CORCOM Product Guide High Performance 3-Phase RFI Power Line Filters for WYE Applications A Series UL Recognized CSA Certified VDE Approved AYP/AYT A Series Specifications The 3-phase filters are designed for 3-phase, four wire, WYE applications providing filtering in each of the three lines plus the neutral and ground line. The 3-phase models feature: n Both common mode and differential mode suppression from 50 kHz to 30 MHz n Effective for both balanced and unbalanced three phase loads n Ground choke included n Shielded construction The dual stage AYT provides higher performance, while the single stage AYP is good for lower noise environments. Maximum leakage current, each line-to-ground: End Bell Mounting Accessories Mounting brackets available in two sizes, 20/30 amp (AA400) and 45/60 amp (AA405). End Bell mounting kit available in two sizes, 20/30 amp (AA406) and 45/60 amp (AA407). Filter AA406/407 End Bell Kit Cover Plate @ 120 VAC 60 Hz: @ 250 VAC 50 Hz: 1.4 mA 3.4 mA Hipot rating (one minute): line-to-ground neutral-to-ground line-to-neutral 1500 VAC 1500 VAC 1450 VDC Operating frequency: 50/60 Hz Rated voltage: phase-to-phase: phase-to-neutral/ground: 440 VAC 250 VAC Minimum insertion loss in dB: Line-to-ground in 50 ohm circuit Current Frequency - MHz Rating .05 .1 .15 .5 1 5 10 30 AYP6C 20A 30A 45A 60A 22 15 8 5 32 24 19 16 39 30 25 22 55 55 49 50 56 55 49 50 65 61 56 54 65 63 58 54 54 50 45 47 AYT6C 20A 30A 45A 60A 45 29 15 12 63 53 36 37 70 61 43 46 75 75 75 75 75 75 75 75 75 75 75 75 75 75 75 70 65 60 50 45 Line-to-line in 50 ohm circuit Frequency - MHz Current Rating .05 .1 .15 .5 1 5 10 30 AYP6C 20A 30A 45A 60A 20 18 8 20 38 28 20 24 50 43 27 27 65 65 60 60 65 65 65 65 65 65 65 65 60 59 56 56 52 48 43 50 AYT6C 20A 30A 45A 60A 27 17 14 26 56 46 41 50 65 55 50 58 70 75 75 75 70 75 75 75 70 75 75 75 70 75 75 75 70 70 65 60 8 Catalog 1654001 Revised 05-07 Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. USA Cust. Svc.: 1-800-468-2023 CORCOM Prods: 1-847-680-7400 Germany: 49-89-6089-0 www.corcom.com www.tycoelectronics.com CORCOM Product Guide High Performance 3-Phase RFI Power Line Filters for WYE Applications (Continued) A Series AYP6C & AYT6C A C E Part No. A* (max) B (max) C (max) 20AYP6C 8.82 224.0 8.82 224.0 9.43 239.5 9.43 239.5 13.82 351.0 13.82 351.0 13.83 351.3 13.83 351.3 5.57 141.5 5.57 141.5 6.92 175.8 6.92 175.8 5.57 141.5 5.57 141.5 6.92 175.8 6.92 175.8 2.56 65.0 2.56 65.0 4.82 122.4 4.82 122.4 2.56 65.0 2.56 65.0 4.82 122.4 4.82 122.4 30AYP6C 45AYP6C D RFI Power Line Filters Case Dimensions Case Style 60AYP6C B 20AYT6C 30AYT6C Terminals: 1/4 x 20 (10) Mounting studs: No. 8-32 (8) 45AYT6C 60AYT6C Torque 56 2 in. lbs. D E .030 .76 .015 .38 4.616 117.2 4.616 117.2 5.950 151.1 5.950 151.1 4.616 117.2 4.616 117.2 5.950 151.1 5.95 151.1 1.50 38.1 1.50 38.1 3.75 95.3 3.75 95.3 1.50 38.1 1.50 38.1 3.75 95.3 3.75 95.3 * For end bell covering terminals and connections, add: Electrical Schematics 20A & 30A 5.57 141.48 45A & 60A 6.45 163.83 AYP6C Models LINE LOAD A A B B C C N Part Numbers 20AYP6C 30AYP6C 45AYP6C 60AYP6C 20AYT6C 30AYT6C 45AYT6C 60AYT6C N LINE GND LOAD GND Mounting Hardware AYT6C Models LINE LOAD A A B B C C N N LINE GND LOAD GND Mounting Bracket Kit with Captive Nuts: AA400 (20/30 Amp) AA405 (45/60 Amp) End Bell Kit with Captive Nuts: AA406 (20/30 Amp) AA407 (45/60 Amp) Additional Captive Nuts to Mount Filters: AA401 (10 Nuts) Resistor location for reference only. 9 Catalog 1654001 Revised 05-07 Dimensions are in inches and millimeters unless otherwise specified. Values in italics are metric equivalents. Dimensions are shown for reference purposes only. Specifications subject to change. USA Cust. Svc.: 1-800-468-2023 CORCOM Prods: 1-847-680-7400 Germany: 49-89-6089-0 www.corcom.com www.tycoelectronics.com