1
CSM_G3F_G3FD_DS_E_5_1
Solid State Relays G3@-VD
G3F/G3FD
International Standards for G3F Series,
Same Profile as MY Power Relays
Shape-compatible with mechanical relays.
Certified by UL, CSA, and VDE (model numbers with a suffix of
“-VD”).
Socket type, same size as MY Power Relays.
Operation indicator provided to confirm input (model numbers
with “N” before the suffix).
Refer to Safety Precautions on page 6.
Note: The socket is optional.
For the most recent information on models that have been certified for
safety standards, refer to your OMRON website.
Model Number Structure
Model Number Legend
1. Basic Model Name
G3F: Solid State Relay
2. Rated Load Power Supply Voltage
2: 200 VAC
3. Rated Load Current
02: 2 A
03: 3 A
4. Terminal Type
S: Plug-in terminals
5. Zero Cross Function
Blank: Equipped with zero cross functions
L: Not equipped with zero cross function
6. Operation Indicator
Blank: Not equipped with operation indicator
N: Equipped with operation indicator
7. Certification
VD: Certified by UL, CSA, and VDE
1. Basic Model Name
G3F: Solid State Relay
2. Load Power Supply Type
D: DC
3. Rated Load Power Supply Voltage
X: 50 VDC
1: 100 VDC
4. Rated Load Current
02: 2 A
03: 3 A
5. Terminal Type
S: Plug-in terminals
6. Operation Indicator
Blank: Not equipped with operation indicator
N: Equipped with operation indicator
7. Certification
VD: Certified by UL, CSA, and VDE
1234 5 6 7
G3F-@@@@@-@
1234 5 6 7
G3FD-@@@@-@
G3F/G3FD
2
Ordering Information
List of Models
Note: 1. Product is labelled “240 VAC”.
2. Product is labelled “48 VDC”.
3. When ordering, specify the rated input voltage.
Accessories (Order Separately)
Connecting Sockets/Hold-Down Clips
Isolation Zero cross
function
Indicator Rated output load Rated input voltage Model
Photocoupler Yes Yes 3 A at 100 to 240 VAC (See note 1.) 5 to 24 VDC G3F-203SN-VD
2 A at 100 to 240 VAC (See note 1.) 100/110 VAC G3F-202SN-VD
200/220 VAC
Phototriac coupler No 3 A at 100 to 240 VAC (See note 1.) 5 VDC G3F-203SLN-VD
12 VDC
24 VDC
Photocoupler 3 A at 4 to 48 VDC (See note 2.) 5 to 24 VDC G3FD-X03SN-VD
2 A at 5 to 110 VDC 100/110 VAC G3FD-102SN-VD
200/220 VAC
5 to 24 VDC
Photocoupler Yes No 3 A at 100 to 240 VAC (See note 1.) 4 to 24 VDC G3F-203S-VD
Phototriac coupler No 5 VDC G3F-203SL-VD
12 VDC
24 VDC
Photocoupler 3 A at 4 to 48 VDC (See note 2.) 4 to 24 VDC G3FD-X03S-VD
2 A at 5 to 110 VDC G3FD-102S-VD
Front-mounting Sockets Back-mounting Sockets
Socket PYF08A(-E) PYF08M PY08-02 PY08(QN)
Hold-down Clip PYC-A1 PYC
PYC-P
PYC-P PYC-P
PYC-S
G3F/G3FD
3
Specifications
Ratings (at an Ambient Temperature of 25C)
Input
Note: 1. The input impedance is given for the maximum operating range. For details, refer to the Technical Guide for Solid State Relays.
2. Constant-current input circuit.
Output
Model Rated voltage Operating voltage Impedance Voltage level
Must operate voltage Must release voltage
G3F-203SN-VD 5 to 24 VDC 4 to 28 VDC 15 mA max. (See note.) 4 VDC max. 1 VDC min.
G3F-202SN-VD 100/110 VAC 75 to 125 VAC 41 k20% 75 VAC max. 20 VAC min.
200/220 VAC 150 to 250 VAC 72 k20% 150 VAC max. 40 VAC min.
G3F-203SLN-VD 5 VDC 4 to 6 VDC 390 20% 4 VDC max. 1 VDC min.
12 VDC 9.6 to 14.4 VDC 900 20% 9.6 VDC max.
24 VDC 19.2 to 28.8 VDC 2 k20% 19.2 VDC max.
G3FD-X03SN-VD 5 to 24 VDC 4 to 28 VDC 1.5 k+20%/–10% 4 VDC max.
G3FD-102SN-VD 5 to 24 VDC 4 to 28 VDC 1.5 k+20%/–10% 4 VDC max.
100/110 VAC 75 to 125 VAC 41 k20% 75 VAC max. 20 VAC min.
200/220 VAC 150 to 250 VAC 72 k20% 150 VAC max. 40 VAC min.
G3F-203S-VD 4 to 24 VDC 3 to 28 VDC 15 mA max. (See note.) 3 VDC max. 1 VDC min.
G3F-203SL-VD 5 VDC 4 to 6 VDC 390 20% 4 VDC max.
12 VDC 9.6 to 14.4 VDC 900 20% 9.6 VDC max.
24 VDC 19.2 to 28.8 VDC 2 k20% 19.2 VDC max.
G3FD-X03S-VD 4 to 24 VDC 3 to 28 VDC 1.5 k+20%/–10% 3 VDC max.
G3FD-102S-VD
Model Rated load
voltage
Applicable load
Load voltage range Load current Inrush current
G3F-203SN-VD
G3F-203SLN-VD
G3F-203S-VD
G3F-203SL-VD
100 to 240 VAC 75 to 264 VAC 0.1 to 3 A at 40C 45 A (60 Hz, 1 cycle)
G3F-203SN-VD 100 to 240 VAC 75 to 264 VAC 0.1 to 2 A at 40C 45 A (60 Hz, 1 cycle)
G3FD-X03SN-VD
G3FD-X03S-VD
4 to 48 VDC 3 to 52.8 VDC 0.1 to 3 A at 40C 18 A (10 ms)
G3FD-102SN-VD
G3FD-102S-VD
5 to 110 VDC 3 to 125 VDC 0.1 to 2 A at 40C 10 A (10 ms)
G3F/G3FD
4
Characteristics
Item G3F-203SN-VD
G3F-202SN-VD
G3F-203S-VD
G3F-203SLN-VD
G3F-203SL-VD
G3FD-X03SN-VD
G3FD-X03S-VD
G3FD-102SN-VD G3FD-102S-VD
Operate time 1/2 of load power
source cycle + 1 ms
max. (DC input)
3/2 of load power
source cycle + 1 ms
max. (AC input)
1 ms max. 0.5 ms max. 0.5 ms max. (DC input)
20 ms max. (AC input)
0.5 ms max.
Release time 1/2 of load power
source cycle + 1 ms
max. (DC input)
3/2 of load power
source cycle + 1 ms
max. (AC input)
1/2 of load power
source cycle + 1 ms
max.
2 ms max. 2.5 ms max. (DC input)
20 ms max. (AC input)
2.5 ms max.
Output ON voltage drop 1.6 V (RMS) max. 1.5 V max.
Leakage current 5 mA max.
(at 100 VAC)
10 mA max.
(at 200 VAC)
2.5 mA max.
(at 100 VAC)
5 mA max.
(at 200 VAC)
5 mA max.
(at 50 VDC)
0.1 mA max.
(at 100 VDC)
0.1 mA max.
(at 100 VDC)
Insulation resistance 100 M min. (at 500 VDC)
Dielectric strength 2,000 VAC, 50/60 Hz for 1 min 1,500 VAC, 50/60 Hz for 1 min
Vibration resistance Destruction: 10 to 55 to 10 Hz, 0.75-mm single amplitude
Shock resistance Destruction: 1,000 m/s2
Ambient temperature Operating: –30C to 80C (with no icing or condensation)
Storage: –30C to 100C (with no icing or condensation)
Ambient humidity Operating: 45% to 85%
Certified standards G3F: UL508, CSA C22.2 No. 14, EN60947-4-3
G3FD: UL508, CSA C22.2 No. 14, EN60950-1
EMC Emission: EN55011 Group 1 Class B
Immunity: EN61000-6-2
Weight Approx. 50 g
G3F/G3FD
5
Engineering Data
Load Current vs. Ambient Temperature Characteristics
One Cycle Surge Current: Non-repetitive
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Ambient temperature (°C) Ambient temperature (°C)
Load current (A)
Load current (A)
G3F-203SN-VD/203S-VD/203SLN-VD/
203SL-VD
G3FD-X03SN-VD/X03S-VD
G3F-202SN-VD
G3FD-102SN-VD/102S-VD
2010
Non-repetitive (Keep the inrush current to half the rated value if it occurs repetitively.)
G3FD-X03SN-VD/X03S-VD G3FD-102SN-VD/102S-VD
Inrush current (A. Peak)
Energized time (ms)
Inrush current (A. Peak)
Energized time (ms)
Inrush current (A. Peak)
Energized time (ms)
G3F-203SN-VD/203S-VD/202SN-VD/
203SLN-VD/203SL-VD
1
5
9
13
4
8(+)
12()
14
+
+
(+)
()
( )
Load
Input
Load
Input voltage
28 max.
21.5 max. 36.5 max.
42.5 max.
Terminal Arrangement/
Internal Connections
Load power
supply
Note: The plus and minus symbols shown
in parentheses are for DC loads.
The load is possible to connect
either + side or - side.
G3F/G3FD
6
Safety Precautions
Refer to Safety Precautions for All Solid State Relays.
Precautions for Correct Use
Please observe the following precautions to prevent failure to
operate, malfunction, or undesirable effect on product performance.
Connection
The SSR for DC switching use can connect to a load regardless of
the polarity of the positive and negative output terminals.
Close Mounting of Multiple Relays
If multiple Relays are mounted side by side, be aware that the outer
wall of each SSR works as a heat sink.
The SSR casing serves to dissipate heat. Install the Relays so that
they are adequately ventilated. If poor ventilation is unavoidable,
reduce the load current by half.
Protective Terminal
When using for AC inductive loads, connect the load terminals of the
SSR to an inrush absorber (varistor).
EMC Directive Compliance
1. AC-switching models comply with EMC Directives under the
following conditions ("-VD" models only).
2. DC-switching models comply with EMC Directives under the
following conditions ("-VD" models only).
Varistor
Varistor: 470 V, 0.6 W
Film capacitor: 1 µF, 250 VAC
OutputInputG3F-VD
Load
Less than 3 m
Connect a varistor between the output terminals.
Connect a film capacitor to the load power supply.
The input cable must be less than 3 m.
Film Capacitor
OutputInputG3FD-VD
Load
Less than 10 m
The input cable must be less than 10 m.
In the interest of product improvement, specifications are subject to change without notice.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Omron:
G3F-203SN DC5-24 G3FD-X03SN-DC5-24 G3F-202SN AC100/110 G3F-203S-DC3-28 G3F-203SLN DC24 G3FD-
102SN AC100/110 G3FD-X03S-DC3-28 G3FD-102-SN-DC5-24 G3FD-102SN-VD DC5-24 G3FD-X03SN-VD DC5-24
G3F-203SL DC24 G3FD-102SN AC200/220 G3FD-102SN-DC5-24 G3FD-X03S-VD DC4-24 G3FD-102SN-VD
AC100/110 G3F-202SN-VD AC100/110 G3F-203SN-VDDC5-24