Product data sheet
Characteristics
MG24528
Multi 9 - C60 UL1077 - MCB - 2P - 40 A - D Curve
- 480Y/277 V - 5 kA
Product availability: Stock - Normally stocked in distribution facility
Price*: 224.00 USD
Main
Range Multi 9
Product or component-
type
Miniature circuit-breaker
Product name Multi 9 C60
Device short name C60 UL1077
Device application Distribution
Number of protected-
poles
2
[In] rated current 40 A at 77 °F (25 °C)
Network type DC
AC
Trip unit technology Thermal-magnetic
Breaking capacity code N
Suitability for isolation Yes conforming to EN/IEC 60947-2
Complementary
System Voltage 125 V DC
240 V AC
440 V AC
415 V AC
Mounting mode Clip-on
Poles description 2P
Breaking capacity AIR 10 kA at 240 V AC conforming to UL 1077
AIR 10 kA at 125 V DC conforming to UL 1077
Icu 6 kA at 440 V AC conforming to EN/IEC 60947-2
Icu 10 kA at 415 V AC conforming to EN/IEC 60947-2
Icu 20 kA at 240 V AC conforming to EN/IEC 60947-2
Icu 6 kA at 440 V AC conforming to GB 14048.2
Icu 10 kA at 415 V AC conforming to GB 14048.2
Icu 20 kA at 240 V AC conforming to GB 14048.2
AIR 5 kA at 480Y/277 V AC conforming to UL 1077
AIR 10 kA at 240 V AC conforming to CSA C22.2
AIR 5 kA at 480Y/277 V AC conforming to CSA C22.2
AIR 10 kA at 125 V DC conforming to CSA C22.2
Icu 10 kA at 125 V DC conforming to EN/IEC 60947-2
Icu 10 kA at 125 V DC conforming to GB 14048.2
Network frequency 50/60 Hz
Curve code D
Magnetic tripping limit 12 x In +/- 20% AC
17 x In +/- 20% DC
Limitation class 3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage 500 V AC conforming to EN/IEC 60947-2
[Uimp] rated impulse withstand voltage 6 kV conforming to EN/IEC 60947-2
Contact position indicator Yes
Control type Toggle
Local signalling ON/OFF indication
Mounting support DIN rail
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. *Prices are indicative
May 11, 2018
1