Input Voltage: 85-132/180-264 VAC, 47-63 Hz, 1 phase
Input Current: <3.2A RMS @ 115 VAC @ full load
<1.6A RMS @ 230 VAC @ full load
Inrush Current: <25A, pk @ 132 VAC @ cold start
<50A, pk @ 265 VAC @ cold start
Power Factor: Meets Class A requirements
Harmonic Distortion: Meets EN61000-3-2 for Class A
EMI Filtering: Meets CISPR 11 and 22 and FCC Part 15
Class B (conducted)
Input Protection: Internal AC line fuse; 250 VAC, 6.3A
Surge Withstand: Meets EN61000-4-5 Level 3
Output Power: 150W with 15CFM air; 80W Convection
Line Regulation: ± 0.3%
Load Regulation: ± 0.5%
PARD: <1% or 50mV;
20MHz bandwidth
Hold-up Time: 20 ms @ full load (120 VAC)
Output Polarity: Output is floating
Minimum Load: 0% of rated load
Transient Response: 3% for 25% load change @ 1A/µs;
50% duty cycle 50/60 Hz
Output Rise Time: <100 ms (10% to 90%)
Current Limit: 105-130% of rated current; Hiccup
Remote Sense: Compensates for up to 250mV of total cable
drop
Remote On/Off: Optional
Leakage Current: < 300 μA
Thermal Shutdown Standard
DC OK: Standard; Open Collector
Turn-on Delay: <1 second after application of AC Input
Stability: <0.1% for 8 hours
after 1/2-hour warm up
Isolation: >20 MΩ @ 100 VDC between output
terminals and chassis ground
AC Power Fail: TTLLOW logic “0” at least 2 ms before
output drops 5%; Open Collector
Overvoltage Protect: Factory set, 125% ±5%,
cycle AC to reset
Reverse Voltage: Output has reverse voltage protection;
Reverse current limited to 100% of output
rating
Efficiency: Up to 85%
MTBF: MIL-STD-HDBK 217E
>200,000 hours @ 25°C
Highly Accelerated Life Testing
Electrical Specifications
Continuous
Voltage Voltages Current
Codes (Volts) (Amps)
-2 3.3 30
-3 5.0 30
-4 12.0 12.5
-5 15.0 10.5
-6 24.0 6.5
-7 28.0 5.5
-8 36.0 4.5
-9 48.0 3.5
* Consult factory for other voltages and OEM quantities.
Note: Standard models are shown bold
Available Voltage Outputs*
PAM150
Model
150 Wattsmax output power
Power Factor Correction
Single Output
Switch Mode Power Supply
H.A.L.T.
TESTED
Highly
Accelerated
Life
Testing
Medical Grade
Certifications
PART # STRUCTURE:
MODEL - VOLTAGE CODE - OPTION CODES (See back)
- V1 -
PAM150 - X - ABC....
Example: Part Number PAM150-6-CK= 150W Power Factor Corrected, 24V @ 6.5A with a fan assembly and a Molex connector.
CLICK HERE TO SEE THE PAM150 CODE TABLE AND AVAILABLE OPTIONS.
Physical Specifications
Dimensions: (HxWxL) 1.5" x 4.0" x 6"
Operating Temp: 0 to 70°C; rated power to 50°C
derate linearly to 50% at 70°C.
Relative Humidity: 5% to 90%, non-condensing
Storage: -50 to 85°C/20-90% RH
Altitude: 6531
40,000' storage
Options (code)
12V@0.5A Aux./Fan Drive (A) Droop Current Share ±10% (B)
Fan Assembly (C) DC OK Invert (E)
PF Invert (F) Field-Configurable (G)
Single Wire Current Share ±5% (I) Square Current Limit (J)
Molex Connector (K) Metric Mounting (M)
OR-ing Diode (O) Remote On/Off (R)
Remote On/Off Invert (S)
Model
Certifications
NRTL* * * Recognition to UL60601-1
CSA C22.2 No. 601.1
BAUART Certification to EN60601-1
CB Test Report in Accordance with IEC60601-1
CE Declaration to Low Voltage Directive 2006/95/EC
* * * Nationaly Recognized Test Laboratory
Compliance
EN61000-4-5 Level 3 EN61000-4-2 Level 2
EN61000-3-2 for Class A EN61000-4-2 Level 3 (Air Only)
EN61000-4-4 Level 3 EN61000-4-11
CISPR 11 and 22 FCC Part 15 Class B (conducted)
FM 32227
© Copyright 2011 TAMURA CORPORATION OF AMERICA. Specifications subject to change without notice.
TAMURA CORPORATION OF AMERICA
1040 South Andreasen Drive, STE. 100 Escondido, CA 92029-1951
(951) 699-1270 / Fax: (951) 676-9482
(800) 472-6624
www.tamuracorp.com
PAM150