Product data sheet
Characteristics
RE22R2CMR
Modular timing relay, 8 A, 2 CO, 0.05 s...300 h, off
delay, 24...240 V AC/DC
Main
Range of product Zelio Time
Product or component type Modular timing relay
Discrete output type Relay
Device short name RE22
Nominal output current 8A
Complementary
Contacts type and composition 1 C/O timed or instantaneous contact, cadmium free
2 C/O timed contact, cadmium free
Time delay type C
Time delay range 10...100 s
3...30 h
1...10 s
3...30 s
30...300 h
0.3...3 s
0.05...1 s
30...300 min
30...300 s
3...30 min
Control type Rotary knob
Diagnostic button
[Us] rated supply voltage 24...240 V AC/DC 50/60 Hz
Release input voltage <= 2.4 V
Voltage range 0.85...1.1 Us
Supply frequency 50...60 Hz +/- 5 %
Connections - terminals Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end
Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end
Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
24/02/2021
1
Tightening torque 0.6…1N.m conforming to IEC 60947-1
Housing material Self-extinguishing
Repeat accuracy +/- 0.5 % conforming to IEC 61812-1
Temperature drift +/- 0.05 %/°C
Voltage drift +/- 0.2 %/V
Setting accuracy of time delay +/- 10 % of full scale at 25 °C conforming to IEC 61812-1
Control signal pulse width 100ms with load in parallel
30ms
Insulation resistance 100 MOhm at 500V DC conforming to IEC 60664-1
Recovery time 120ms on de-energisation
Immunity to microbreaks 10ms
Power consumption in VA 3VA at 240 V AC
Power consumption in W 1.5W at 240 V DC
Switching capacity in VA 2000VA
Minimum switching current 10mA at 5 V DC
Maximum switching current 8A
Maximum switching voltage 250V AC
Electrical durability 100000cycles, 8A at 250 V, AC-1
100000cycles, 2A at 24 V, DC-1
Mechanical durability 10000000cycles
Rated impulse withstand voltage 5kV for 1.2…50µs conforming to IEC 60664-1
Power on delay 100ms
Creepage distance 4 kV/3 conforming to IEC 60664-1
Overvoltage category III conforming to IEC 60664-1
Safety reliability data MTTFd = 251.1 years
B10d = 230000
Mounting position Any position
Mounting support 35 mm DIN rail conforming to EN/IEC 60715
Status LED LED backlight green (steady) for dial pointer indication
LED yellow (steady) for output relay energised
LED yellow (fast flashing) for timing in progress and output relay de-energised
LED yellow (slow flashing) for timing in progress and output relay energised
Width 22.5mm
Net weight 0.105kg
Environment
Dielectric strength 2.5kV for 1 mA/1 minute at 50 Hz between relay output and power supply with basic insulation
conforming to IEC 61812-1
Standards UL 508
IEC 61812-1
Directives 2006/95/EC - low voltage directive
2004/108/EC - electromagnetic compatibility
Product certifications CSA
CCC
RCM
CE
GL
UL
EAC
Ambient air temperature for operation -20…60°C
Ambient air temperature for storage -40…70°C
IP degree of protection IP40 housing: conforming to IEC 60529
IP20 terminals: conforming to IEC 60529
IP50 front panel: conforming to IEC 60529
Pollution degree 3 conforming to IEC 60664-1
Vibration resistance 20 m/s² (f= 10…150Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn not operating for 11ms conforming to IEC 60068-2-27
5 gn in operation for 11ms conforming to IEC 60068-2-27
2
Relative humidity 95% at 25…55°C
Electromagnetic compatibility Fast transients immunity test - test level: 1 kV level 3 (capacitive connecting clip) conforming to IEC
61000-4-4
Surge immunity test - test level: 1 kV level 3 (differential mode) conforming to IEC 61000-4-5
Surge immunity test - test level: 2 kV level 3 (common mode) conforming to IEC 61000-4-5
Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2
Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 (80 MHz...1
GHz) conforming to IEC 61000-4-3
Conducted RF disturbances - test level: 10 V level 3 (0.15...80 MHz) conforming to IEC 61000-4-6
Fast transient bursts - test level: 2 kV level 3 (direct contact) conforming to IEC 61000-4-4
Immunity to microbreaks and voltage drops - test level: 30 % (500 ms) conforming to IEC 61000-4-11
Immunity to microbreaks and voltage drops - test level: 100 % (20 ms) conforming to IEC 61000-4-11
Packing Units
Package 1 Weight 0.108kg
Package 1 Height 0.260dm
Package 1 width 0.820dm
Package 1 Length 0.950dm
Offer Sustainability
Sustainable offer status Green Premium product
REACh Regulation REACh Declaration
EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope)
EU RoHS Declaration
Mercury free Yes
RoHS exemption information Yes
China RoHS Regulation China RoHS declaration
Environmental Disclosure Product Environmental Profile
Circularity Profile End of Life Information
3
Product data sheet
Dimensions Drawings
RE22R2CMR
Dimensions
4
Product data sheet
Connections and Schema
RE22R2CMR
Wiring Diagram
5
Product data sheet
Technical Description
RE22R2CMR
Function C: Off-Delay Relay with Control Signal
Description
After energisation of power supply and energization of Y1 causes output(s) R close(s). When Y1 deenergizes, timing T starts.At the end of
this timing period T,the output(s) R revert(s) to its/their initial position.The second output (R2) can be either timed (when set to "TIMED") or
instantaneous (when set to "INST").
Function: 1 Output
Function: 2 Outputs
Legend
Relay de-energised
Relay energised
Output open
Output closed
U - Supply
T - Timing period
R1/R2 - 2 timed outputs
R2 inst. - The second output is instantaneous if the right position is selected
Y1 - Retrigger / Restart control
6