accordance with IEC 60661-1)
Rated surge voltage: 4kV
6. Output circuit
2 potential free change-over contacts
Rated voltage: 250V AC
Switching capacity: 750VA (3A / 250V AC)
If the distance between the devices is less than 5mm!
Switching capacity: 1250VA (5A / 250V AC)
If the distance between the devices is greater than 5mm!
Fusing: 5A fast acting
Mechanical life: 20 x 106 operations
Electrical life: 2 x 105 operations at 1000VA resistive load
Switching frequency: max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
(in accordance with IEC 60947-5-1)
Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage: 4kV
7. Measuring circuit
Fusing: max. 20A (in accordance with UL 508)
Measured variable: DC or AC Sinus (16.6 to 400Hz)
Input:
30V AC/DC terminals E-F1(+)
60V AC/DC terminals E-F2(+)
300V AC/DC terminals E-F3(+)
Overload capacity:
30V AC/DC 100Veff
60V AC/DC 150Veff
300V AC/DC 440Veff
Input resistance:
30VAC/DC 47kΩ
60VAC/DC 100kΩ
300VAC/DC 470kΩ
Switching threshold
Max: 10% to 100% of UN
Min: 5% to 95% of UN
Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage: 4kV
8. Accuracy
Baseaccuracy: ≤5%(ofmaximumscalevalue)
Frequency response: -10% to +5% (at 16.6 to 400Hz)
Adjustmentaccuracy: ≤5%(ofmaximumscalevalue)
Repetitionaccuracy: ≤2%
Voltage influence: -
Temperatureinfluence: ≤0.05%/°C
9. Ambient conditions
Ambienttemperature: -25to+55°C
(in accordance with IEC 60068-1)
-25to+40°C(inaccordancewithUL508)
Storagetemperature: -25to+70°C
Transporttemperature: -25to+70°C
Relative humidity: 15% to 85%
(in accordance with IEC 60721-3-3 class 3K3)
Pollution degree: 3 (in accordance with IEC 60664-1)
Vibration resistance: 10 to 55Hz 0.35mm
(in accordance with IEC 60068-2-6)
Shock resistance:
15g 11ms (in accordance with IEC 60068-2-27)
G2UM300VL20
24-240V
www.tele-online.com
Window function (WIN, WIN+LATCH)
The output relays switch into on-position (yellow LED illuminated) when
the measured voltage exceeds the value adjusted at the MIN-regulator.
When the measured voltage exceeds the value adjusted at the MAX-
regulator, the set interval of the tripping delay (DELAY) begins (red LED
MAX flashes). After the interval has expired (red LED MAX illuminated),
the output relays switch into off-position (yellow LED not illuminated).
The output relays again switch into on-position (yellow LED illuminated)
when the measured voltage falls below the value adjusted at the MAX-
regulator (red LED MAX not illuminated). When the measured voltage
falls below the value adjusted at the MIN-regulator, the set interval of the
tripping delay (DELAY) begins again (red LED MIN flashes). After the
interval has expired (red LED MIN illuminated), the output relays switch
into off-position (yellow LED not illuminated).
If the fault latch is activated (WIN+LATCH) and the measured voltage
remains below the MIN-value longer than the set interval of the
tripping delay, the output relays remain in the off-position even if the
measured voltage exceeds the value adjusted at the MIN-regulator. If
the measured voltage remains above the MAX-value longer than the set
interval of the tripping delay, the output relays remain in the off-position
even if the measured voltage falls below the value adjusted at the
MAX-regulator. After resetting the failure (interrupting and re-applying
the supply voltage), the output relays switch into on-position and a new
measuring cycle begins with the set interval of the start-up suppression
(START).
Functions
When the supply voltage U is applied, the output relays switch into
on-position (yellow LED illuminated) and the set interval of the start-up
suppression (START) begins (green LED U flashes). Changes of the
measured voltage during this period do not affect the state of the output
relay. After the interval has expired the green LED is illuminated steadily.
For all the functions the LEDs MIN and MAX are flashing alternating,
when the minimum value for the measured voltage was chosen to be
greater than the maximum value.
Overvoltage monitoring (OVER, OVER+LATCH)
When the measured voltage exceeds the value adjusted at the
MAX-regulator, the set interval of the tripping delay (DELAY) begins
(red LED MAX flashes). After the interval has expired (red LED MAX
illuminated), the output relays switch into off-position (yellow LED not
illuminated). The output relays again switch into on-position (yellow LED
illuminated), when the measured voltage falls below the value adjusted
at the MIN-regulator (red LED MAX not illuminated).
If the fault latch is activated (OVER+LATCH) and the measured voltage
remains above the MAX-value longer than the set interval of the tripping
delay, the output relays remain in the off-position even if the measured
voltage falls below the value adjusted at the MIN-regulator. After
resetting the failure (interrupting and re-applying the supply voltage), the
output relays switch into on-position and a new measuring cycle begins
with the set interval of the start-up suppression (START).
Undervoltage monitoring (UNDER, UNDER+LATCH)
When the measured voltage falls below the value adjusted at the
MIN-regulator, the set interval of the tripping delay (DELAY) begins
(red LED MIN flashes). After the interval has expired (red LED MIN
illuminated), the output relays switch into off-position (yellow LED not
illuminated). The output relays again switch into on-position (yellow LED
illuminated), when the measured voltage exceeds the value adjusted
at the MAX-regulator. If the fault latch is activated (UNDER+LATCH)
and the measured voltage remains below the MIN-value longer than
the set interval of the tripping delay, the output relays remain in the off-
position even if the measured voltage exceeds the value adjusted at the
MAX-regulator. After resetting the failure (interrupting and re-applying
the supply voltage), the output relays switch into on-position and a new
measuring cycle begins with the set interval of the start-up suppression
(START).
G2UM300VL20
24-240V
www.tele-online.com
Range 300V, supply voltage 24V AC/DC and fault latch
15
16 18
25
26 28
max.
20A
Umax=300V AC/DC
Reset
0V
24VAC/DC
Dimensions
Connections
Range 30V, supply voltage 24V AC/DC and fault latch
15
16 18
25
26 28
max.
20A
Umax=30V AC/DC
Reset
0V
24VAC/DC
Range 60V, supply voltage 230V AC and fault latch
15
16 18
25
26 28
max.
20A
Umax=60V AC/DC
Reset
L1
N
RELEASE 2009/07
Subject to alterations and errors