I IA CE
SIPLUS RIC IEC on S7
Interoperability list IEC 60870-5-103 Master
V1.5
Interoperability list IEC 60870-5-103 I IA CE
SIPLUS RIC IEC on S7 V1.5 Page 2 of 5 ©SIEMENS AG 2013
Contents
1. Physical Layer ...................................................................................................................................3
2. Application Layer ..............................................................................................................................4
3. Protection devices ............................................................................................................................5
Copyrigh 2013 All rights reserved
The forwarding and reproduction of this document, and the
reuse and distribution of its content is not permitted, unless
explicit permission has been granted. Damages will be sought
in all cases of infringement. All rights reserved, in particular in
the event of patents being granted or a utility model being
registered.
Siemens AG
I IA CE
P.O. Box 23 55
90713 Fürth
Germany
Disclaimer
We have checked the content of this printed document in
accordance with the hardware and software described.
Nevertheless, the risk of deviations cannot be excluded
completely, which is why we do not accept liability for
complete conformity. The details provided in this printed
document are checked on a regular basis, however, and any
corrections necessary are included in subsequent editions.
We would be happy to receive your suggestions for
improvement.
Technical data subject to change.
Interoperability list IEC 60870-5-103 I IA CE
SIPLUS RIC IEC on S7 V1.5 Page 3 of 5 ©SIEMENS AG 2013
IEC60870-5-103
This documentation is used to match the functionality required/demanded for communication with
SIMATIC S7-300, SIMATIC S7-400 or SIMATIC ET200S devices based on telecommunication standard
IEC 60870-5-103.
General information
Legend:
Not implemented
Implemented
1. Physical Layer
(network specific parameter; all implemented configurations are marked with ‚X’)
Electrical Interface RS-485
Optical Interface*
*) The optical interface can be realized by external media converter.
Transmission speed
Same transmission speed for control direction and monitoring direction.
Asymmetrical interface
RS485/RS422
9600 bits/s
19200 bits/s
The available transmission rates depend on the used CP and interface module.
X
X
X
X
Interoperability list IEC 60870-5-103 I IA CE
SIPLUS RIC IEC on S7 V1.5 Page 4 of 5 ©SIEMENS AG 2013
2. Application Layer
ASDUs in monitoring direction
Type-ID
<1> := Time tagged message
<2> := Time-tagged message with relative time
<3> := Measurands I
<4> := Time-tagged measurands with relative time
<5> := Identification message
<6> := Time synchronization
<8> := Termination of general interrogation
<9> := Measurands II
<10> := Generic Data
<11> := Generic identification
<23> := List of recorded disturbances
<26> := Ready for transmission of disturbance data
<27> := Ready for transmission of a channel
<28> := Ready for transmission of tags
<29> := Transmission of tags
<30> := Transmission of disturbance values
<31> := End of Transmission
ASDUs in control direction
Type-ID
<6> := Time synchronization
<7> := Initiation of general interrogation
<10> := Generic data
<20> := General Command
<21> := Generic Command
<24> := Order for disturbance data transmission
<25> := Acknowledgement for disturbance data transmission
Basic application functions
Test mode
Blocking of monitoring direction
Disturbance data
Generic services
Private data (only Type-ID 140, Measurands SIMEAS T)
X
X
X
X
X
X
X
X
X
X
X
X
Interoperability list IEC 60870-5-103 I IA CE
SIPLUS RIC IEC on S7 V1.5 Page 5 of 5 ©SIEMENS AG 2013
3. Protection devices
- Distance Protection (function type 128)
- Over current protection (function type 160)
- Transformer differential protection (function type 176)
- Linie differential protection (function type 192)
Private defined information with respect to chapter 2 can be supported.
Every information is parameterized individually.
A catalogue with pre defined information is not planned.
X
X
X
X