1
24-hour/Weekly Time Switch H2F
Up to 96 ON/OFF Cycles from DIN-sized
(72 x 72 mm) Timer
Easy setting with color-coded programming tabs.
Choose 24-hour or 1-week models with either
SPST-NO or SPDT control outputs.
Minute dial assures accurate settings.
Models with memory protection available.
Control outputs can be manually turned ON/OFF.
Designed for surface, flush, or track mounting.
RC
Ordering Information
Mounting
method
Control output
24-hour operation
1-week operation
Synchronous motor
Quartz motor (with
memory protection)
Quartz motor (with
memory protection)
Flush SPST-NO H2F-D H2F-DM H2F-WM
SPDT H2F-DC H2F-DMC H2F-WMC
Surface/track SPST-NO H2F-DF H2F-DMF H2F-WMF
SPDT H2F-DFC H2F-DMFC H2F-WMFC
Accessories (Order Separately)
Extra
programming tabs
1 pair for each ON/OFF (see note)
Y92S-21
Rechargeable Battery
Y92S-22
Note:
24-hour type is supplied with three pairs of programming tabs.
1-week type is supplied with seven pairs of programming tabs.
Specifications
Time Ranges
Operation
period
Minimum division Minimum set time
Maximum set time
24-hour
15 min 30 min
23 hrs 45 min
1-week
1 hr
2 hrs
166 hrs
ON/OFF Cycle
Operation
period
24-hour 1-week
Maximum cycles
96 84
Ratings
Rated
supply voltage
Synchronous motor: 100/1
10/120 V
AC, 200/220/240 V
AC (50/60 Hz) (see note)
Quartz motor: 100 to 240 V
AC (50/60 Hz)
Operating voltage range
85% to 1
10% of rated supply voltage
Power consumption
Synchronous motor: 3 V
A max.
Quartz motor: 1 V
A max. at 100 to 120 V
AC, 4 V
A max. at 200 to 240 V
AC
Control outputs
15 A at 250 V
AC, resistive load, SPST-NO, SPDT
Note:
Refer to
Precautions
.
H2F H2F
2
Characteristics
Item 24-hour
operation 1-week operation
Synchronous motor
Quartz motor
Accuracy of operating time (see note 1)
±
3 min max.
±
30 min max.
Influence of voltage
±
30 min max.
Influence of temperature
±
30 min max.
Setting error (see note 2)
±
3 min max.
±
30 min max.
Cyclic error
±
3 min max.
±
30 min max.
Memory protection against power
failure ---
180 hrs min. (see note 3)
Insulation resistance
100 M
Ω
min. (at 500 VDC)
Dielectric strength
2,000 V
AC, 50/60 Hz for 1 min (between current-carrying terminals and
non-current-carrying metal parts)
1,000 V
AC, 50/60 Hz for 1 min (between non-continuous contacts)
V
ibration resistance
Destruction:
16.7 Hz, 4-mm double amplitude
Malfunction:
10 to 55 Hz, 0.5-mm double amplitude
Shock resistance
Destruction:
1,000 m/s
2
(approx. 100G)
Malfunction:
200 m/s
2
(approx. 20G)
Ambient temperature
Operating: –10
°
C to 55
°C
Ambient humidity
Operating: 35% to 85%
Life expectancy
2 years min. (approx. 10,000 operations min.)
Approved standards
UL (File No. E52800), CSA (File No. LR22310)
Weight
Flush mounting: approx. 150 g
Surface mounting: approx. 200 g
Note: 1.
Accuracy of operating time of when the timer is ON or when the timer is OFF
.
2. Dif
ference between the set and actual operation time with the pointer set to the present time.
3.
When the timer is used for the first time after energization of 72 hrs.
H2F H2F
3
Dimensions
Note:
All units are in millimeters unless otherwise indicated.
Mounting Dimensions
Surface Mounting: H2F-DF/-DMF/-WMF
Track Mounting: H2F-DFC/-DMFC/-WMFC
Mounting
Holes
Two, M3 holes
M3.5
6
29
Screw size
M3 x 45
(included)
Flush Mounting: H2F-D/-DM/-WM/-DC/-DMC/-WMC
Panel Cutout
Recommended panel thickness: 3.2 mm
Note: The
mounting adapter and
screws
are included.
65.5
H2F H2F
4
Installation
Connections
Synchronous Motor Model
(SPST-NO Output)
H2F-D
(SPDT Output)
H2F-DC
H2F-DF H2F-DFC
Quartz Motor Model
(SPST-NO Output)
H2F-DM/H2F-WM
(SPDT Output)
H2F-DMC/WMC
H2F-DMF/H2F-WMF H2F-DMFC/WMFC
2
Note: Connect
an independent power source to the load.
H2F H2F
5
Precautions
Flush Mounting
1. To
mount the adapter to the panel cutout, first deform the adapter
by pushing it on the two opposing corners (as indicated by ar-
rows
A. Then
push part B into the cutout (i.e., toward the back of
the
panel).
Panel
Adapter
B
A
2. After
the adapter is mounted, insert the timer as shown in the fig
-
ure below. Secure the timer by tightening the two mounting
screws (M3 x 45) included as accessories.
3. If
the lead wires have been connected to the timer from the
front
of
the panel before the timer is mounted in the panel, engage the
timer to part A of the adapter and push it in the direction of B.
Then
tighten the two screws as described in 2.
Panel
Lead wire
B
A
Time Setting
To
set the time, turn the center knob clockwise to the correct time.
Turning
it
counterclockwise or turning it with your fingers hooked on
the
setting bracket may cause a malfunction.
Set
the hour to the arrow on the upper left corner of the front panel
and
the minute, to the arrow on the center knob.
Use
the gold setting tabs to set
the ON time and the silver ones to set
the
OFF time. Position the thick leg of the tab toward the outside of
the
dial and insert the tab securely into the groove on the dial.
Three pairs pairs of setting tabs are attached.
Store
the
spare tabs in the compartment at the lower right corner of
the
front panel.
H2F H2F
6
Manual Switch
SPST-NO Output
A 3-position selector switch, located at the lower left corner of the
front panel, determines output operation. In the OFF position, the
control
output is forcibly turned OFF regardless of the setting of the
programming tabs. Set to the AUTO position, the output is turned
ON
and OFF according to the settings of the programing tabs. In the
ON
position, the output is forcibly turned ON regardless
of the set
-
ting
of the programming tabs.
SPDT Output
When
the manual switch
at the lower left corner of the front is set to
the OFF position, both load 1 (connected across terminals 4 and 5)
and
load 2 (across 5 and 6) are turned OFF
.
When
it is set to the AUT
O position, the output is turned ON and OFF
according
to the setting of the programming tabs.
When
the manual switch is set to the ON position,
load 1 (connected
across terminals 4 and 5) is turned ON and load 2 (across
5
and 6) is
turned OFF.
Output Indicator
The
output indicator at the upper
left corner of the front panel shows
the
status of the output when the manual switch is set to the AUT
O
position.
In addition, the output can be manually turned ON or OFF by rotat
-
ing
the knob clockwise (in the arrow direction). The knob
will not turn
counterclockwise.
Note on H2F-D, -DF Series (synchronous motor versions)
Before
using
the timer
, select the appropriate frequency of your area
by
the frequency selector switch provided on
the upper part of the
rear panel.
Upper part of rear panel
(cycles per second)
H2F-jM Series (Quartz Motor Models)
Battery
Remove
the battery cover on the rear panel of the H2F
, load the pro
-
vided
Battery into the battery box, then turn ON the H2F
. Be sure to
load the Battery before using the
H2F
. If the Battery is not loaded,
the power indicator will flash and the H2F will not work properly
.
Press down.
Battery cover
Slide out
Be
sure to load the Battery with the correct polarity
. The polarity is
indicated in the battery box. After loading the Battery, be sure to
place
the cover on the battery box.
Battery
The
Battery is fully charged before shipment. The Battery may
lose
its
charge while the Battery is stored. Therefore, there is a backup
function
that is guaranteed for 180 hours on condition
that the Bat
-
tery
is
loaded into the H2F and charged continuously for 72 hours. If
the Battery has no charge, the H2F may not operate immediately
after it is turned ON. In that case, continue providing power to the
H2F
for three or more minutes before setting the time.
If
the H2F is turned ON and OFF frequently
, the Battery
life will be
greatly
reduced. Use the H2F with a continuous supply of power
.
The Battery has a life of approximately three years. If three years
have passed
since the Battery was loaded, replace the Battery as
soon as possible with a AAAA-size NiCd rechargeable battery
.
If
the H2F is idle over a long time, unload the Battery from the H2F
and
store the Battery separately in order
to prevent the Battery from
being
overly discharged.
H2F H2F
7
H2F H2F
8
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To
convert millimeters into inches, multiply by 0.03937. T
o convert grams into ounces, multiply by 0.03527.
Cat. No. L013-E1-3A In the interest of product improvement, specifications are subject to change without notice.
Printed
in Japan
1298-0.5C (0696)
OMRON Corporation
Supervisory Control Devices Division
28th Fl., Crystal T
ower Bldg.,
1-2-27, Shiromi, Chuo-ku,
Osaka 540-6028 Japan
Phone: (81)6-949-6035 Fax: (81)6-949-6069