https://www.phoenixcontact.com/us/products/2803506
09/10/2014Page2/4
Type 2 surge protection plug-VAL-MS 350/20 ST-2803506
Technical data
General
Surge protection fault message Optical
Direction of action 1L-N/PE
Protective circuit
IEC test classification II
T2
EN type T2
Nominal voltage UN240 V AC
Maximum continuous operating voltage UC350 V AC
UT (TOV-proof) 415 V AC (5 s)
Nominal frequency fN50 Hz (60 Hz)
Residual current IPE ≤ 340 µA
Standby power consumption PC≤ 120 mVA
Max. discharge current Imax (8/20) µs 20 kA
Nominal discharge current In (8/20) µs 10 kA
Voltage protection level Up≤ 1.4 kV
Residual voltage ≤ 1.4 kV (at In)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 3 kA)
Response time ≤ 25 ns
Max. backup fuse with branch wiring 125 A (gL / gG)
Short-circuit resistance IP with max. backup fuse (effective) 25 kA
Connection, protective circuit
Connection method FLASHTRAB/VALVETRAB plug-in system connector
Standards and Regulations
Standards/regulations IEC 61643-1 2005
EN 61643-11/A11 2007
Classifications
eCl@ss
eCl@ss 4.0 27140201
eCl@ss 4.1 27130801
eCl@ss 5.0 27130801
eCl@ss 5.1 27130801
eCl@ss 6.0 27130805