SPECIFICATIONS
Current Ratings 0.1 to 16 amps, standard ratings available
Voltage Ratings 240 VAC, 50/60 Hz, 50 VDC, 24 VDC (VDE)
Max Breaking Capacity 8x In for < 6A, 60A max. > 6A
Conditional Short Circuit Capacity 1KA, PC1, 240Vac 24Vdc
ref: EN60934, SC: 1KA, C1 240Vac 50Vdc
ref: CSA22.2 No. 235.04, UL-1077
Tripping Current Code (TC) TC2 ref: CSA22.2, No. 234-04
Insulation Resistance Min 100 MΩ @ 500VDC
Dielectric Strength 1,500 VAC for 1 min.
Operational Life 1000 Cycles @ 2 x In
Overload Rating OL0 240Vac, 50Vdc, ref: CSA22.2, No. 235-04
Overload Switching Capacity 6x In AC Up to 9A, 4x In DC Up to 12A
60A Max. from 10A to 12A
Max Operating Temperature 60°C (140°F) Ambient
Application Type General Industrial ref: CSA22.2, No. 235-04
Method of Tripping Thermal “TO”, trip-free
Type of Actuation Reset type “R”
FEATURES
• Protectionrangeandoperatingvoltage:
0.1 to 16.0 Amps, 240 VAC, 50 VDC (cЯUus,cCSAus)
0.5 to 12 Amps, 240 VAC, 24 VDC (VDE)
• RoHScompliant,singlepole,thermalcurrentoverloadprotector
• Reliable,trip-freeoperationoncurrentoverloads
•Warranty:24-monthsfromdateofmanufacture
DESCRIPTION
The Airpax™ ATR11 product family is a single pole, thermally operated overload protector with a snap-acting trip mechanism that
provides reliable, trip-free operation on current overloads. The ATR11 series is designed with multiple mounting configurations
including central nut, wing clip, snap-in, integral and PC board mounting.
ATR11 Series
Thermal Circuit Protector for Equipment
http://airpax.sensata.com/
ATR11 Series
302
ADDITIONAL PRODUCTS
SHUNT TERMINAL (Option N)
Available on units of up to 6 amps equipped with a heater winding, an optional additional terminal can be provided as a parallel circuit
to the main current-sensing circuit. The shunt circuit between terminals 1 and 3 may be used for any signal that may be required in
addition to the main circuit. However, since the circuit makes use of the bimetal strip as a current-carrying path, the trip time of the
circuit protector may be slightly influenced.
http://airpax.sensata.com/ ATR11 Series 303
(min) 60
30
20
10
5
1
(S) 50
20
10
5
2
1
0.5
0.2
0.1
Trip-Time
1.05 1.32 2 3 4 5 8 10
Multiple of Current Rating
Rated Current
Ambient
Temperature
< 6A
³ 6A
23°C
(x I )
n
Example :
Normal Continuous Current = 1.8 A
Ambient Temperature = 40°C
Multiplication Factor = 1.12 (from graph)
Recommended Rating: 1.8 x 1.12 = 2.016
Select the Nearest Rating = 2 amps
TIME / CURRENT CHARACTERISTICS
The standard characteristic is valid for an ambient temperature of 23°C. However, if the device is to be used in an ambient temperature
other than 23°C, an allowance must be made when selecting the current rating.
See the chart, graph and example below to help determine the right circuit protector rating for your application.
AMBIENT TEMPERATURE CORRECTION FACTOR
Ambient Temperature (°C) - 20 - 5 0 + 10 + 20 + 30 + 40 + 50 + 60
Multiplication Factor 0.8 0.88 0.9 0.96 1 1.05 1.12 1.2 1.3
Operating Characteristics :
http://airpax.sensata.com/
ATR11 Series
304
MOUNTING OPTIONS, inches [mm]
ATR11.....
LINE
LINE
ATR11.....
Printing / Label
LINE
ATR11.....ATR11.....
LINE
PRESS
RESET
Printing / Label
Printing / Label
Printing / Label
Printing / Label
Printing / Label
12
DIAGRAM
R
R R
R
.737
18.7
`D1' TYPE
RESET
PRESS
.500
12.7
.650
16.5
1
2
.249
6.3
.249
6.3
.249
6.3
.249
6.3 .249
6.3
RESET CONDITION
terminal
Shunt
.158
4
RESET CONDITION
DRILLING
Ø
.862
.866
.870
.878
.890
`X'
DIMENSION
THICKNESS
PANEL
.118
.079
.059
.039
.032
PANEL CUTOUT
X
.591
15
.855
21.7
.512
13
.032
0.8
.433
11
.552
14
.500
12.7 .599
15.2
`W ' TYPE
`D' TYPE
RESET
PRESS
(For panel of thickness 1 to 3mm)
TERMINAL 1, 2 & 3 'N' TYPE
TERMINAL 2&3 'Y' TYPE
TERMINAL 1&2 'X' TYPE
12
3
32
.032
0.8
.032
0.8
.512
13
DOUBLE `D'
PANEL CUTOUTPANEL CUTOUT
SINGLE `D'
`D' & `D1' TYPE `W' TYPE
.433
11
.158
4
.157
4
.433
11
M10X1
.394
10 .354
9
Maximum Torque
4 inch-pounds
PANEL CUTOUT
.354
9.5
.571
14.5 .472
12
1.084
27.5
.236
6
.118
3
.276
7
.594
15
1.734
44 .402
10.2
.370
9.4
-.004
.611
15.5
.611
15.5
.587
14.9
.532
13.5
.623
15.8
.587
14.9
.623
15.8 .532
13.5
.500
12.7
.650
16.5
.985
25
.548
13.9
+.004
-.004
.626
15.9
-.004
.630
16.0
+.004
.591
15.0
+.004
.276
7
.394
10 .354
9 .473
12
.118
3
.473
12
.571
14.5
1.734
44
1.084
27.5
.594
15
.374
9.5
.374
9.5
.079
2
.335
8.5
.441
11.2
.473
12
.512
13 1.655
42
.276
7
.445
11.3
+.004
+.004
.051
1.3
1.182
30
.296
7.5
.690
17.5
.355
9 .394
10
.335
8.5
.441
11.2
1.084
27.5
.276
7
.032
0.8
.591
15
.158
4
.433
11 .039
1
TINNED
.189
4.8
.197
5
1.734
44
.079
11.2
.335
8.5
.276
7
.355
9
.394
10
.749
19
.591
15
.249
6.3
1.084
27.5
.032
0.8
.249
6.3
.374
9.5
.433
11
.158
4
Central Mounting (C)
WingClips(W) WingClipsTypes
Snap Fitting (S)
Body Mounting (B) PCB Mounting (P)
First Decision
Type
1
Second Decision
2
Mounting
Third Decision
3
Terminal Format
X
Y
N
Fourth Decision
4
Eighth Decision
8
Standard Current Ratings*
0.1, 0.25, 0.5, 0.8, 0.9, 1.0, 1.2, 1.5, 1.8, 2.0, 2.2, 2.5, 2.7,
3.0, 3.3, 4.0, 5.0, 6.0, 6.5, 7.0, 8.0, 9.0, 10.0, 12.0, 15.0, 16.0
*For other ratings, please consult the factory.
12 3 4 5
ATR1 1 - C - X - 63 - R - 1 - A - 7.0A
63
48
28
10
.250 Q.C.
.187 Q.C.
.110 Q.C.
PCB, .040 solder
Terminal 1 & 2
Terminal 2 & 3
Shunt Terminal
Terminal
8
6
Sixth Decision
6
Button Marking*
0
1
2
No Marking
Vertical
Horizontal
7
*D & D1 Mounting are
supplied with -2 marking
Single pole, series, thermal circuit protector
ATR11
C
W
D
D1
S
B
P
Central hex nut
Wing clip
Wing clip
Wing clip
Snap-in
Integral
PCB
Fifth Decision
5
Reset Button
R
B
W
RB
BB
WB
Red
Black
White
Red w/trip band
Black w/trip band
White w/trip band
Seventh Decision
7
Mounting Nut
N
A
B
C
D
None
Knurled Metal
Slotted Knurled Metal
Hex Metal
Knurled Sealing Boot
Note: Terminals 1 & 2 are standard for current ratings 12A
Terminals 2 & 3 are standard for current ratings > 12A
Terminals 1, 2 & 3 are optional for current ratings 6A
ADDITIONAL PRODUCTS
http://airpax.sensata.com/ ATR11 Series 305
M10x1
SEALING KNURLED BOOT
P/N 053-000-0001
Positions
Cutouts
Panel
M10x1
TRIPED CONDITIONTRIPED CONDITION WB
BB
WHITE SLIDER
BLACK TRIP BANDWHITE TRIP BAND
BLACK SLIDER
A sealing boot for central mounting
Type (C) Circuit breaker to provide
dust &splash protection (IP 54).
KNURLED NUT
P/N 053-000-0002
2.5
2.5
Panel
Cutouts
Positions
HORIZONTAL
VERTICAL
RB
TRIPED CONDITION
RED SLIDER
WHITE TRIP BAND
.630
16
.079
2
.709
18
.099
2.5
.512
13
ADDITIONAL OPTIONS
Button Marking for Current Rating Button Color with Trip Band
Accesories
DECISION TABLES