General Purpose Relays Industrial Relays Potter & Brumfield W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers n n n n n n n Designed for the international market. UL Recognzied (UL1077 and UL1500), CSA Accepted and VDE approved. Ratings to 50 amps. Heavy duty #10-32 stud connections. (W9) Quick-connect or screw terminals. (W6) Several delay curve options. Choice of toggle or rocker actuator per pole or per unit (W6). Trip-free operation. Agency Approvals UL: Recognized as Supplementary Protector under UL 1077. Available models meet Ignition Protection requirements in accordance with UL1500. File E69543 CSA: Accepted as a Supplementary Protector. File LR15734. VDE: Approved to VDE 0642/EN 60 934 (Circuit Breakers for Equipment) License No. 73782 Users should thoroughly review the technical data before selecting a product part number. It is recommended that users also seek out the pertinent approvals files of the agencies/ laboratories and review them to confirm the product meets the requirements for a given application. Electrical Data Calibration: Breakers will hold 100% of rated current. Breakers may trip between 101% and 124% of rated load (134% for AC/ DC units). Breakers must trip at 125% of rated load and above (135% for AC/DC units). Dielectric Strength: 50/60 Hz., 1500V: DC, 1100V Insulation Resistance: 100 Megaohms at 500VDC Endurance: 10,000 on/off cycles - 6000 at rated load, 4000 at no load. Units tested at six cycles per minute, 1 second on and 9 seconds off at 25C ambient. Typical Resistance and Impedance Current DC 50/60 (Amps.)Resistance Impedance (Ohms) (Ohms) 0.2 90 90 1.0 1.2 1.2 2.0 0.28 0.28 5.0 0.04 0.04 10.0 0.013 0.013 20.0 0.004 0.005 30.0 0.0027 0.004 40.0 0.002 0.002 50.0 0.0015 0.0015 Tolerance: 0.1 - 4.99 15%; 5 - 9.99 20%; 10 - 15 25%; 16 - 30 50%. Mechanical/Environmental Data Operating Temperature: -40C to +85C. Humidity: Meets requirements of Mil-STD-202 method 103. Shock: Tested per Mil-STD-202, method 213, test condition C (100g @ 6 ms) Vibration: Tested per Mil-STD-202, method 201, 10-55 Hz., 0.06" (1.52mm) total excursion in 2 planes. 12-2014, Rev. 1214 www.te.com (c) 2014 Tyco Electronics Corporation, a TE Connectivity Ltd. company Datasheets and product specification according to IEC 61810-1 and to be used only together with the `Definitions' section. Mechanical/Environmental Data (continued) Fungus and Moisture Resistance: Special moisture resistant finish applied to all ferrous parts. Plastic parts are made of inherently fungus resistant material. Marking: International "1" and "0" symbols are marked on the toggle for both W6 and W9. W9 units have "ON" and "OFF" molded into the area at the base of the toggle. On a special order basis, graphics can be imprinted on the rockers of rocker actuated W6 units. VDE approved versions of rocker actuated W6 breakers have their rockers imprinted with "1" and "0". Mounting: Units are mounted with two #6-32 screws from the front of the panel. Metric models for use with M3 x 0.5 screws are available. To maintain published performance specifications, units should not be mounted more than 90 from their normal upright position. Weight: Approximately 2.5 ounces per pole. Approvals and Ratings Table 1 W6 Series Maximum Voltage 65 277 277 277/480 UL1077/CSA (All Circuit Functions) Current Interrupting Frequency Rating Capacity Phase (Hz) (Amps) (Amps) DC 0.2 - 50 2,000 50/60 1 0.2 - 20 5,000 50/60 1 21 - 50 2,500 50/60 3O-Wye 0.2 - 20 5,000 W9 Series UL1077/CSA (All Circuit Functions) Maximum Voltage Frequency (Hz) Phase 65 277 277/480 DC 50/60 50/60 1 3O-Wye W6 or W9 Series Interrupting Capacity (Amps) 2,000 5,000 5,000 VDE (Circuit Function X) Maximum Voltage Frequency (Hz) Phase 65 250 250 415/240 DC 50/60 50/60 50/60 1 1 3O W6 or W9 Series Current Rating (Amps) 0.2 - 50 0.2 - 50 0.2 - 20 Current Rating (Amps) 0.2 - 50 0.2 - 30 31 - 50 0.2 - 30 Interrupting Capacity (Amps) 2,000 5,000 2,000 5,000 UL1500 (Circuit Function X) Maximum Voltage Frequency (Hz) Phase 48 125/250 250 DC 50/60 50/60 1 3O-Wye Datasheets and product data is subject to the terms of the disclaimer and all chapters of the `Definitions' section, available at http://relays.te.com/definitions Current Rating (Amps) 0.2 - 50 0.2 - 50 0.2 - 50 Interrupting Capacity (Amps) 3,000 1,000 1,000 Datasheets, product data, `Definitions' section, application notes and all specifications are subject to change. 1 General Purpose Relays Industrial Relays Potter & Brumfield W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued) Time vs Current Trip Curves For W6 Series and W9 Series AC 50/60 Hz. DC & 50/60 Hz. TRIP TIMES OVERLOAD @ 50/60 Hz. & DC @ 400 Hz. 1000 125% 150% 200% 400% 600% 800% 10 1 May Trip 100 ms max. 30 ms max. 15 ms max. 12 ms max. 12 ms max. .1 100 10 1 10 - 150 2.2 - 20 .2 - 2 .03 - .75 .007 - .15 .005 - .04 .1 300 400 500 600 700 800 900 1000 1100 1200 LOAD CURRENT AS A PERCENT OF BREAKER RATING MOTOR START / LONG DELAY CURVE 10 HIGH INRUSH 50/60 Hz. AC OVERLOAD TRIP TIMES (SEC.) 125% 40 - 500 200% 9 - 100 400% 2 - 20 600% .8 - 10 800% .1 - 4.5 1000% .009 - 2 100 10 1 .001 0 10,000 .1 100 200 125 150 300 400 500 600 700 800 900 1000 1100 1200 LOAD CURRENT AS A PERCENT OF BREAKER RATING CURVE 12 HIGH INRUSH 50/60 Hz. OVERLOAD TRIP TIMES (SEC.) 125% 200% 400% 600% 800% 1000% 100 10 1 10 - 150 3 - 25 .5 - 2.5 .15 - 1 .015 - .7 .009 - .35 .1 100 200 125 150 300 .001 0 400 500 600 700 800 900 1000 1100 1200 LOAD CURRENT AS A PERCENT OF BREAKER RATING 125% 200% 400% 600% 800% 1000% 100 10 1 1 - 15 .15 - 1.5 .03 - .25 .007 - .15 .003 - .08 .003 - .04 .1 .001 0 100 200 125 150 300 400 500 600 700 800 900 1000 1100 1200 LOAD CURRENT AS A PERCENT OF BREAKER RATING CURVE 13 HIGH INRUSH 50/60 Hz. 10,000 OVERLOAD TRIP TIMES (SEC.) 1000 .01 .01 OVERLOAD TRIPTIMES (SEC.) 1000 .01 1000 TIME IN SECONDS 100 200 125 150 1000 TIME IN SECONDS 125% 200% 400% 600% 800% 1000% CURVE 3 SHORT DELAY 50/60 Hz. 10,000 .01 10,000 .001 0 OVERLOAD TRIP TIMES (SEC.) 1000 .01 .001 0 CURVE 2 STANDARD DELAY 50/60 Hz. TIME IN SECONDS TIME IN SECONDS 100 100 ms max. 55 ms max. 30 ms max. 15 ms max. 12 ms max. 12 ms max. 10,000 TIME IN SECONDS CURVE 0 INSTANTANEOUS TIME IN SECONDS 400 Hz. 10,000 125% 200% 400% 600% 800% 1000% 100 10 1 .8 - 30 .15 - 2.5 .03 - .3 .02 - .15 .009 - .12 .009 - .09 .1 .01 100 200 125 150 300 400 500 600 700 800 900 1000 1100 1200 LOAD CURRENT AS A PERCENT OF BREAKER RATING .001 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING DC TIME IN SECONDS 1000 125% 200% 400% 600% 800% 1000% 100 10 1 2 - 55 .60 - 8 .1 - 1.5 .02 - .5 .004 - .05 .004 - .025 .1 OVERLOAD TRIP TIMES (SEC.) 1000 125% 200% 400% 600% 800% 1000% 100 10 1 .6 - 7 .16 - 1.5 .03 - .25 .01 - .13 .004 - .05 .003 - .015 .1 .01 .01 .001 0 CURVE 3 SHORT DELAY DC 10,000 100 200 125 150 300 400 500 600 700 800 900 1000 1100 1200 LOAD CURRENT AS A PERCENT OF BREAKER RATING .001 0 CURVE 53 DC HIGH INRUSH 10,000 OVERLOAD TRIP TIMES (SEC.) 125% 80 - 700 200% 15 - 150 400% 2 - 20 600% .70 - 10 800% .10 - 3 1000% .01 - .1 1000 TIME IN SECONDS OVERLOAD TRIP TIMES (SEC.) TIME IN SECONDS CURVE 2 STANDARD DELAY DC 10,000 100 10 1 .1 .01 100 200 125 150 300 400 500 600 700 800 900 1000 1100 1200 LOAD CURRENT AS A PERCENT OF BREAKER RATING .001 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 125 150 LOAD CURRENT AS A PERCENT OF BREAKER RATING AC/DC 10,000 TIME IN SECONDS 1000 CURVE 34 DC, 50/60 Hz. STANDARD DELAY OVERLOAD TRIP TIMES (SEC.) 135% 200% 400% 600% 800% 1000% 100 10 1 1 - 90 .60 - 20 .095 - 2 .02 - .95 .002 - .45 .002 - .09 .1 .01 .001 0 100 200 300 400 500 600 700 800 900 1000 1100 1200 125 150 LOAD CURRENT AS A PERCENT 135 OF BREAKER RATING Note: For instantaneous curves for all voltages refer to Curve 0 instananeous under the AC 50/60 Hz. heading 2 12-2014, Rev. 1214 www.te.com (c) 2014 Tyco Electronics Corporation, a TE Connectivity Ltd. company Datasheets and product specification according to IEC 61810-1 and to be used only together with the `Definitions' section. Datasheets and product data is subject to the terms of the disclaimer and all chapters of the `Definitions' section, available at http://relays.te.com/definitions Datasheets, product data, `Definitions' section, application notes and all specifications are subject to change. General Purpose Relays Industrial Relays Potter & Brumfield W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued) Product code structure W Typical product code 67- X 2 Q 1 2- 20 W6 Series Circuit Breaker Mounting W #6-32 mounting threads M M3.0 x 0.5 mounting threads Number of Poles 67 Single Pole 68 Two Pole 69 Three Pole 70 Four Pole Circuit Function (Only X is VDE approved) X Series trip Actuator One actuator per pole 1 Black toggle 3 2 White toggle 4 Black rocker White rocker 5 6 Red rocker Grey rocker One actuator per unit 7 Black toggle 8 White toggle J Black rocker 9 Red toggle Termination Q .250" QC (DIN 46 244) [30A Max. UL/CSA; 25A Max. VDE] S #8-32 screw [30A Max.] T #10-32 screw [50A Max.] U #8-32 screw, nickel plated, bent inward 30 [30A Max.] V #10-32 screw, nickel plated, bent inward 30 [30A Max.] Notes: #10-32 termination must be used for all ratings of greater than 30 amps. #10-32 termination must be specified for circuit function D, but relay trip pole will be equipped with .250" QC. Maximum Line Voltage (see Table 1 for current ranges) UL/CSA 1 277VAC, 50/60 Hz. Types 2 277/480VAC, 50/60 Hz. [20A Max.] (Requires insulating barriers, see outline dimension drawing) 5 65VDC 7 AC/DC 277VAC, 50/60 Hz. or 65VDC (Time delay curve 34 must be specified) 8 AC/DC 120VAC, 120/240VAC, 48VDC (Agency Approval M [UL1500] and time delay curve 34 must be specified) VDE Types 1 5 7 250VAC, 415/240VAC 65VDC AC/DC 250VAC, 415/240VAC, 65VDC (Time delay curve 34 must be specified) Time Delay Curve 0 Instantaneous 2 Standard delay 3 Short delay 53 DC high inrush Amp Rating 0.2 0.50 0.25 0.75 1.0 1.5 2.0 2.5 10 AC high inrush motor start / long delay 12 AC high inrush version of #2 13 AC high inrush version of #3 34 Combination AC/DC standard delay 3.0 3.5 4.0 5.0 6.0 7.0 7.5 8.0 9.0 11.0 10.0 12.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 Consult factory for other values Agency Approval Blank UL1077/CSA breaker V VDE approved breaker M UL1077/UL1500 ignition protected breaker Authorized distributors are more likely to stock the following items. W67-X2Q10-3 W67-X2Q10-5 W67-X2Q12-2 W67-X2Q12-3 W67-X2Q12-5 W67-X2Q12-7 W67-X2Q12-10 W67-X2Q12-15 W67-X2Q12-20 W67-X2Q12-30 W67-X2Q13-1 W67-X2Q13-2 12-2014, Rev. 1214 www.te.com (c) 2014 Tyco Electronics Corporation, a TE Connectivity Ltd. company W67-X2Q13-3 W67-X2Q13-10 W67-X2Q13-15 W67-X2Q13-20 W67-X2Q13-25 W67-X2Q13-30 W67-X2Q50-5 W67-X2Q50-10 W67-X2Q52-5 W67-X2Q52-10 W67-X2Q52-15 W67-X2Q52-20 Datasheets and product specification according to IEC 61810-1 and to be used only together with the `Definitions' section. W67-X2Q52-30 W67-X2Q110-15 W67-X2Q110-20 W68-X2Q12-3 W68-X2Q12-5 W68-X2Q12-7 W68-X2Q12-10 W68-X2Q12-15 W68-X2Q12-20 W68-X2Q12-25 W68-X2Q12-30 W68-X2Q13-15 Datasheets and product data is subject to the terms of the disclaimer and all chapters of the `Definitions' section, available at http://relays.te.com/definitions W68-X2Q110-10 W68-X2Q110-20 W69-X2Q12-5 W69-X2Q12-10 W69-X2Q12-15 W69-X2Q12-20 W69-X2Q12-25 W69-X2Q12-30 W69-X2Q110-20 W69-X2Q110-30 Datasheets, product data, `Definitions' section, application notes and all specifications are subject to change. 3 General Purpose Relays Industrial Relays Potter & Brumfield W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued) Product code structure W Typical product code 91- X 1 1 2- 20 W9 Series Circuit Breaker Mounting W #6-32 mounting threads M M3.0 x 0.5 mounting threads Number of Poles 91 Single Pole 92 Two Pole 93 Three Pole 94 Four Pole Circuit Function (Only X is VDE approved) X Series trip Actuator One actuator per pole 1 Black toggle 2 White toggle Maximum Line Voltage (see Table 1 for current ranges) UL/CSA 1 277VAC, 50/60 Hz. Types 2 277/480VAC, 50/60 Hz. [20A Max.] 5 65VDC 7 AC/DC 277VAC, 50/60 Hz. or 65VDC (Time delay curve 34 must be specified) 8 AC/DC 120VAC, 120/240VAC, 48VDC (Agency Approval M [UL1500] and time delay curve 34 must be specified) VDE Types 1 5 7 250VAC, 415/240VAC 65VDC AC/DC 250VAC, 415/240VAC, 65VDC (Time delay curve 34 must be specified) Time Delay Curve 0 Instantaneous 2 Standard delay 3 Short delay 53 DC high inrush Amp Rating 0.20 0.75 0.25 1.00 0.50 1.50 2.0 2.5 3.0 10 AC high inrush motor start / long delay 12 AC high inrush version of #2 13 AC high inrush version of #3 34 Combination AC/DC standard delay 3.5 4.0 5.0 6.0 7.0 7.5 8.0 11.0 9.0 12.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 50.0 Consult factory for other values Agency Approval Blank UL1077/CSA approved breaker V VDE approved breaker M UL1077/UL1500 ignition protected breaker Authorized distributors are more likely to stock the following items. W91-X112-1 W91-X112-2 W91-X112-3 W91-X112-5 W91-X112-7 W91-X112-10 4 W91-X112-15 W91-X112-20 W91-X112-40 W91-X112-50 W91-X113-5 W91-X113-10 12-2014, Rev. 1214 www.te.com (c) 2014 Tyco Electronics Corporation, a TE Connectivity Ltd. company W91-X113-15 W91-X150-5 W91-X152-10 W91-X152-15 W91-X152-20 W91-X152-30 W91-X152-40 W91-X152-50 W91-X1110-20 W92-X112-1 W92-X112-2 W92-X112-3 Datasheets and product specification according to IEC 61810-1 and to be used only together with the `Definitions' section. W92-X112-5 W92-X112-7 W92-X112-10 W92-X112-15 W92-X112-20 W92-X112-25 W92-X112-30 W92-X112-40 W92-X112-50 W92-X113-15 W92-X113-20 W92-X1110-20 Datasheets and product data is subject to the terms of the disclaimer and all chapters of the `Definitions' section, available at http://relays.te.com/definitions W92-X1110-30 W93-X112-5 W93-X112-10 W93-X112-15 W93-X112-20 W93-X112-25 W93-X112-30 W93-X112-40 W93-X112-50 W93-X1110-20 W93-X1110-30 Datasheets, product data, `Definitions' section, application notes and all specifications are subject to change. General Purpose Relays Industrial Relays Potter & Brumfield W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued) Outline Dimensions - Toggle Actuator Models W6 Series Panel Mounting Cutout 2.043 (51.89) .235 (5.97) 1.640 (41.66) LINE .66 (16.8) .245 (6.22) (15.88 +0.25 ) -0.00 ON A .750 (19.05) O .625 +.010 -.000 1 PER POLE 29 1.520 (38.61) 1.660 (42.16) 1.048 (26.62) 30 OFF B O .156 [2 PLACES PER POLE] (3.96) LOAD W6 Series - One Actuator Per Pole 1 Pole O .590 (15.00) 2 Pole .750 (19.05) 3 Pole 4 Pole 3.000 (76.20) 2.250 (57.15) 1.500 (38.10) 1.660 (42.16) 2.000 (50.80) 1.05 (26.67) 1.22 (31.00) 6.32 TH'D. .14 (3.56) DP. TYP. M3 X 0.5 OPTIONAL Note: Multi-pole models furnished with seperate handle tie hardware W6 Series - One Actuator Per Unit 1 Pole 2 Pole O .590 (15.00) .750 (19.05) 3 Pole 4 Pole 2.250 (57.15) 1.500 (38.10) 3.000 (76.20) 1.660 (42.16) 2.000 (50.80) 1.22 (31.00) 1.05 (26.67) 6.32 TH'D. .14 (3.56) DP. TYP. M3 X 0.5 OPTIONAL Note: 4-pole models furnished with sperate handle tie hardware 480V Model with Barriers 2.250 (57.15) .269 (6.83) 2.778 (70.56) 2.530 (64.26) .235 2.032 Termination Options (5.97) (51.61) Note: 3-pole model shown LINE .266 (6.76) Notes: 1. Terminal protrusion dimensions are referenced from back of mounting panel 2. Main terminals are male quick connect type .250 (6.35) wide x .031 (.79) thick x .377 (9.58) long. Optional 8-32 x .250 (6.35) or 10-32 x .250 (6.35) screw type 3. Panel mounting cutout detail mtg. detail tol.: .005 (.13) unless noted. Add additional cutouts to correspond to number of poles. Outline drawing tolerance .015 (.35) unless noted 12-2014, Rev. 1214 www.te.com (c) 2014 Tyco Electronics Corporation, a TE Connectivity Ltd. company LINE A A Datasheets and product specification according to IEC 61810-1 and to be used only together with the `Definitions' section. LINE A 1.520 (38.61) B LOAD B LOAD Datasheets and product data is subject to the terms of the disclaimer and all chapters of the `Definitions' section, available at http://relays.te.com/definitions LOAD .416 (10.56 1.058 (26.97) .827 (21.00) B Datasheets, product data, `Definitions' section, application notes and all specifications are subject to change. 5 General Purpose Relays Industrial Relays Potter & Brumfield W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued) Outline Dimensions - Optional Toggle Guards W6 Series .03 (.76) .95 (24.1) .08 (2.03) .313 (7.95) 2x .27 DIA. (6.86) 2.185 INSIDE (55.50) 1.093 (27.76) .75 (19.05) .75 (19.05) .2 x R1.0 (25.4) .47 (11.94) .17 (4.32) 2.00 (50.8) 1.375 INSIDE (34.92) .313 (7.95) .75 (19.05) .625 INSIDE (15.88) .78 (19.8) .17 REF. (4.32) .625 (15.88) 1.66 (42.16) .44 (11.18) .53 (13.46) 2 x .16 DIA. (4.06) 4 x .16 DIA. (4.06) 84-005 (for 2 Pole Breaker) 84-004 (for 1 Pole Breaker) 84-004 toggle guard shown with W67 series circuit breaker mounted in a panel. .20 (5.08) 6 x .16 DIA. (4.06) 84-006 (for 3 Pole Breaker) Optional toggle guards may be ordered seperately for use on W6 toggle actuator models. These guards help to prevent accidental operation and allow the breaker to be locked in the "off" position. Outline Dimensions - Rocker Actuator Models 1 Pole (Shown with optional "ON" and "OFF" graphics) W6 Series 1.769 (44.93) .240 (6.10) LOAD .392 (9.96) .774 (19.65) .750 (19.05) .388 (9.86) 1.500 (38.10) 2 POLE .375 (9.53) .180 (4.57) 2.250 (57.15) 3.000 (76.20) 3 POLE 4 POLE D 2.000 (50.80) 1.660 (42.16) 1.520 (38.61) LINE 2, 3 & 4 Pole, One Actuator Per Pole 1.995 (50.68) 1.30 (33.0) A ON OFF 2.608 (66.24) 2.435 (61.85) .750 (19.05) .388 (9.86) 2.600 (66.04) TAPPED FOR #6-32 M3 X 0.5 OPTIONAL TAPPED FOR #6-32 M3 X 0.5 OPTIONAL .375 (9.53) .375 (9.53) .750 (19.05) .750 (19.05) .750 (19.05) 2, 3 & 4 Pole, One Actuator Per Unit 1.500 (38.10) 2.250 (57.15) 3.000 (76.20) .388 (9.86) 2.000 (50.80) 2.600 (66.04) 1.660 (42.16) 1.660 (42.16) .375 (9.53) .375 (9.53) Panel Mounting Cutout .375 (9.53) .750 (19.05) .750 (19.05) .750 (19.05) 6 .750 (19.05) 1.500 (38.10) 3.000 (76.20) 12-2014, Rev. 1214 www.te.com (c) 2014 Tyco Electronics Corporation, a TE Connectivity Ltd. company .750 (19.05) .375 (9.53) .750 (19.05) .750 (19.05) .750 (19.05) .750 (19.05) VDE Rocker Marking I 2.250 (57.15) TAPPED FOR #6-32 M3 X 0.5 OPTIONAL .205 (5.21) 1.250 (31.75) 1.660 (42.16) 1 POLE 2 POLE 3 POLE 4 POLE .750 (19.05) O O .156 (3.96) TYP. 2 PER POLE Notes: 1. Outline drawing tolerance .015 (.38) unless noted. Dimensions in brackets ( ) are in milimeters. 2. Mounting Detail Tol. .005 (.013) unless noted Datasheets and product specification according to IEC 61810-1 and to be used only together with the `Definitions' section. Datasheets and product data is subject to the terms of the disclaimer and all chapters of the `Definitions' section, available at http://relays.te.com/definitions Datasheets, product data, `Definitions' section, application notes and all specifications are subject to change. General Purpose Relays Industrial Relays Potter & Brumfield W6/W9 Series Magnetic Hydraulic P&B Circuit Breakers (Continued) Outline Dimensions W9 Series Series Trip Model Series Trip Model .060 (1.52) .375 .281 (9.52) (7.14) 1.845 (46.86) 1.15 (29.21) LINE .313 (7.95) ON 29 1.940 (49.28) .060 (1.52) 30 .14 2.10 (3.56) (53.34) 2.50 (64.00) ON ON OFF OFF OFF LOAD #10-32 STUD TERMINATION .750 (19.05) .375 (9.53) .218 (5.54) 2.065 (52.45) ON ON OFF OFF .750 (19.05) ON ON TAPPED #6-32 X .16 (4.06) DEEP M3 X 0.5 OPTIONAL .750 (19.05) ON ON .398 (10.11) ON ON OFF OFF OFF OFF OFF OFF 2 POLE 1.500 (38.10) 2.250 (57.15) 1 POLE .74 (18.8) .750 (19.05) .375 (9.53) 3POLE 3.000 (76.20) 1.438 (36.53) 2.50 (63.5) 4 POLE Note: 1. Top mounted plate (shown with broken line) is present only on UL1500 models Panel Mounting Cutout Detail .732 (18.59) .750 (19.05) .750 (19.05) .750 (19.05) .385 (9.78) .907 (23.04) 1.450 (36.83) 2.065 (52.45) 2X O .156 (3.96) PER POLE 3.04 (77.2) 2.28 (57.9) 1.52 (38.6) .76 (19.3) 1 POLE 2 POLE 3 POLE 4 POLE Notes: 1. Terminal protrusion dimensions are referenced from the back of the mounting panel 2. Mounting detail tolerance .005 (13) unless noted 3. Outline drawing tolerance .015 (.38) unless noted Dimensions in brackets ( ) are in milimeters. Disclaimer: While TE and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this document, TE cannot assure that this information is error free. For this reason, TE does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. TE reserves the right to make any adjustments to the information at any time. TE expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. TE`s only obligations are those stated in TE's Standard Terms and Conditions of Sale. TE will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgment to evaluate the suitability of a product for a certain purpose and test each product for its intended application. In case of any potential ambiguities or questions, please don't hesitate to contact us for clarification. 12-2014, Rev. 1214 www.te.com (c) 2014 Tyco Electronics Corporation, a TE Connectivity Ltd. company Datasheets and product specification according to IEC 61810-1 and to be used only together with the `Definitions' section. Datasheets and product data is subject to the terms of the disclaimer and all chapters of the `Definitions' section, available at http://relays.te.com/definitions Datasheets, product data, `Definitions' section, application notes and all specifications are subject to change. 7 Mouser Electronics Authorized Distributor Click to View Pricing, Inventory, Delivery & Lifecycle Information: TE Connectivity: W91-X152-15