https://www.phoenixcontact.com/us/products/2906840
04/13/2017Page1/6
Surge protection device-TTC-6-MOV-C-120AC-UT-I-2906840
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Medium surge protection with integrated status indicator for a signal wire with grounded reference potential.
The figure shows the version with
24VDC
Why buy this product
Space-saving installation due to the narrow overall width of 6.2 mm
Signaling without additional auxiliary power, thanks to the mechanical status indicator
Optional remote signaling module monitors up to 40 items, without additional wiring
Safe behavior in the event of overload, thanks to the integrated disconnect device
Medium surge protection by means of varistor
Key Commercial Data
Packing unit 1
GTIN
GTIN 4055626136967
Custom tariff number 85363010
Technical data
Dimensions
Height 92 mm
Width 6.2 mm
Depth 69.5 mm
Ambient conditions
https://www.phoenixcontact.com/us/products/2906840
04/13/2017Page2/6
Surge protection device-TTC-6-MOV-C-120AC-UT-I-2906840
Technical data
Ambient conditions
Ambient temperature (operation) -40 °C ... 85 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20 (with end cover)
General
Housing material PBT
Flammability rating according to UL 94 V-0
Color traffic grey A RAL 7042
Mounting type DIN rail: 35 mm
Design Rail-mountable module, one-piece
Direction of action Line-Earth Ground
Protective circuit
IEC test classification C1
C2
C3
Nominal voltage UN120 V AC
Maximum continuous voltage UC150 V AC
Rated current 10 A (60°C)
Operating effective current IC at UC≤ 100 µA
Residual current IPE ≤ 100 µA
Nominal discharge current In (8/20) µs (core-earth) 2.5 kA
Voltage protection level Up (core-ground) ≤ 200 V (C1 - 800 A)
≤ 500 V (C2 - 5 kV)
≤ 380 V (C3 - 25 A)
≤ 380 V (C3 - 35 A)
Response time tA (core-earth) ≤ 25 ns
Input attenuation aE, asym. typ. 0.3 dB (≤ 300 kHz / 150 Ω)
Cut-off frequency fg (3 dB), asym. (PE) in 150 Ohm system typ. 1 MHz
Capacity (core-earth) 5 nF
Resistance in series ≤ 100 mΩ
Surge protection fault message optical
Impulse durability (conductor-ground) C1 - 800 A
C2 - 2.5 kA
C3 - 35 A
Connection data
Connection method Screw connection
Connection method IN Screw terminal blocks
https://www.phoenixcontact.com/us/products/2906840
04/13/2017Page3/6
Surge protection device-TTC-6-MOV-C-120AC-UT-I-2906840
Technical data
Connection data
Connection method OUT Screw terminal blocks
Screw thread M3
Tightening torque 0.5 Nm ... 0.6 Nm
Stripping length 8 mm
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section solid 0.2 mm² ... 4 mm²
Conductor cross section AWG 24 ... 12
Standards and Regulations
Standards/specifications IEC61643-21 2000 + corrigendum 2001 + A1:2008, modified + A2:2012
EN61643-21 2001 + A1:2009 + A2:2013
Drawings
Diagram
I [A]
T [°C]
6
4
2
8
10
40 907050 60 80
Dimensional drawing
6,2
62
69,5
92
Circuit diagram
3
4
1
2
!
unprotected protected
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27130801
eCl@ss 5.0 27130801
eCl@ss 5.1 27130801
eCl@ss 6.0 27130807
eCl@ss 7.0 27130807
https://www.phoenixcontact.com/us/products/2906840
04/13/2017Page4/6
Surge protection device-TTC-6-MOV-C-120AC-UT-I-2906840
Classifications
eCl@ss
eCl@ss 8.0 27130807
eCl@ss 9.0 27130807
ETIM
ETIM 2.0 EC000943
ETIM 3.0 EC000943
ETIM 4.0 EC000943
ETIM 5.0 EC000943
ETIM 6.0 EC000943
UNSPSC
UNSPSC 6.01 30212010
UNSPSC 7.0901 39121610
UNSPSC 11 39121610
UNSPSC 12.01 39121610
UNSPSC 13.2 39121620
Approvals
Approvals
Approvals
UL Listed
Ex Approvals
Approval details
UL Listed http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 138168
Accessories
Accessories
Labeled terminal marker
https://www.phoenixcontact.com/us/products/2906840
04/13/2017Page5/6
Surge protection device-TTC-6-MOV-C-120AC-UT-I-2906840
Accessories
Zack Marker strip, flat-ZBF 6 CUS-0825027
Zack Marker strip, flat, Strip, can be ordered: Strip, white, labeled according to customer specifications, Mounting type:
Snap into flat marker groove, for terminal block width: 6.2 mm, Lettering field: 5.15 x 6.15 mm
Zack Marker strip, flat-ZBF 6,QR:FORTL.ZAHLEN-0808765
Zack Marker strip, flat, Strip, white, labeled, Printed vertically:Consecutive numbers 1 - 10, 11 - 20, etc. up to 91 - 100,
Mounting type: Snap into flat marker groove, for terminal block width: 6.2 mm, Lettering field: 5.15 x 6.15 mm
Marker pen
Marker pen-X-PEN 0,35-0811228
Marker pen without ink cartridge, for manual labeling of markers, labeling extremely wipe-proof, line thickness 0.35 mm
Terminal marking
Zack Marker strip, flat-ZBF 6:UNBEDRUCKT-0808710
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, Mounting type:
Snap into flat marker groove, for terminal block width: 6.2 mm, Lettering field: 5.15 x 6.15 mm
Zack Marker strip, flat-ZBF 6/WH-100:UNBEDRUCKT-0808736
Zack Marker strip, flat, Strip, white, unlabeled, can be labeled with: CMS-P1-PLOTTER, PLOTMARK, Mounting type:
Snap into flat marker groove, for terminal block width: 6.2 mm, Lettering field: 5.15 x 6.15 mm
https://www.phoenixcontact.com/us/products/2906840
04/13/2017Page6/6
Surge protection device-TTC-6-MOV-C-120AC-UT-I-2906840
Accessories
Additional products
Remote signaling set-TTC-6-FMRS-UT-2907810
Module for floating remote signaling of neighboring surge protective devices from the TERMITRAB complete product
range.
Cover-TTC-6-LCP-2908729
End cover for terminating a row of TERMITRAB complete TTC-6... terminal blocks
Shield connection-SSA 3-6-2839295
shield fast connections for conductor diameter 3 - 6 mm. Potential connection cable: 200 mm, black
Shield connection-SSA 5-10-2839512
Shield fast connection for conductor diameters 5 - 10 mm. Potential connection cable: 200 mm, black
Phoenix Contact 2017 © - all rights reserved
http://www.phoenixcontact.com