https://www.phoenixcontact.com/us/products/2906808
04/10/2017Page1/4
Surge protection device-TTC-6-2XTVSD-24DC-PT-2906808
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Fine surge protection with integrated status indicator for two signal wires with common reference potential.
Why buy this product
Space-saving installation due to the narrow overall width of 6.2 mm
Quick and tool-free installation of surge protective devices, thanks to Push-in connection technology
Key Commercial Data
Packing unit 1
GTIN
GTIN 4055626135724
Custom tariff number 85363010
Technical data
Dimensions
Height 105.8 mm
105.8 mm
Width 6.2 mm
Depth 69.5 mm
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
https://www.phoenixcontact.com/us/products/2906808
04/10/2017Page2/4
Surge protection device-TTC-6-2XTVSD-24DC-PT-2906808
Technical data
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: 35 mm
Design Rail-mountable module, one-piece
Direction of action Line-Earth Ground
Protective circuit
IEC test classification C1
C3
Nominal voltage UN24 V DC
Maximum continuous voltage UC30 V DC
Rated current 6 A (55 °C)
Residual current IPE ≤ 10 µA
Nominal discharge current In (8/20) µs (core-earth) 0.5 kA
Total discharge current Itotal (8/20)µs 1 kA
Voltage protection level Up (core-ground) ≤ 60 V (C1 - 1 kV/500 A)
≤ 45 V (C3 - 25 A)
≤ 50 V (C3 - 100 A)
Response time tA (core-earth) ≤ 1 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 300 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 960 kHz
Capacity (core-earth) typ. 2.2 nF
Resistance in series ≤ 100 mΩ
Surge protection fault message None
Max. required back-up fuse 6.3 A (FF)
Impulse durability (conductor-ground) C1 - 1 kV/500 A
C3 - 100 A
Connection data
Connection method Push-in connection
Connection method IN Push-in connection
Connection method OUT Push-in connection
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Standards and Regulations
https://www.phoenixcontact.com/us/products/2906808
04/10/2017Page3/4
Surge protection device-TTC-6-2XTVSD-24DC-PT-2906808
Technical data
Standards and Regulations
Standards/specifications IEC61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN61643-21 2001 + A1:2009 + A2:2013
Drawings
Diagram
I [A]
T [°C]
6
4
2
8
40 907050 60 80
Dimensional drawing
62
69,5
105,8 6,2⁺⁰¹
Circuit diagram
4
5
6
1
2
3
!
unprotected protected
Approvals
Approvals
Approvals
UL Listed
Ex Approvals
Approval details
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 138168
https://www.phoenixcontact.com/us/products/2906808
04/10/2017Page4/4
Phoenix Contact 2017 © - all rights reserved
http://www.phoenixcontact.com