Data sheet...
VSSC6 RTD EX Weidmüller Interface GmbH & Co. KG
Klingenbergstraße 16
D-32758 Detmold
Germany
Fon: +49 5231 14-0
Fax: +49 5231 14-292083
www.weidmueller.com
Technical data
Creation date April 26, 2013 10:31:09 PM CEST
Catalogue status 12.03.2013 / We reserve the right to make technical changes. 2
Dimensions and weights
Width 12.2 mm Height 88.5 mm
Depth 81 mm Net weight 37.8 g
Temperatures
Humidity 5...96 % Operating temperature -40 °C...+70 °C
Storage temperature -40 °C...+80 °C
Probability of failure
λges 61 MTTF 1,871 Years
PFH in 1*10-9 per hour 3.25 SFF 94.67 %
SIL in compliance with IEC 61508 3
General data
Colour Light Blue Mounting rail TS 35
Optical function display No Protection degree IP 20
Segment Instrumentation and
Control
UL 94 flammability rating
V-0
Insulation coordination acc. to EN 50178
Pollution severity 2 Surge voltage category III
Protection level
Protection level, UP wire - PE 126 V Protection level, UP wire - wire 15 V
technical data
Rated voltage (DC) 1 V Rated current 300 mA
Max. continuous voltage, Uc (DC) 5 V Discharge current In (8/20µs) wire-wire 2.5 kA
Discharge current Imax (8/20µs) wire-
wire 5 kA
Discharge current In (8/20µs) wire-PE
2.5 kA
Discharge current Imax (8/20µs) wire-PE 5 kA Discharge current, max. (8/20 µs) 10 kA
Protection level UP (typ.)
≤ 1650 V
Standards IEC61643-21:2009, DIN
EN 60079-0.2009, DIN EN
60079-26:2007, DIN EN
61241-11:2006
Colour Light Blue Humidity 5...96 %
Requirements category acc. to IEC
61643-21 C2, D1
Lightning test current Iimp (10/350 µs)
0.5 kA
Volume resistance 1.8 Ω 10 % Dielectric strength at FG against PE ≥ 500 V
Overload - failure mode Modus 2
Connection data
Clamping range, rated connection, min. 0.5 mm² Clamping range, rated connection, max. 4 mm²
Wire connection cross section, stranded,
rated connection, min. 0.5 mm²
Wire connection cross section, stranded,
rated connection, max. 4 mm²
Tightening torque, min. 0.5 Nm Tightening torque, max. 0.8 Nm