SPECIFICATION
DR-120-12 DR-120-24 DR-120-48
MODEL
DC VOLTAGE
RATED CURRENT
CURRENT RANGE
RATED POWER
OUTPUT VOLTAGE ADJ. RANGE
LINE REGULATION
LOAD REGULATION
SETUP, RISE TIME
HOLD UP TIME (Typ.)
VOLTAGE RANGE
FREQUENCY RANGE
EFFICIENCY (Typ.)
INPUT
INRUSH CURRENT (Typ.)
LEAKAGE CURRENT
OVER TEMPERATURE
SAFETY STANDARDS
SAFETY &
WORKING TEMP.
WORKING HUMIDITY
STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
MTBF
DIMENSIONOTHERS
NOTE
PACKING
OVERLOAD
OVER VOLTAGE
AC CURRENT (Typ.)
12V 24V 48V
10A 5A 2.5A
0 ~ 10A 0 ~ 5A 0 ~ 2.5A
120W 120W 120W
80mVp-p 80mVp-p 100mVp-p
12 ~ 14V 24 ~ 28V 48 ~ 53V
±2.0% ±1.0% ±1.0%
±0.5% ±0.5% ±0.5%
±1.0% ±1.0% ±1.0%
88 ~ 132VAC/176 ~ 264VAC by switch 248 ~ 370VDC
47 ~ 63Hz
80% 84% 85%
29 ~ 33V
90 5 (TSW1)℃± 90 5 (TSW1)℃±
58 ~ 65V
2.6A/115VAC 1.6A/230VAC
COLD START 20A/115VAC 40A/230VAC
<3.5mA / 240VAC
105 ~ 150% rated output power
15 ~ 16.5V
Protection type : Constant current limiting, recovers automatically after fault condition is removed
Protection type : Shut down o/p voltage, re-power on to recover
85 5 (TSW1)℃±
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
-10 ~ +60 (Refer to "Derating Curve")
20 ~ 90% RH non-condensing
-20 ~ +85 , 10 ~ 95% RH
±℃ )0.03%/ (0 ~ 50
10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
432.1Khrs min. MIL-HDBK-217F (25 )
65.5*125.2*100mm (W*H*D)
0.79Kg; 20pcs/16.5Kg/1.29CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25 of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. The ambient temperature derating of 3.5 /1000m with fanless models and of 5 /1000m with fan models for operating altitude higher than 2000m(6500ft).℃℃
File Name:DR-120-SPEC 2018-01-12
UL508, UL60950-1, TUV EN60950-1 approved,EAC TP TC 004
Compliance to EN55011,EN55032 (CISPR32) Class B, EN61000-3-2,-3, EAC TP TC 020
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), heavy industry level, criteria A, EAC TP TC 020
120W Single Output Industrial DIN RAIL Power Supply DR-120 series
Features :
AC input range selectable by switch
Protections: Short circuit / Overload / Over voltage / Over temperature
Cooling by free air convection
Can be installed on DIN rail TS-35/7.5 or 15
UL 508(industrial control equipment)approved
LED indicator for power on
100% full load burn-in test
Fixed switching frequency at 55KHz
3 years warranty
ENVIRONMENT
PROTECTION
EMC
(Note 4)
WITHSTAND VOLTAGE
ISOLATION RESISTANCE
I/P-O/P:3KVAC I/P-FG:2.0KVAC O/P-FG:0.5KVAC
I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25 / 70% RH
500ms, 70ms/230VAC 500ms, 70ms/115VAC at full load
36ms/230VAC 32ms/115VAC at full load
RIPPLE & NOISE (max.) Note.2
VOLTAGE TOLERANCE Note.3
EMC IMMUNITY
EMC EMISSION
Bauar
Sicherheit
egel gema
tgepruft
od
be
www.
ID 2000000000
tuv.com
wac g
os
NRND
Case No. 921A Unit:mm
INPUT VOLTAGE (V) 60Hz
OUTPUT VOLTAGE (V)
OUTPUT RIPPLE (mVp-p)
AMBIENT TEMPERATURE ( )
LOAD (%)
-100102030455060
20
40
60
80
100
12V,24V
48V
100
200
85
170160
8
80 180 190
9590
12
16
20
24
115
230210 220
110105 250240 264
125120 132
28
32
80
100
150
200
250
300
350
(VERTICAL)
Mechanical Specification
Static Characteristics (24V)
120W Single Output Industrial DIN RAIL Power Supply DR-120 series
Derating Curve
Block Diagram fosc : 55KHz
O.V.P.
CONTROL
FG
I/P -V
+V
RECTIFIERS
&
FILTER
SWITCHING
POWER
FILTER
&
RECTIFIERS
FILTER
EMI
O.L.P.
DETECTION
CIRCUIT
PWM
O.T.P.
230
115
Terminal Pin No. Assignment (TB1)
Terminal Pin No. Assignment (TB2)
Pin No.
Pin No.
1
1,2
2
3,4
3
Assignment
Assignment
FG
AC/L
AC/N
DC OUTPUT +V
DC OUTPUT -V
ADMISSIBLE DIN-RAIL: TS35/7.5 OR TS35/15
35
2
1
3
TB2
TB1
4
2
1
3
LED
+V ADJ.
125.2
115VAC
65.5
230VAC
100
File Name:DR-120-SPEC 2018-01-12
NRND