GAMMA instabus
Technical Product Information
May 2008
AP 251/11, Motion detector IP55 (titanium white) 5WG1 251-3AB11
AP 251/21, Motion detector IP55 (anthracite) 5WG1 251-3AB21
Siemens AG AP 251/_1, 4 pages Technical Manual
Industry Sector, Building Technologies
Electrical Installation Technology © Siemens AG 2008 Update: http://www.siemens.com/gamma
P.O.Box 10 09 53, D-93009 Regensburg Subject to change without prior notice
2.13.1.5/1
Product and Applications Description
The IP55 motion detector (short title AP 251/_1) is a
surface mounted device with integrated KNX interface
for mounting on a wall or ceiling (see figure 1) in inside
or outside areas. It works by passive detection of heat
radiated by bodies in its capture zone. It can be set sepa-
rately for the beginning and end of detected movements,
whether these are to be reported over the bus and
whether a further telegram is also to be sent. Owing to
its large capture zone of 290°, the motion sensor is also
suitable for mounting on a 90° outside corner. A special
mounting base is available for this purpose as an acces-
sory (5TC7 900 in titanium white and 5TC 901 in anthra-
cite).
By using an infrared remote control which is also avail-
able as an accessory (5TC7 902), a user can conveniently
set, by means of the IR receiver incorporated in the mo-
tion detector, as well the detector's mode (test mode,
brightness-dependent or brightness-independent mode,
standard mode, pulsed mode) as the brightness thresh-
old and the delay time, independently.
The factory setting of the mode in the as-delivered state
is brightness-dependent motion detection with a bright-
ness threshold of 7 lux and a delay time of 2 minutes.
The detector electronics are powered via the bus voltage.
Application Program
The motion detector AP 251/_1 requires the application
program „25 S1 Motion Detector 909101“ which can be
configured and loaded with the Engineering Tool Soft-
ware (ETS) from version ETS2 V1.3 upwards.
Via the ETS it can be set separately for the beginning and
end of detected movements, whether these are to be
reported over the bus, whether the telegram “Movement
= On” respectively “Movement = Off” has to be sent only
once or cyclically and whether an additional telegram is
to be sent only once or cyclically. The telegram to be sent
additionally may be a switching command On/Off, an 8-
bit value (0-255) or a telegram for recalling an 8-bit
scene.
Via a separate communication object the motion detec-
tor may be blocked and released if required. If it is
blocked no telegram will be sent neither at the beginning
nor at the end of a detected motion.
Installation Instructions
The device can be used for permanent installations in
inside or outside areas.
V WARNING
The device must be mounted and commissioned by an
authorised electrician.
For planning and construction of electric installations,
the relevant guidelines, regulations and standards of
the respective country are to be considered.
Technical Specifications
Sensor
Capture zone: 290°
Mounting height: 2 – 4 m, ideally 2.50 m
Range (mounting height 2.50 m, +22°C): approx. 16 m
Dawn/twilight sensor: 0.5 - 2000 lux
Delay time 5 seconds - 30 minutes
Pulse mode 1 second ON, 9 seconds OFF
Test mode: Brightness-independent mode,
after-run time 2 seconds
Power supply
Bus voltage: via bus line
Bus current: 11 mA
Operating elements
1 commissioning button (see figure 1): for switching
over between normal mode / addressing mode
2 buttons (S1 and S2, see figure 2):
for local setting of operating mode, brightness switch-
ing threshold and after-run time of the motion detec-
tor, independent of the bus
Display elements
1 red LED: for display of normal mode / addressing
mode (off / on)
1 red LED (below the lens of the motion detector):
for confirmation after operating mode and parameter
settings
Connections
Bus connection: screw-less bus terminal, single-wire
0.6...0.8 mm , insulation strip length 5 mm.
GAMMA instabus
Technical Product Information
May 2008
AP 251/11, Motion detector IP55 (titanium white) 5WG1 251-3AB11
AP 251/21, Motion detector IP55 (anthracite) 5WG1 251-3AB21
Technical Manual AP 251/_1, 4 pages Siemens AG
Industry Sector, Building Technologies
Update: http://www.siemens.com/gamma © Siemens AG 2008 Electrical Installation Technology
Subject to change without prior notice P.O.Box 10 09 53, D-93009 Regensburg
2.13.1.5/2
Mechanical data
Housing: plastic
Dimensions:: approx. 180 mm × 86 mm × 74 mm
(L × W × H)
Tilting arm adjustment zone: max. 120°
Weight: approx. 245 g
Fire load: approx. 7500 kJ
Electric safety
Degree of pollution (according to IEC 60664-1): 2
Type of protection (according to EN 60529): IP 55
Overvoltage category (according to IEC 60664-1): III
Bus: safety extra-low voltage SELV DC 24 V
Device complies with: EN 50090-2-2
EMC requirements
complies with EN 50090-2-2
Environmental conditions
Climatic withstand capability: EN 50090-2-2
Ambient temperature during operation: - 25 ... + 50 °C
Storage temperature: - 25 ... + 70 °C
rel. humidity (not condensing): 5 ... 93 %
Markings
KNX EIB
CE mark
complies with the EMC regulations (residential and func-
tional buildings), and low voltage regulations
Location and Function of the Display and Operat-
ing Elements
A2
A1
Figure 1: Position of display and operating elements on
the printed circuit board of the motion detector
A1 Key for toggling between normal mode and address-
ing mode for transferring the physical address.
A2 LED for indicating normal mode (LED Off) or ad-
dressing mode (LED On); it is automatically extin-
guished once the physical address has been trans-
ferred.
Figure 2: Position of display and operating elements on
the sensor side of the motion detector
S1 Operating key S1 (Brightness)
S2 Operating key S2 (Time)
Mounting and wiring
Mounting site
For optimum motion detection, the motion detector
should be mounted sideways on to the direction of mo-
tion (see figure 3), as far as possible at a height of 2.5 m,
as far as possible not over but under a luminaire and with
at least 0.5 m separation from any luminaire in the cap-
ture zone.
Figure 3: Mounting site and direction of motion
Capture zone
In order to avoid unwanted responses from the motion
detector, you must consider potential sources of inter-
ference (such as warm air flows, moving bushes or
trees). Unwanted capture zones can be filtered out as
required by fitting the cover screen supplied. It is to be
cut out accordingly for this purpose. The cover screen
fixing ring must not be separated when cutting out seg-
ments (see figure 4). No movements will be captured by
areas of the lens covered by the cover screen.
GAMMA instabus
Technical Product Information
May 2008
AP 251/11, Motion detector IP55 (titanium white) 5WG1 251-3AB11
AP 251/21, Motion detector IP55 (anthracite) 5WG1 251-3AB21
Siemens AG AP 251/_1, 4 pages Technical Manual
Industry Sector, Building Technologies
Electrical Installation Technology © Siemens AG 2008 Update: http://www.siemens.com/gamma
P.O.Box 10 09 53, D-93009 Regensburg Subject to change without prior notice
2.13.1.5/3
Figure 4: Adjustment of the cover screen
The capture zone of the detector can also be altered by
turning the lens through some +/- 30° to the right or left.
The capture range can be changed by adjusting the tilt-
ing arm (see figure 5).
Figure 5: Adjusting range of the tilting arm
Mounting and connecting the bus cable
The motion detector's connection box must be correctly
positioned when mounting on a wall (TOP showing, see
figures 6 and 7). You can use the dowels and screws
supplied for this. The spacing of the drilled holes in the
connection box is to be matched on a 60 mm flush-
mounted socket.
Figure 6: Correct position of the connection box
Figure 7: Mounting the connection box
The bus cable is to be brought in through one of the
punched out openings in the connection box. The insula-
tion of the red and black wire is to be stripped back for
approx. 5 mm, the wires are to be plugged into the part
of the bus terminal with the same colour and the bus
terminal is then to be plugged into its mounting on the
detector's printed connection board.
The detector is then to be plugged into the connection
box and screwed to it with the fixing screw (see figure
8).
Figure 8: Screwing of the motion detector
Depending on the requirement and the type of mount-
ing, the corresponding condensation opening adjoining
the screw opening is to be punched out (see figures 7
and 9).
Figure 9: Punching out of the condensation opening
GAMMA instabus
Technical Product Information
May 2008
AP 251/11, Motion detector IP55 (titanium white) 5WG1 251-3AB11
AP 251/21, Motion detector IP55 (anthracite) 5WG1 251-3AB21
Technical Manual AP 251/_1, 4 pages Siemens AG
Industry Sector, Building Technologies
Update: http://www.siemens.com/gamma © Siemens AG 2008 Electrical Installation Technology
Subject to change without prior notice P.O.Box 10 09 53, D-93009 Regensburg
2.13.1.5/4
Commissioning
Initialising phase
On first applying the bus voltage and after every bus
voltage recovery, the motion detector starts its initialisa-
tion phase. For this, the detector output is switched on
approx. 2 seconds. The red LED inside the lens flashes
approx. 3 times per second, until the device enters test
mode automatically after a maximum of 45 seconds.
Test mode
Test mode is a brightness-independent mode with an ON
period of 1 second and an after-run time of 2 seconds. It
can be used for manual checking of the capture zone and
to change the alignment or sensing angle of the lens. At
the end of the test mode period of 10 minutes, the mo-
tion sensor switches automatically to the factory setting
(brightness threshold 7 lux, delay time 2 minutes) or to
the individual setting made.
Test mode will be started automatically on first connect-
ing to the bus voltage only after the initialisation phase
has cycled. During any later bus voltage failure, only the
initialisation phase will then be recycled and the motion
sensor then enters the individual setting directly or the
factory setting if no individual setting has been pro-
grammed yet.
If test mode is re-activated, then this can be triggered by
holding down S1 and S2 simultaneously for at least 3
seconds (max. 5 seconds). The LED also flashes quickly
for 3 seconds and then stays ON. If you now release the
buttons, then test mode is confirmed by the LED flashing
twice. Test mode can be interrupted prematurely by
tapping S1 or S2 (see figure 2).
Mode and parameter settings
The following table shows the setting options using the
S1 and S2 pushbuttons.
Whereas the detector is switched on for the set delay
time with every motion captured during brightness-
independent operation, during brightness-dependent
operation the detector is switched on with a captured
motion only if the brightness falls below the set switch-
ing threshold. If a brightness switching threshold differ-
ing from the factory setting is wanted, then the user can
store the current brightness value as the new switching
threshold in the detector's memory by holding S1 down
for a period of less than 3 seconds. When doing this, take
care that the sensor is not covered by the user while
storing the new value.
In pulsed mode, the detector output is switched on for 1
second after the brightness falls below the threshold and
motion is detected. It will then no longer respond to a
movement for 9 seconds.
Action
Operation
LED
acknowl.
S1 S2
Reset (return
to factory
setting)
Hold down simultaneously for at least 6
seconds (LED flashes rapidly and remains on
after 3 seconds)
2 flashes
approx. 0.5
sec.
Test mode Hold down simultaneously for at least
3 seconds (LED flashes rapidly and remains
on after 3 seconds) and a max. 5 seconds
2 flashes
approx. 0.5
sec.
Leave test
mode
Press S1 or S2.
Alternatively, wait for 10 minutes: Detector
reverts automatically to the individual or
factory setting
_____
Toggling
brightness-
dependent
switching
!
brightness-
independent
switching
and vice
versa
Hold down for at least
3 seconds.
Preset brightness
threshold is retained
2 flashes
approx. 0.5
sec.
Brightness-
independent
switching is
indicated by a
short flash
every
5 seconds
Toggling
between
pulse mode
!
delay time
mode and
vice versa
Hold down for at
least
3 seconds.
Preset switching
time is retained
2 flashes
approx. 0.5
sec.
Store
brightness
threshold
in brightness-
dependent
switching
mode
Hold down for less
than 3 seconds
1 flash
approx. 0.5
sec.
Programming
individual
after-run
time between
5 seconds
and
30 minutes
differing
from the
factory
setting
1. Hold down for
less than 3 seconds:
starts the timer
2. Hold down for
less than 3 seconds:
stops the timer
Permanent
flashing from
timer start
until stop
General Notes