Circuit Breakers
DIN rail-mounted equipment protection
Phoenix Contact offers a full family of modular components
covering virtually all of your industrial electrical and electronic
needs as well as a broad range of value-added services.
CLIPLINE
• DIN rail-mount terminal blocks
• Marking materials and printers
Tools
• Ferrules
TRABTECH
• Surge voltage protection
INTERFACE
Analog signal converters • PLC cabling
• Power supplies • Rail-mount breakout modules
• Relays • Intrinsic safety modules
COMBICON
• PCB terminal blocks
• Electronic component housings
PLUSCON
• Industrial plug connectors
• Sensor cabling and sensor boxes
AUTOMATIONWORX
Solutions, products and services • Controllers and software
for DeviceNet, Profi bus, Ethernet • Fieldbus I/O
and Interbus • Ethernet infrastructure components
DIN rail-mounted
Thermal Miniature and Thermal Magnetic Circuit Breakers
1
Thermal Miniature Circuit Protection (TCP)
Thermal circuit proctectors use heat-sensitive bimetallic elements that respond to
overload electrical currents.
Thermal Miniature Circuit Protectors are compact protectors designed to
interrupt an electric current under overload conditions. The protector can accommodate
ten nominal currents ranging from 0.10 A to 10 A.
After an overload has occurred, TCP breakers are easily reset by pushing the reset button.
The breakers can be plugged into UK 6-FSI/C (screw) or ST 4-FSI/C (spring) terminal
blocks for convenient DIN rail mounting.
Thermal Magnetic Circuit Breakers (TMC)
Thermal Magnetic circuit breakers interrupt an electrical current under overload
or short-circuit conditions. They have both thermal circuit interruption and magnetic
interruption functions. The thermal function uses heat-sensitive bimetallic elements that
respond to overload currents. The magnetic function responds to very high current
overloads such as those that might occur during short-circuit conditions.
TMC 42 breakers are available in one- or two-pole confi guration for currents ranging
from 0.10 to 16 amps. TMC 42 breakers can be snapped directly on a DIN rail. They are
reset by pushing a red reset button.
TMC 60 breakers are available in one-, two-, or three-pole confi gurations for currents
ranging from 0.5 to 63 amps. TMC 60-Series breakers can be snapped directly on a DIN
rail. They are reset by moving the toggle switch to the green (activation) position.
TMC 1 breakers are available in one-, two- or three-pole confi gurations for currents
ranging from 0.1 to 32 amps. This high-density breaker has built-in auxiliary contacts.
TMC 1 breakers can be snapped directly on a DIN rail. They are reset by moving the
toggle switch to the I (activation) position.
The normal current load (nominal current)
Specify the size of the breaker in amps based on the normal
current load.
Possible types of failure
Match the short-circuit and overload protection requirements
to the performance characteristics of the breaker.
Rupture capacity
Specify the breaker, knowing the maximum fault current that
can be repeatedly (3x minimum) interrupted without failure
of the breaker.
Maximum interrupting capacity
Choose the breaker, knowing the maximum current at a
given voltage that the breaker can interrupt safely without
damage to surrounding components.
The wire size the breaker must accommodate
Determine if the breaker can accept the wire sizes required.
To choose a circuit breaker,
determine the following:
How fast the circuit breaker must react
to a fault condition
Specify a breaker by selecting a speed that avoids
nuisance tripping but protects against component damage.
How many poles are needed
Determine the number of poles needed that are
connected electrically and structurally.
Functional requirements of the breaker
Defi ne the requirements for visual inspection, switching,
auxiliary circuits or space.
Environmental factors –
temperature, moisture, vibration
Determine if there are unusual conditions in which the
breaker must operate.
Thermal (Miniature) Circuit Protectors (TCP)
3
TCPs are compact circuit protectors designed to interrupt an electric current under
overload conditions. There are ten nominal current ratings available, ranging from 0.10 A
to 10 A.
TCP protectors are trip-free and reset easily after a current interruption by pushing
the
reset button. The protector can be plugged into UK 6-FSI/C or ST 4-FSI/C fuse base
terminal blocks for convenient DIN rail-mounting.
[V AC] [V DC]
Nominal Voltage 250 72
2
Technical data for TCP
Time/current characteristic curve
Ambient temperature 23 C
Technical Data Type Order No. Pcs./Pkt.
Thermal Circuit Breaker Nominal current [A]
plugged into UK 6-FSI/C or ST 4-FSI/C base 0.10 TCP 0.10 07 12 10 7 1
terminal blocks 0.25 TCP 0.25 07 12 12 3 1
0.50 TCP 0.5 07 12 15 2 1
1.00 TCP 1 07 12 19 4 1
2.00 TCP 2 07 12 21 7 1
3.00 TCP 3 07 12 23 3 1
4.00 TCP 4 07 12 25 9 1
6.00 TCP 6 07 12 27 5 1
8.00 TCP 8 07 12 29 1 1
10.00 TCP 10 07 12 31 4 1
(1) Flat Zack strip, unprinted, 10-section for
ZBF 5: WH:
labeling the upper marker grooves Unprinted 08 08 64 2 10
Technical data in accordance with IEC/DIN VDE
Nominal voltage [V AC] / [V DC] 250 / 72
Nominal current [A] 0.10-10
Ambient temperature °C -20...+60
Interrupting capacity
for nominal currents of 0.10 - 4 A [A] 6x rated current *
for nominal currents of 6 - 10 A [A] 8x rated current **
for short circuit 2,000 Amps
Insulating material Polymide (PA), non-reinforced
Infl ammability class in accordance with UL 94 V0
Approval data (UL and c/UL) [V AC] / [V DC] / [A] 250 / 72 / 0.1-10
* If fault current exceeds 6 times IN, TCP may require replacing.
** If fault current exceeds 8 times IN, TCP may require replacing.
Thermal Miniature Circuit Breaker TCP compared to glass fuses
TCP Feature TCP Glass Fuses
Convenience Reset with reset button when overload is resolved Storing, ordering and locating issues
Deterioration Virtually no aging Age with eventual failure at normal loads
Life expectancy 3,000 operations at current rating, 500 operations at 2x current rating Unknown
Interruption detection Visual identifi cation Status not determined until fuse is removed from its holder
ON / OFF capability Switch duty actuator allows product to operate as an electrical switch Not applicable
Hot-swappable May be removed or replaced under load Not applicable
Controlled trip Avoids nuisance trips due to high in-rush currents Not applicable
...times rated current
Trip time in seconds
Screw: 48.11 mm, 1.89 in.
Spring: 45.31 mm, 1.78 in.
(breaker button up)
The time/current characteristic curve depends on the ambient temperatures. To avoid a premature or late
switch-off, the nominal current of the circuit breaker must be multiplied with a temperature factor.
Ambient temperature °F -4 14 32 73.4 104 122 140
°C -20 -10 0 23 40 50 60
Temperature factor 0.76 0.84 0.92 1 1.08 1.16 1.24
NOTE: If the TCP circuit protectors are mounted side-by-side with less than the minimum of 1 mm of space for air
movement, then do not exceed 80 percent of their rating.
Dimensional drawing Switching diagram
Nominal currents and internal
resistances
Nominal current Internal resistance
[A] [W]
0.1 81
0.25 14
.5 3.4
1 0.9
2 0.25
3 0.11
4 0.07
6 < 0.05
8 < 0.05
10 < 0.05
Technical Data Type Order No. Pcs./Pkt.
Fuse Terminal Block with universal foot for mounting on NS 32 or NS 35 DIN rails UK 6-FSI/C 31 18 20 3 50
Fuse Terminal Block Light indicator / voltage [V DC] Current [mA]
as shown above with light indicator LED red / 12 2.0 UK 6-FSI/C-LED 12 30 01 92 5 50
LED red / 24 2.0 UK 6-FSI/C-LED 24 30 01 93 8 50
(1) Fixed Bridge for cross connections in the terminal center, screw
heads with insulating collar, 10-position, divisible, with 10 screws FBI 10-8 imax:34 A 02 03 26 3 50
(2) Separating Plate for electrical separation of neighboring bridges,
can be fi tted later, no loss of pitch TS-KK 3 27 70 21 5 100
(3) Zack Strip, 10-section, white ZB 8: UNPRINTED 10 52 00 2 10
(4) Screwdriver SZS 1.0 x 4.0 12 05 06 6 10
Dimensions
Width / length [mm / in.] Width: 8.2 mm / 0.32 in.; Length: 64 mm / 2.52 in.
Height (NS 35:7.5/NS 35:15/NS 32) [mm / in.] NS 35:7.5: 7.5 mm / 0.30 in.; NS 35:15: 15 mm / 0.60 in.
Technical data in accordance with IEC/DIN VDE
Fuse type ISO/DIS 8820/DIN 72-581-3 - C
Maximum current with single arrangement1) [A] 30
Maximum power dissipation
Rated surge voltage / contamination class [k V] / - 4 / 3
Surge voltage category / insulation material group - | / - lll / l
Connection capacity
Stranded with ferrule without/with plastic sleeve [mm2 / in.2] Without: 0.25-6 mm2 / 0.00039-0.00930 in.2;
With: 0.25-4 mm2 / 0.00039-0.00620 in.2
Multi-conductor connection (2 cond. with same cross section)
Solid / stranded [mm2] Solid: 0.2-2.5; Stranded: 0.2-2.5
Stranded with ferrule without plastic sleeve [mm2] 0.25 - 2.5
Stranded with TWIN ferrule with plastic sleeve [mm2] 0.5 - 4
Stripping length [mm] 10
Internal cylindrical gauge (IEC 60 947-1) A5
Screw thread/torque - / [Nm] / in. lbs M 4 / 1.5-1.6 / M 4 / 13.3-14.2
Insulation material Polyamide (PA), non-reinforced
Infl ammability class in accordance with UL 94 V0
Approval data (UL and cUL)2) UL: [V] / [A] / AWG 300 / 30 / 26 - 8
Nom. voltage / nom. current / conduc. sizes cUL: [V] / [A] / AWG 300 / 30 / 26 - 8
1) Special arrangement on request
2) File number E 140459
Base terminal block with spring-cage connection for
accommodating the TCP circuit breaker ST 4-FSI/C
(IEC) rigid exible
[mm2] solid stranded AWG [A] [V]
Connection data 0.2 - 6 0.2 - 4 24 - 10 * 400*
* The current and voltage are determined by the thermal circuit breaker
Technical Data Type Order No. Pcs./Pkt.
Fuse Terminal Block with universal foot for mounting on 35 DIN rail ST 4-FSI / C 30 36 37 2 50
Fuse Terminal Block, 1) Light indicator / voltage [V DC] Current [mA]
as shown above with light indicator LED red / 12 2.0 ST 4-FSI / C-LED12 30 36 49 5 50
LED red / 24 2.0 ST 4-FSI / C-LED 24 30 36 50 5 50
(1) Insulating stop sleeve, prevents unintentional clamping of the insulation in the
case of smaller cross sections
Cross section range 0.25-0.5 mm2 / 0.0039-0.0077 in.2 Gray ISH 4 / 0.5 30 02 88 5 50
0.75-1 mm2 / 0.00116-0.00155 in.2 Black ISH 4 / 1 30 02 89 8 50
(2) Plug-in bridge, for cross connections in the terminal center 2-position FBS 2-8 imax:41 A 30 30 28 4 10
3-position FBS 3-8 41A 30 30 29 7 10
4-position FBS 4-8 41A 30 30 30 7 10
5-position FBS 5-8 41A 30 30 31 0 10
10-position FBS 10-8 41A 30 30 32 3 10
(3) Test adapter, for 4 mm Ø test adapter PS and 4 mm safety
test plugs, making contact in the bridge shaft PAI 4 30 30 92 5 10
(4) 2.3 mm Ø test plus 2, consisting of a metal part and a red insulating sleeve MPS-RD 02 01 55 3 10
(5) Modular test plug, can be labeled with ZBFM 8 PS 8 30 31 00 5 10
(6) Zack marker sheet, fl at, 50-section, for labeling in the outer marker grooves ZBFM 8/WH:
UNPRINTED 08 00 73 4 10
(7) Zack strip, 10-section, for labeling in the terminal center ZB 8: UNPRINTED 10 52 00 2 10
(8) Screwdriver, for actuating the spring cage SZF 1 - 0.6x3.5 12 04 51 7 10
Dimensions
Width / length [mm / in.] Width 8.2 mm / 0.32 in. / Length 86.5 mm / 3.4 in.
Height (NS 35:7.5/NS 35:15) [mm / in.] 7.5 mm / 0.30 in. / 15 mm / 0.60 in.
Technical data in accordance with IEC/DIN VDE
Fuse type ISO/DIS 8820/DIN 72 581-3 - C
Maximum current with single arrangement [A] 30
Maximum power dissipation
Rated surge voltage / contamination class [kV] / - 6 / 3
Surge voltage category / insulation material group - / - lll / l
Connection capacity
Stranded with ferrule without / with plastic sleeve [mm2] / AWG 0.25-4 mm2 / 24-12
Stranded with TWIN ferrule with plastic sleeve [mm2] / AWG 0.5-1 mm2 / 20-18
Stripping length [mm / in.] 10 / 0.39
Internal cylindrical gauge (IEC 60 947-1) A4
Insulation material Polyamide (PA), non-reinforced
Infl ammability class in accordance with UL 94 V0
Approval data (UL and cUL) UL: [V] / [A] / AWG 300 / 30 / 24 - 10
Nominal voltage/nominal current/conduc. sizes cUL: [V] / [A] / AWG 300 / 30 / 24 - 10
1) If the fuse is defective, the downstream circuit is not off-load
2) Additional colors are available on request
89.7 mm / 3.53 in.
(breaker button up)
Thermal Miniature Circuit Protector Base
4
92 mm / 3.62 in.
(breaker button up)
5
Thermal Miniature Circuit Protector Base
Base terminal block with screw connection for
accommodating the TCP circuit breaker UK 6-FSI/C
(IEC) rigid exible
[mm2] solid stranded AWG [A] [V]
Connection data 0.2 - 10 0.2 - 6 24 - 8 * 250*
* The current and voltage are determined by the thermal circuit breaker
Thermal Magnetic Circuit Breaker
TMC 42-01/42-02
7
Standard current ratings and typical internal resistance values
Technical Data
Maximum Voltage Rating 250 V AC, 50 / 60 Hz; 80 V DC
Current Rating Range 42-01 : 0.10...16 A
Typical Life 5,000 operations at 2 x lN
Temperature Range 0° to 55° C (32° to 131° F)
Creepage Resistance PTI 600 to IEC 112
Insulation Coordination
(IEC 664 and 664A) Rated Impulse Withstand Voltage Pollution Degree
Operating Area 4k V 3
Dielectric Strength
(IEC 664 and 664A) Test Voltage
Operating Area AC 4,000 V (double insulation)
Insulation Resistance
Interrupting Capacity >100 MΩ (DC 500 V)
(VDE 0660, Part 101, P-2) 0.05 to 0.8 A Self Limiting
1 to 2 A 200 A
2.5 to 16 A 400 A
Interrupting Capacity
(UL 1077/EN60934 PC1) I
N UN Self Limiting
0.05 to 16 A 250 V AC 1,000 A
0.05 to 16 A 80 V DC 1,000 A
Environmental Protection
(IEC 529/DIN 40050) Operating Area IP 40, Terminal Area IP 20
Vibration 5g (57-50 Hz), +0.38 mm (10-57 Hz) to IEC 68-2-6,
Test Fc 10 frequency cycles/axis
Shock 25g (11ms) to IEC 68-2-27, Test Ea
Corrosion 96 hours at 5% saltspray to IEC 68-2-11, Test Ka
Humidity 240 hours at 95% RH to IEC 68-2-3, Test Ca
Weight Approx. 60g
Conductor Size 0.5-6mm2 (AWG 20-AWG 10)
Recommended Torque 0.8 Nm max
Mounting Adapter 5650505 (TMC 42 C-Rail Adapter)
One- and two-pole thermal magnetic circuit breaker with tease-free, trip-free, snap action
mechanism
and two-button operation (M-type TMCBE to IEC 934). The one-pole features
a narrow profi le housing,
recessed terminals, standard DIN rail-mounting and precision
CBE performance.
Typical Applications
Circuit protection for process control systems, equipment manufacturers and instrumentation.
Approvals
Authority Voltage Ratings Current Ratings
VDE, Demko AC 250 V, DC 65 V 0.10 to 16 A
UL 1077, CSA AC 250 V, DC 80 V 0.10 to 16 A
Label Slot
6
Dimension
One-Pole
Two-Pole
Internal Wiring
Internal Wiring
The time/current characteristic curve depends on the ambient temperature
prevailing. In order to eliminate nuisance tripping, multiply the circuit breaker
current ratings by the derating factor shown below.
Ambient temperature
°F -22 -4 14 32 73.4 104 122 140
°C -30 -20 -10 0 23 40 50 60
Derating factor 0.76 0.79 0.83 0.88 1 1.08 1.16 1.24
Direct Current – Magnetic tripping
currents are increased by 30 percent in
DC circuits with the effect of shifting the
magnetic trip range 30 percent to the
right of AC trip curves.
Typical time / current characteristics at 23 degrees Celsius
Thermal Magnetic Circuit Breakers
TMC 42-01 One-Pole TMC 42-02 Two-Pole
Ohms Current Rating Type Part# Type Part #
447.00 0.05 TMC42-01-0.05 A 5600509* N/A N/A
131.00 0.10 TMC42-01-0.1 A 5530915 TMC42-02-0.1 A 5650123*
40.00 0.20 TMC42-01-0.2 A 5650102* TMC42-02-0.2 A 5650124*
19.30 0.30 TMC42-01-0.3 A 5650103* TMC42-02-0.3 A 5650127*
10.40 0.40 TMC42-01-0.4 A 5530944 TMC42-02-0.4 A 5531244*
7.10 0.50 TMC42-01-0.5 A 5650106* TMC42-02-0.5 A 5531257*
4.30 0.60 TMC42-01-0.6 A 5530960* TMC42-02-0.6 A 5531260*
3.30 0.70 N/A N/A TMC42-02-0.7 A 5650128*
2.50 0.80 TMC42-01-0.8 A 5530986* TMC42-02-0.8 A 5531286*
1.67 1.00 TMC42-01-1.0 A 5650108 TMC42-02-1.0 A 5531299
1.22 1.22 TMC42-01-1.2 A 5531008* TMC42-02-1.2 A 5531309*
0.61 1.50 TMC42-01-1.5 A 5650109 TMC42-02-1.5 A 5650129*
0.55 1.80 TMC42-01-1.8 A 5650110* TMC42-02-1.8 A 5531325*
0.38 2.00 TMC42-01-2.0 A 5600314 TMC42-02-2.0 A 5531338
0.24 2.50 TMC42-01-2.5 A 5650113* TMC42-02-2.5 A 5650130*
0.19 3.00 TMC42-01-3.0 A 5650114 TMC42-02-3.0 A 5650131
0.16 3.50 TMC42-01-3.5 A 5531053* TMC42-02-3.5 A 5531367*
0.09 4.00 TMC42-01-4.0 A 5531066 TMC42-02-4.0 A 5650134*
0.09 4.50 TMC42-01-4.5 A 5650115* TMC42-02-4.5 A 5650135*
0.06 5.00 TMC42-01-5.0 A 5531082 TMC42-02-5.0 A 5651396
0.07 5.50 TMC42-01-5.5 A 5531095* TMC42-02-5.5 A 5531406*
0.04 6.00 TMC42-01-6.0 A 5531105 TMC42-02-6.0 A 5650136*
0.04 6.50 TMC42-01-6.5 A 5650116* TMC42-02-6.5 A 5650137*
0.03 7.00 TMC42-01-7.0 A 5650117* TMC42-02-7.0 A 5531435*
0.02 8.00 TMC42-01-8.0 A 5650120 TMC42-02-8.0 A 5650138*
0.02 9.00 TMC42-01-9.0 A 5531147* TMC42-02-9.0 A 5531451*
<0.02 10.00 TMC42-01-10 A 5650121 TMC42-02-10 A 5531464
<0.02 11.00 TMC42-01-11 A 5531163* TMC42-02-11 A 5531477*
<0.02 12.00 TMC42-01-12 A 5650122* TMC42-02-12 A 5650141*
<0.02 13.00 TMC42-01-13 A 5531189* TMC42-02-13 A 5531493*
<0.02 14.00 TMC42-01-14 A 5531192* TMC42-02-14 A 5531503*
<0.02 15.00 TMC42-01-15 A 5600310 TMC42-02-15 A 5600309
<0.02 16.00 TMC42-01-16 A 5531202 TMC42-02-16 A 5650142*
* Indicates breakers that are made-to-order and may require an 8 to 10 week lead time.
Adapter x20040901
Adapter x20040901
Socket-Magnetic can
Socket-Magnetic can
be snapped on from
be snapped on from
both sides
both sides
Amps Temperature
-20˚C -15˚ -10˚ -5˚ +5˚ +10˚ +15˚ +20˚ +25˚ +30˚ +35˚ +40˚ +45˚ +50˚
-4˚F +5˚ +14˚ +23˚ +32˚ +41˚ +50˚ +59˚ +68˚ +77˚ +86˚ +95˚ +104˚ +113˚ +122˚
0.5 - 4.0 0.84 0.85 0.87 0.88 0.89 0.91 0.93 0.94 0.96 0.98 1.00 1.02 1.04 1.06 1.09
8.0 - 10 0.75 0.77 0.78 0.81 0.83 0.85 0.88 0.90 0.93 0.96 1.00 1.04 1.09 1.14 1.20
13 - 40 0.79 0.80 0.82 0.84 0.86 0.88 0.90 0.93 0.94 0.97 1.00 1.03 1.06 1.11 1.15
50-60 0.81 0.83 0.84 0.85 0.87 0.89 0.91 0.93 0.94 0.97 1.00 1.02 1.05 1.09 1.12
Thermal Magnetic Circuit Breakers - UL 1077
TMC 60 Series for mounting on 35 mm DIN rail
9
Overview
The TMC 60 Series provides supplemental overload and short-circuit protection.
An interrupt capacity of 10 kAIC at 480 / 277 V AC and DC ratings make the series
ideal for a wide range of applications.
These DIN rail-mountable circuit breakers are available in one-, two- and three-pole
confi gurations. An auxiliary contact in S- or H-function status output is also available.
The TMC 60 Series is UL recognized, CSA approved and carries the CE mark.
Typical Application
Circuit protection for power supplies, UPS, controller I/O points, relay/contactor
coils, control circuits, appliances and motor circuits.
8
Part Number Description
0902014 TMC 61C 0,5A
0902027 TMC 61C 01A
0902030 TMC 61C 02A
0902043 TMC 61C 03A
0902056 TMC 61C 04A
0902069 TMC 61C 06A
0902072 TMC 61C 10A
0902085 TMC 61C 13A
0902098 TMC 61C 16A
0902108 TMC 61C 20A
0902111 TMC 61C 25A
0902124 TMC 61C 32A
0902137 TMC 61C 40A
0902140 TMC 61C 50A
0902153 TMC 61C 63A
Part Number Description
0902166 TMC 62C 0,5A
0902179 TMC 62C 01A
0902182 TMC 62C 02A
0902195 TMC 62C 03A
0902205 TMC 62C 04A
0902218 TMC 62C 06A
0902221 TMC 62C 10A
0902234 TMC 62C 13A
0902247 TMC 62C 16A
0902250 TMC 62C 20A
0902263 TMC 62C 25A
0902276 TMC 62C 32A
0902289 TMC 62C 40A
0902292 TMC 62C 50A
0902302 TMC 62C 63A
Part Number Description
0902315 TMC 63C 0,5A
0902328 TMC 63C 01A
0902331 TMC 63C 02A
0902344 TMC 63C 03A
0902357 TMC 63C 04A
0902360 TMC 63C 06A
0902373 TMC 63C 10A
0902386 TMC 63C 13A
0902399 TMC 63C 16A
0902409 TMC 63C 20A
0902412 TMC 63C 25A
0902425 TMC 63C 32A
0902438 TMC 63C 40A
0902441 TMC 63C 50A
0902454 TMC 63C 63A
One-pole Two-pole Three-pole
Typical time/current characteristics at 23 degrees Celsius
Direct Current -
Magnetic tripping currents are
increased by 30 percent in DC
circuits with the effect of shifting
the magnetic trip range 30 percent
to the right of Alternating Current
(AC) trip curves.
10,000
1,000
100
10
1
0.1
0.01
0.001
Trip time in seconds
0.8 1 2 3 4 6 8 10 20 30 50 70 100
. . . times rated current
(multipole types: all poles symmetrically loaded)
lower trip limit 1,01 lN
upper trip limit 1,45 lN
rated current up to AC 6A
10,000
1,000
100
10
1
0.1
0.01
0.001
Trip time in seconds
0.8 1 2 3 4 6 8 10 20 30 50 70 100
. . . times rated current
lower trip limit 1,01 lN
upper trip limit 1,45 lN
rated current AC 10-40A
(50A 1-pole)
10,000
1,000
100
10
1
0.1
0.01
0.001
Trip time in seconds
0.8 1 2 3 4 6 8 10 20 30 50 70 100
. . . times rated current
lower trip limit 1,01 lN
upper trip limit 1,45 lN
rated current AC 63A
(50A 2+3 pol.)
The time/current characteristic curve depends on the ambient
temperature prevailing. In order to eliminate nuisance tripping, multiply
the circuit breaker current ratings by the derating factor shown at right.
Standard current ratings and typical internal resistance values
Technical Data
Maximum Voltage Rating AC 277 / 480 V
Interrupting Capacity 10,000 Amps
Current Rating Range 0.05 A to 63 A
Temperature Range
Operating Temperature -25° to +55°C (-13° to +131°F)
Storage Temperature -55° to +55°C (-67° to +131°F)
Insulation Values
(IEC 664 and 664A) Rated Impulse Withstand Voltage Pollution Degree
Operating Area 6.0 k V 3
Insulation Resistance >100 MΩ (DC 500 V)
Life at Rated 6,000 operations (UL tested)
Current Mechanical 10,000 operations
Cable Size max 35 mm2 / AWG 2 (LINE)
max 25 mm2 / AWG 3 (LOAD)
max 2.5 mm2 / AWG 12 (auxiliary circuits)
Minimum 1 mm
2
or AWG 16 for all circuits. Use a ferrule with wire sizes smaller than 16 AWG.
Vibration 3 g (10 to 55 Hz) to IEC 68-2-6
Trip Characteristics C: 0.5-63A
Torque 4.5 Nm / 39.8 lbf-in
Vibration
(per IEC 60077) 3 g (in x, y, z direction)
Plastics Rating per UL 94 V0
Protection Level IP 20
Configuration 1 pole 2 pole 3 pole
Weight 125 g 250 g 375 g
1110
Technical Data
Auxiliary Contact
Ratings Voltage / Current AC 240 V / 5 A
DC 24 V / 4 A
DC 60 V / 1 A
DC 220 V / 0.4 A
Contacts 1 Form C
Rated Wire Sizes 2.5 mm² / 14 AWG
Weight 70 g
Contact Functions* Auxiliary (H) or Signal (S)
* The TMC 6AUX S / H can operate as either an auxiliary contact (H function) or
a signal contact (S function). The operation of the auxiliary switch is determined at
the time of installation. The signal contact (function S) status provides the automatic
trip status of the protection device. The auxiliary (H function) provides the OPEN/
CLOSED status of the protective device. A test button on the front of the auxiliary
switch simulates functions S or H. The test button also acts as a reset for the trip
signal (function S) contacts.
Thermal Magnetic Circuit Breakers - UL 1077
TMC 60 Series Accessories
Accessories
Auxiliary Contact Lock Out Component
0902470 0902467
TMC 6AUX S / H TMC 6LOCKOUT
3-Phase Comb Bridge Single Row Comb Bridge
2809241*2809212*
3-Phase / 6 position Single Phase / 3 position
* Available in up to 57 positions
Dimensions
Note: all measurements in millimeters
DC Circuit Wiring
Marking
2809128
ZBN 18: UNBEDRUCKT
quantity: 10 pieces
End Covers
2809322
3-Phase bridge end cover
13
Standard current ratings and typical internal resistance values
Direct Current – Magnetic tripping
currents are increased by 30 percent
in DC circuits with the effect of
shifting the magnetic trip range 30
percent to the right of AC trip curves.
Typical time/current characteristics at 23 degrees Celsius
Thermal Magnetic Circuit Breakers
Internal TMC 1 M1 100 TMC 1 M1 200 TMC 1 F1 100 TMC 1 F1 200 TMC 2 M1 120 TMC 3 M1 122
Resistance Current One-Pole One-Pole One-Pole One-Pole Two-Pole Three-Pole
per Pole Ratings N/O Aux.Con.** N/C Aux. Con.** N/O Aux.Con. N/C Aux.Con. NO/NC Aux.Con. 1N/O 2N/C Aux.Con.
(ohms) (amps) Part # Part # Part # Part # Part # Part #
92 0.1 5650299* 5650418* N/A N/A 5650425* 5650467*
26.1 0.2 5531422 5531040* 5650525* 5531231 5650426* 5650470*
11.6 0.3 5650267* 5650416* 5650526* N/A 5650427* 5650471*
6.6 0.4 5650411* 5650417* 5650527* N/A 5650428* 5650472*
4.1 0.5 5531370 5531752* 5650528 5651057 5650429* 5650473*
3 0.6 5650412* 5650419* 5531817* N/A 5650430* 5650435*
1.65 0.8 5531273 5650420* 5650529* N/A 5650431* 5650436*
1.1 1.0 5531723 5531341* 5531914 5531532 5650254 5532997
0.47 1.5 5531176* 5531558 5650530* 5650282* 5650385* 5650437*
0.28 2.0 5531820 5531448* 5530928 5650352* 5517967* 5650438*
0.183 2.5 5531079* 5650421* 5650531* N/A 5650432 5650439*
0.124 3.0 5531927 5531545* 5531024 5602531* 5650255 5650440*
0.077 4.0 5530973 5531354* 5531875 5650829* 5650266 5650441*
0.063 5.0 5530931 5531642 5531121 5650830* 5512014 5650384
0.045 6.0 5531969 5600358* 5650532* 5650366* 5530863 5650442*
<0.02 7.0 N/A N/A N/A N/A 5605074 N/A
<0.02 8.0 5531037 5531749* 5531228* 5650831 5517954 5650443*
<0.02 10 5531862 5530957 5650533 5650283* 5511170 5650354
<0.02 12 5531134 5531846* 5650534* 5602532* 5650433* 5518979
<0.02 15 5510757 5650475* N/A N/A 5600432 5650353
<0.02 16 5531765 5531943* 5531574 5651032* 5530892 5530876
<0.02 20 5650413* 5650422* N/A N/A 5650308 5650445
<0.02 25 5650414* 5650423* N/A N/A 5650476* 5650446*
<0.02 32 5650415* 5650424* N/A N/A 5650434 5650447
The time / current characteristic curve depends on the ambient temperature prevailing. In order to eliminate nuisance
tripping, multiply the circuit breaker current ratings by the derating factor shown below.
Ambient temperature
°F -22 -4 14 32 50 73.5 86 104 122 140
°C -30 -20 -10 0 10 23 30 40 50 60
Multiplication factor 0.76 0.79 0.83 0.88 0.93 1 1.04 1.11 1.19 1.29
Thermal Magnetic Circuit Breaker (TMC)
TMC 1/2/3
12
Typical Applications
Process control equipment, robotics, machine tool control,
communications systems, instrumentation.
TMC Type Key for Orders
TMC 1 M1 100 1A
Nominal Current 0.2; 0.3; 0.4; 0.5; 0.6; 0.8; 1.5; 2;
2.5; 3; 4; 5; 6; 8; 10; 12; 15; 16; 20
Auxiliary Contact Variants 100: 1 position: 1 N / O contact
200: 1 position: 1 N / C contact
120: 2 position: 1 N / O, 1 N / C contact
122: 3 position: 1 N / O, 2 N / C contact
Characteristic Curve F1: Therm. 1.05-1.4 lN, magn. 2-4 lN DC (fast), only for
DC applications
M1: Therm. 1.05-1.4 lN, magn. 6-12 lN AC, 7, 8-15, 6 DC
(normal below)
Number of Main Current Paths 1: 1 position: 2: 2 position: 3: 3 position
Type Designation Thermal Magnetic Circuit Breaker
Dimensions
Technical Data
Maximum Voltage Rating AC 277 V; 3 AC 480 V (50/60 Hz)
DC 65 V
Current Rating Range 0.1...32 A non-inductive
Auxiliary Circuit 1 A, AC 277 V / DC 65 V
Typical Life 10,000 operations at 1 x lN
Temperature Range 0° to +55°C (+32° to +131°F)
Creepage Resistance PTI 400 to IEC 112
Insulation Coordination
(IEC 664 and 664A) Rated Impulse Withstand Voltage Pollution Degree
Operating Area 2.5 k V 2
Main/Auxiliary Circuit 2.5 k V 2
Pole/Pole 2.5 k V 2
Dielectric Strength
(IEC 664 and 664A) Test Voltage
Operating Area AC 3,000 V (double insulation)
Main / Auxiliary Circuit AC 3,000 V
Pole / Pole AC 1,500 V
Insulation Resistance >100 MΩ (DC 500 V)
Interrupting Capacity 0.1...5 A 400 A; 6...32 A 800 A
(VDE 0660, Part 101, P-2) Curve T2; 0.1...32 A 15 lN
(AC 250/415 V, DC 65 V) Curve M3; 0.1...2 A 200 A AC
Interrupting Capacity l
N U
N Self Limiting
(UL 1077/EN 60934 PC 1) 0.1...16 A AC 277 V 5,000 A
20...32 A AC 277 V 2,000 A
0.1...16 A 3 AC 480 V 5,000 A
20...32 A 3 AC 480 V 2,000 A
0.1...32 A DC 65 V 2,000 A
Environmental Protection Operating Area IP 30
(IEC 529/DIN 40050) Terminal Area IP 20
Vibration Curve F1:
3g (57-500 Hz) +0.23 mm (10-57 Hz)
Curves M1, M3, T1, T2:
5g (57-500 Hz +0.38 mm (10-57 Hz) to IEC 68-2-6,
Test FC 10 Frequency Cycles/Axis
Shock Curve F1: 25g (11 ms), directions 1-5
10g (11 ms), direction 6
Curves M1, M3, T1, T2
25g (11 ms), directions 1-5
20g (11 ms), direction 6 to
IEC 68-2-27, Test Ea
Corrosion 96 hours at 5% saltspray to IEC 68-2-11, Test Ka
Humidity 240 hours at 95% RH to IEC 68-2-3, Test Ca
Weight Approximately 60g per Pole
One-, two- and three-pole thermal magnetic circuit breakers with trip-free, snap action
mechanism and toggle actuation (S-type: IEC 934). Breaker has a universal mounting
foot so it can be snapped on both NS 35 and NS 32 mounting rail profi les. Available
with auxiliary contact (1 x N / O or 1 x N / C) for status signaling. Two- and three-pole
models are internally linked to ensure that all poles trip in the event of an overload on
one pole,
even if the actuator is held in the ON position. This circuit breaker can be
supplied in current
ratings to 32 A with a choice of characteristic curves. All screw
terminals are recessed for safety.
In the OFF position (contacts between
terminals 1 and 2 are open), the
auxiliary contacts between terminals
11 and 12 are considered N/C
In the OFF position (contacts between
terminals 1 and 2 are open), the
auxiliary contacts between terminals
13 and 14 are considered N/O
Internal Wiring Diagram
* Indicates breakers that are made-to-order and may require an 8- to 10-week lead time.
** N/O = Normally Open, N/C = Normally Closed
Circuit Protector Comparison Sheet
1514
Interrupting Maximum Overall Auxiliary Trip Tease Bus
Type Breaker Capacity Interrupting Trip Speed Size (mm) Contacts Free Free Connection
Protector (1) Construction Mechanism Poles Amps UL Voltage (2) (3) Capacity (4) (5) AWG HxDxW (6) (7) (8) Available (9) Characteristics
TMC 42 Thermal Single Body Push Button 1, 2 0.1-16 AC 250 Self-Limiting (0.1-8 A) 200A @ AC 250V (0.05-4.5A) Medium 20-8 Sol. 70 x 80 x 12 None Yes Yes Yes General Purpose,
1 Magnetic AC 250 200 A (1-2 A) 1,000A @ AC 250 / 125 (0.05-16A) [similar to C-type 20-10 Str. High Density Pkg.
2 DC 80 400 A (2.5-16 A) 1,000 @ DC 80V (0.05-16A) breaker]
TMC 1 Thermal Single Body Toggle 1, 2, 3 0.1-32 AC 277 400 A (0.1-5 A) 5,000A @ AC 277 / 480V (0.1-16A) Delayed Main – Up 90 x 80 x 12 1 N/O or N/C Yes Yes Yes Trip Speed Options,
Magnetic [similar to D-type
breaker]
2 3 AC 480 800 A (6-32 A) 2,000A @ AC 277 / 480V (20-32A) Medium to 10 Sol. 2 N/O, N/C Aux. Contacts
[similar to C-type
breaker]
3 DC 65 2,000A
@ DC 65V Fast Aux. – Up 3 N/O, 2 N/C
[similar to B-type to 16 Sol.
breaker]
TMC 61 Thermal Single Body Toggle 1 0.5-63 AC 277/480 10,000 A 10,000A @ AC 277 / 480V (0.5-63A) Medium Line to 2 70 x 95 x 18 Available Yes No Yes Low to High
TMC 62 Magnetic 2 (0.5-63 A) 6,000A
@ DC 48V [C-type breaker] Load to 3 AC Amperage
TMC63 3
TCP Thermal Two Piece: Push Button 1 0.1-10 AC 250 6 x Inductive AC 250V: 2,000A Slow 26-8 92.0 x 64.0 x 8.2 None Yes Yes Yes Plug-in,
Plugs into TCP Plugs DC 65 Load (0.1-5 A) DC 65V: 200A [similar to D-type Screw Screw; Bridge possible Thermal only,
UK6-FSI/C in Terminal breaker] Block; 89.7 x 86.5 x 8.2 on Base Blocks LED Available on
Screw or Blocks 8 x Inductive 24-10 Spring Base Block
ST 4-FSI/C Load (6-10 A) Spring
Spring Blk. Block
(1) Thermal Magnetic – Thermal provides overload protection; magnetic provides short-circuit protection.
(2) Interrupting capacity is the maximum fault current that can be repeatedly (3x minimum) interrupted without failure of the breaker.
(3) Self-limiting means that internal resistance is high enough to restrict the fl ow of current to a level that will not harm the circuit breaker.
(4) Maximum current at a given voltage at which the circuit breaker can interrupt safely without damage to surrounding components.
(5) Review trip curve for precise trip behavior of the breaker.
(6) N/O means auxiliary contacts are open and N/C means auxiliary contacts are closed when main terminal contacts are open.
(7) Trip-free means the breaker contacts cannot be forced or held closed during any fault condition (overloads or short circuits).
(8) Tease-free means breaker contacts cannot be forced close enough for current to arc (and potentially weld together) under a fault condition.
(9) A bus bar can connect to the supply terminal and can feed a series of breakers.
Load
Terminal
TMC 42 Series TMC 1 Series (with Alarm Contact)
Movable
Contact
Load
Terminal
Magnet
Line
Terminal
Alarm
Contact
Reset Button
Movable
Contact
Stationary
Contact
Load
Terminal
Bi-metal
Manual Release
Button
Magnet
Line
Terminal
1716