S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 1 of 33 www.power-one.com
RoHS lead solder exemption compliant
Extremely-wide input voltage range
Input over- and undervoltage lockout
Efficient input filter and built-in surge and transient
suppression circuitry
Outputs: SELV, no-load, and short-circuit proof
No derating over entire operating temperature range
PCBs coated with protective lacquer
Very high reliability
Table of Contents Page
Description ................................................................................1
Model Selection ........................................................................2
Part Number Description and Product Marking........................3
Functional Description ..............................................................4
Electrical Input Data..................................................................5
Electrical Output Data ..............................................................8
Auxiliary Functions..................................................................12
168
6.6"
60
2.4"
12 TE
111
4.4"
3 U
Safety according to IEC/EN 60950
Page
Electromagnetic Compatibility (EMC) ....................................15
Immunity to Environmental Conditions ..................................17
Mechanical Data ....................................................................18
Safety and Installation Instructions ........................................19
Description of Options ............................................................23
Accessories ............................................................................32
EC-Declaration of Conformity ................................................33
Input voltage ranges from 8 to 385 VDC and 85 to 264 VAC, 47-440 Hz
1or 2 isolated outputs up to 48 VDC
Class I equipment
Description
The S Series AC-DC and DC-DC converters represents a broad
and flexible range of power supplies for use in advanced
electronic systems. Features include high efficiency, high
reliability, low output voltage noise and excellent dynamic
response to load/line changes. LS models can be powered by
DC or AC with a wide-input frequency range (without PFC).
The converter inputs are protected against surges and
transients. An input over- and undervoltage lockout circuitry
disables the outputs if the input voltage is outside of the
specified range. Certain types include an inrush current limiter
preventing circuit breakers and fuses from tripping at switch-on.
All outputs are open- and short-circuit proof and are protected
against overvoltages by means of built-in suppressor diodes.
The outputs can be inhibited by a logic signal applied to pin 18
(i). If the inhibit function is not used, pin 18 must be connected
with pin 14 to enable the outputs.
LED indicators display the status of the converter and allow for
visual monitoring of the system at any time.
Full input-to-output, input-to-case, output-to-case and output-to-
output isolation is provided. The converters are designed and
built according to the international safety standards IEC/EN
60950 and EN50155. They have been approved by the safety
agencies TÜV and UL (for USA and Canada).
The case design allows operation at nominal load up to 71 °C in a
free-air ambient temperature. If forced cooling is provided, the
ambient temperature may exceed 71 °C, but the case temperature
must remain below 95 °C under all conditions.
A temperature sensor generates an inhibit signal, which disables
the outputs if the case temperature Tcexceeds the limit. The
outputs are automatically re-enabled when the temperature drops
below the limit.
Various options are available to adapt the converters to individual
applications.
The converters may either be plugged into a 19" rack system
according to IEC 60297-3, or be chassis mounted. They are ideally
suited for Railway applications.
Features
Important: For applications requiring compliance with IEC/EN
61000-3-2 (harmonic distortion), please use our LS4000 and LS5000
Series with incorporated power factor correction (PFC).
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 2 of 33 www.power-one.com
Output 1 Output 2 Input Voltage Efficiency 1Options
Vo nom Io nom Vo nom Io nom Vi min -Vi max
η
[VDC] [A] [VDC] [A] 8 to 35 VDC [%]
5.1 16 - - AS1001-7R 76 -9
12 8 - - AS1301-7R 81 D
15 6.5 - - AS1501-7R 83 V 2
24 4.2 - - AS1601-7R 84 P
12 4 12 34 AS2320-7R 79 T
15 3.2 15 33.2 AS2540-7R 80 B1, B2
24 2 24 32 AS2660-7R 80
Output 1 Output 2 Input Voltage Eff. 1Input Voltage Eff. 1Input Voltage Eff. 1Options
Vo nom Io nom Vo nom Io nom Vi min -Vi max
η
Vi min -Vi max
η
Vi min -Vi max
η
[VDC] [A] [VDC] [A] 14 to 70 VDC [%] 28 to 140 VDC [%] 20 to 100 VDC [%]
5.1 16 - - BS1001-7R 77 CS1001-7R 77 FS1001-7R 77 -9
12 8 - - BS1301-7R 83 CS1301-7R 83 FS1301-7R 83 E 4, -9E 4
15 6.5 - - BS1501-7R 85 CS1501-7R 84 FS1501-7R 84 V 2
24 4.2 - - BS1601-7R 86 CS1601-7R 85 FS1601-7R 86 P
12 4 12 34 BS2320-7R 80 CS2320-7R 80 FS2320-7R 80 T
15 3.2 15 33.2 BS2540-7R 82 CS2540-7R 82 FS2540-7R 82 B1, B2
24 2 24 32 BS2660-7R 82 CS2660-7R 82 FS2660-7R 82
Model Selection
Non-standard input/output configurations or special custom adaptions are available on request.
Table 1a: Model types AS
Table 1b: Model types BS, CS, and FS
Table 1c: Model types DS, ES, and LS
1Min. efficiency
η
at
V
i nom,
I
o nom, and
T
A= 25 °C (DC input for LS models). Typical values are approx. 2% better.
2Option V for S1001 models only.
3Second output semi-regulated.
4Option E only for CS, DS, ES, FS, and LS models; mandatory for all -9 models.
Output 1 Output 2 Input Voltage Eff. 1Input Voltage Eff. 1Input Voltage Eff. 1Options
Vo nom Io nom Vo nom Io nom Vi min -Vi max
η
Vi min -Vi max
η
Vi min -Vi max
η
[VDC] [A] [VDC] [A] 44 to 220 VDC [%] 67 to 385 VDC [%] 88 to 372 VDC [%]
85 to 264 VAC
5.1 16 - - DS1001-7R 79 ---- -- LS1001-7R 78 E 4, -9E 4
12 8 - - DS1301-7R 84 ES1301-7R 83 LS1301-7R 83 D
15 6.5 - - DS1501-7R 86 ES1501-7R 84 LS1501-7R 84 V 2
24 4.2 - - DS1601-7R 86 ES1601-7R 86 LS1601-7R 85 P
12 4 12 34 DS2320-7R 81 ES2320-7R 81 LS2320-7R 80 T
15 3.2 15 33.2 DS2540-7R 82 ES2540-7R 83 LS2540-7R 81 B1, B2
24 2 24 32 DS2660-7R 83 ES2660-7R 83 LS2660-7R 81
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 3 of 33 www.power-one.com
Part Number Description and Product Marking
C S 2 5 40 -9 E R D3 T B1
Input voltage range Vi:
8 - 35 VDC ................A
14 - 70 VDC .............. B
20 - 100 VDC .............. F
28 - 140 VDC................C
44 - 220 VDC................D
67 - 385 VDC .............. E
85 - 264 VAC or 88 - 372 VDC................ L
Series................................................................................S
Number of outputs ........................................................1, 2
Single output models:
Nominal voltage output 1 (main output), Vo1 nom
5.1 V ......0, 1, 2
12 V ................3
15 V ............4, 5
24 V ................6
Other voltages1............7, 8
Other specifications for
single output models1......01 - 99
Double output models:
Nominal voltage output 1 and 2
12, 12V ......................................................................20
15, 15V ......................................................................40
24, 24V ......................................................................60
Other specifications and additional features1......70 - 99
Operational ambient temperature range TA:
–25 to 71 °C................-7
–40 to 71 °C................-9
Other 1....-0, -5, -6
Auxiliary functions and options:
Inrush current limiter ......................................................E 3
Output voltage control input ..........................................R 2
Potentiometer (output voltage adjustment) ....................P 2
Undervoltage monitor (D0 - DD, to be specified) ..........D 4
ACFAIL signal (V0, V2, V3, to be specified) ..................V 4
Current share....................................................................T
Cooling plate standard case ..........................................B1
Cooling plate for long case (220 mm) 1..........................B2
1Customer-specific models.
2Feature R excludes option P and vice versa.
3Option E available for CS, DS, ES, FS, and LS models; mandatory for all -9 model types.
4Option D excludes option V and vice versa; option V available for S1001 models only.
Example: CS2540-9ERD3TB1: DC-DC converter, input voltage range 28 - 140 V, double output, each providing 15 V/3.2 A,
equipped with inrush current limiter, R input (voltage adjust), undervoltage monitor D3, current share, and a cooling plate
B1. Ambient temperature –40 to 71 °C.
Product Marking
Basic type designation, applicable approval marks, CE mark, warnings, pin allocation, Power-One patents, and company logo.
Identification of LEDs, test sockets, and potentiometer.
Specific type designation, input voltage range, nominal output voltages and currents, degree of protection, batch no., serial no., and
data code including production site, modification status, and date of production.
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 4 of 33 www.power-one.com
Functional Description
The input voltage is fed via an input fuse, an input filter, a bridge
rectifier (LS), and an inrush current limiter to the input capacitor.
This capacitor sources a single transistor forward converter.
Each output is powered by a separate secondary winding of the
main transformer. The resultant voltages are rectified and their
ripple smoothed by a power choke and output filter. The control
logic senses the main output voltage Vo1 and generates, with
respect to the maximum admissible output currents, the control
signal for the primary switching transistor.
The second output of double-output models is controlled by the
main output but has independent current limiting. If the main output
is driven into current limitation, the second output volt age will fall as
well and vice versa.
1Transient suppressor (VDR) in CS, DS, ES, FS, LS models
2Suppressor diode in AS, BS, CS, FS models
Control circuit
1
2
P
3
Forward converter
(approx. 110 kHz)
16
18
20
22
12
14
4
6
8
10
Output 2
filter
Output 1
filter
26
28
30
32
24
+
Y
YY
Y
Y
Y
R
i
D
T
Vi+
Vi–
03058-022706
Vo1+
Vo1–
Vo2+
Vo2–
Input filter
4
5
N
5
L
Fuse
3Inrush current limiter in CS, DS, ES, LS (NTC resistor or option E circuit)
4Bridge rectifier (LS only)
5LS models
Input filter
Control circuit
2
4
P
3
Forward converter
(approx. 120 kHz)
Y
16
18
20
22
12
4
6
8
10
14
Y
Output
filter
1
26
28
30
32
24
+
Y
Y
Vi+
Vi–
R
i
D/V
T
03057-022706
S+
Vo+
Vo–
S–
Fuse
5
N
5
L
Fig. 2
Block diagram of symmetrical double output converters AS - LS2000
Fig. 1
Block diagram of single output converters AS - LS1000
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 5 of 33 www.power-one.com
Table 2b: Input data
Input CS DS ES LS
Characteristics Conditions min typ max min typ max min typ max min typ max Unit
V
iOperating input voltage
I
o= 0
- I
o nom 28 140 44 220 67 385 88 372 VDC
T
C min
- T
C max 85 4264 4VAC
V
i nom Nominal input voltage 60 110 220 310 VDC
I
iInput current
V
i nom,
I
o nom 12.1 1.1 0.55 0.4 A
P
i0 No-load input power
V
i min
- V
i max 2.5 2.5 2.5 2.5 W
P
i inh Idle input power converter inhibited 1.5 1.5 1.5 4.5
R
iInput resistance 150 170 180 480 mΩ
R
NTC NTC resistance 212 44Ω
C
iInput capacitance 830 330 270 270 μF
V
i RFI
Conducted input RFI EN 55022 B B B B
Radiated input RFI
V
i nom,
I
o nom BB BA
V
i abs Input voltage limits 0 154 0 400 30 400 -400 400 VDC
without damage
1For double output models both outputs loaded with Io nom.
2Valid for -7 versions without option E. This is the nominal value at 25 °C and applies to cold models at initial switch-on cycle. Subsequent
switch-on/off cycles increase the inrush current peak value.
3For 1 s max.
4AC operating frequency range is 47 to 440 Hz (440 Hz for 115 V mains). For frequencies 63 Hz refer to Safety and Installation Instructions.
Input Transient Protection
A suppressor diode and/or a VDR (depending on input voltage
range) together with the input fuse and a symmetrical input filter
form an effective protection against high input transient volt ages
which typically occur in most installations, but especially in
battery-driven mobile applications.
Nominal battery voltages in use are: 12, 24, 36, 48, 60, 72, 110,
and 220 V. In most cases each nominal value is specified in a
tolerance of –30% to 25%.
In certain applications, surges according to RIA 12 are
specified in addition to those defined in IEC 60571-1. The
power supply must not switch off during these surges and
since their energy can practically not be absorbed an
extremely wide input range is required. The ES input range
for 110 V batteries has been designed and tested to meet
this requirement.
Electrical Input Data
General Conditions
TA= 25 °C, unless TCis specified.
– Pin 18 connected to pin 14, R input not connected, Voadjusted to Vo nom (option P)
– Sense line pins S+ and S– connected to Vo+ and Vo–, respectively.
Table 2a: Input data
Input AS BS FS
Characteristics Conditions min typ max min typ max min typ max Unit
V
iOperating input voltage
I
o= 0
- I
o nom 8 35 14 70 20 100 VDC
V
i nom Nominal input voltage
T
C min
- T
C max 15 30 50
I
iInput current
V
i nom,
I
o nom 17.5 4.3 2.6 A
P
i0 No-load input power
V
i min
- V
i max 2.5 2.5 2.5 W
P
i inh Idle input power converter inhibited 1.5 1.5 1.5
R
iInput resistance 65 100 70 mΩ
C
iInput capacitance 1040 370 1500 μF
V
i RFI Conducted input RFI EN 55022 A B B
Radiated input RFI
V
i nom,
I
o nom AAB
V
i abs Input voltage limits 0 40 0 80 0 100 VDC
without damage
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 6 of 33 www.power-one.com
Input Fuse
Afuse mounted inside the converter protects the module against
severe defects. This fuse may not fully protect the module when
the input voltage exceeds 200 VDC! In applications where the
converters operate at source voltages above 200 VDC an
external fuse or a circuit breaker at system level should be
installed!
The inrush current peak value (initial switch-on cycle) can be
determined by following calculation:
V
i source
I
inr p = ––––––––––––––––
(
R
s ext +
R
i+
R
NTC)
Rs ext RiRNTC
Iinr p
Vi source
+Ci int
05109_060805
Reverse Polarity
The converters (except LS) are not protected against reverse
polarity at the input, but in general, only the input fuse will trip. LS
models are fully protected due to the built-in bridge rectifier.
Static Input Current Characteristic
Fig. 5
Typical input current versus relative input voltage
234561
1
2
5
10
FS
CS
ES
LS (DC input)
Vi
Vi min
Ii [A]
DS
20
0.5
AS
BS
04037_011906
Input Under-/Overvoltage Lockout
If the input voltage remains below approx. 0.8 Vi min or exceeds
approx. 1.1 Vi max, an internally generated inhibit signal disables
the output(s). When checking this function the absolute maximum
input voltage rating Vi abs should be considered! Between Vi min
and the undervoltage lockout level the output voltage may be
below the value defined in table: Electrical Output Data.
Fig. 3
Typical inrush current versus time at V
i max,
R
ext = 0.
For AS, BS, and FS as well as for application-related values
use the formula given in
this section
to get realistic results.
Inrush Current
The CS, DS, ES, and LS models (not -9, not option E)
incorporate an NTC resistor in the input circuitry, which at initial
turn-on reduces the peak inrush current value by a factor of 5 to
10. Subsequent switch-on cycles within short periods increase
the inrush current due to the hotter NTC resistor.
123 t [ms]
0
50
100
Ii inr [A]
150
CS
ES, LS
DS
04038_110705
Fig. 4
Equivalent circuit for input impedance
Table 3: Fuse Specification
Model Fuse type Reference Rating
AS 1fast-blow Little fuse 314 30.0 A, 125 V
BS 1fast-blow Little fuse 314 25.0 A, 125 V
CS 2slow-blow SPT 12.5 A, 250 V
DS 2slow-blow SPT 8 A, 250 V
ES 2slow-blow SPT 4 A, 250 V
FS 2slow-blow SPT 16 A, 250 V
LS 2slow-blow SPT 4 A, 250 V
1Fuse size 6.3 x32 mm 2Fuse size 5 x20 mm
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 7 of 33 www.power-one.com
234561
0.30
1
Vi
–––––
Vi min
th [ms]
10
100
DS
CS
ES
FS
AS BS
04041_011906
234561
2
th
[ms]
10
100
04049_011906
Vi
Vi min
Fig. 6a
Typical hold-up time t
h
versus relative input voltage
V
i
/V
imin
. The DC-DC converters require an external
series diode in the input path if other loads are connected
to the same input supply lines.
Fig. 6b
Typical hold-up time t
h
versus relative AC input voltage (LS
models)
Hold-up Time Versus Relative Input Voltage
Electrical Output Data
General Conditions
T
A= 25 °C, unless
T
Cis specified.
– Pin 18 (i) connected to pin 14 (S–/Vo1–),
V
oadjusted to
V
o nom (option P), R input not connected.
– Sense line pins 12 (S+) and 14 (S–) connected to Vo1+ and Vo1–, respectively.
Table 4a: Output data: single output models
Output AS-LS1001 AS-LS1301 AS-LS1501 AS-LS1601
V
o nom 5.1 V 12 V 15 V 24 V
Characteristics Conditions min typ max min typ max min typ max min typ max Unit
V
oOutput voltage
V
i nom,
I
o nom 5.05 5.15 11.88 12.12 14.85 15.15 23.76 24.24 V
V
o P Overvoltage protection 7.6 21 26.5 43.5
(suppressor diode)
I
o nom Output current nom 1
V
i min
- V
i max 16 8 6.5 4.2 A
T
C min
- T
C max
I
o L Output current limit 2
V
i min
- V
i max 16.2 8.2 6.7 4.4
v
oOutput Switching freq.
V
i nom,
I
o nom 10 65 65 65 6mVpp
noise 5Total incl. BW = 20 MHz 50 50 60 90
spikes
Δ
V
o u Static line regulation
V
i min -
V
i max ±15 ±20 ±25 ±30 mV
with respect to
V
i nom
I
o nom
Δ
V
o I Static load regulation
V
i nom, -20 -25 -30 -40
(0.1 - 1)
I
o nom
vo d Dynamic Voltage
V
i nom,±100 ±100 ±100 ±100
load deviation 3
I
o nom 0.5
I
o nom
t
d regulation 5Recovery 0.4 0.5 0.5 0.5 ms
time 3
αvo Temperature coefficient
T
C min
- T
C max,±0.02 ±0.02 ±0.02 ±0.02 %/K
of output voltage 4
I
o nom
1If the output voltages are increased above Vo nom through R-input control, option P setting, remote sensing or option T, the output
current should be reduced accordingly so that Po nom is not exceeded.
2 See: Output Voltage Regulation.
3 See: Dynamic Load Regulation.
4 For battery chargers a defined negative temperature coefficient can be provided, see Accessories.
5 Measured according to IEC/EN 61204.
6LS models have an additional low-frequency ripple at twice the input frequency (< 5mVpp).
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 8 of 33 www.power-one.com
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 9 of 33 www.power-one.com
Table 4c: Output data: double output models
Output AS-LS2660
V
o nom 24 V/24 V
Characteristics Conditions Output 1 Output 2
min typ max min typ max Unit
V
oOutput voltage
V
i nom,
I
o nom123.76 24.24 23.52 24.48 V
V
o P Overvoltage protection 37 37
(suppressor diode)
I
o nomOutput current nom 2
V
i min
- V
i max 22A
T
C min
- T
C max
I
o L Output current limit 6
V
i min
- V
i max 2.2 2.2
v
oOutput Switching freq.
V
i nom,
I
o nom 5 75 7mVpp
noise 3
Total including BW = 20 MHz 50 50
spikes
Δ
V
o u Static line regulation
V
i min -
V
i max ±30 6mV
with respect to
V
i nom
I
o1 nom,
I
o2 nom
Δ
V
o I Static load regulation
V
i nom,
I
o2 nom, -60 6
(0.1 - 1)
I
o1 nom
V
o d Dynamic Voltage
V
i nom, ±100 ±150
load deviation 4
I
o1 nom0.5
I
o1 nom,
t
dregulation3
Recovery 0.5
I
o2 nom 0.2 ms
time 4
αvo Temperature coefficient
T
C min
- T
C max ±0.02 %/K
of output voltage 5
I
o1 nom,
I
o2 nom
1Same conditions for both outputs.
2If the output voltages are increased above
V
o nom via R-input control, option P setting,
remote sensing or option T, the output currents
should be reduced accordingly so that
P
o nom is
not exceeded.
3Measured according to IEC/EN 61204.
4See:
Dynamic Load Regulation.
5For battery chargers a defined negative
temperature coefficient can be provided, see
Accessories.
6See:
Output Voltage Regulation of Double
Output Models
.
7LS models have an additional low-frequency
ripple at twice the input frequency (< 5 mVpp).
Table 4b: Output data: double output models
Output AS-LS2320 AS-LS2540
V
o nom 12 V/12 V 15 V/15 V
Characteristics Conditions Output 1 Output 2 Output 1 Output 2
min typ max min typ max min typ max min typ max Unit
V
oOutput voltage
V
i nom,
I
o nom 111.88 12.12 11.76 12.24 14.85 15.15 14.70 15.30 V
V
o P Overvoltage protection 19 19 24 24
(suppressor diode)
I
o nomOutput current nom 2
V
i min -
V
i max 4 4 3.2 3.2 A
T
C min -
T
C max
I
o L Output current limit 6
V
i min -
V
i max 4.2 4.2 3.4 3.4
v
oOutput Switching freq.
V
i nom,
I
o nom 5 75 75 75 7mVpp
noise 3Total including BW = 20 MHz 40 40 50 50
spikes
Δ
V
o u Static line regulation
V
i min -
V
i max ±20 6±25 6mV
with respect to
V
i nom
I
o1 nom,
I
o2 nom
Δ
V
o I Static load regulation
V
i nom,
I
o2 nom, -40 6-50 6
(0.1 - 1)
I
o1 nom
v
o d Dynamic Voltage
V
i nom, ±100 ±150 ±100 ±150
load deviation 4
I
o1 nom0.5
I
o1 nom,
t
dregulation 3Recovery 0.5
I
o2 nom 0.2 0.2 ms
time 4
αvo Temperature coefficient
T
C min -
T
C max ±0.02 ±0.02 %/K
of output voltage 5
I
o1 nom,
I
o2 nom
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 10 of 33 www.power-one.com
Thermal Considerations
If a converter is located in free, quasi-stationary air (convection
cooling) at the indicated maximum ambient temperature TA max
(see table: Temperature specifications) and is operated at its
nominal input voltage and output power, the temperature
measured at the Measuring point of case temperature TC(see:
Mechanical Data) will approach the indicated value TC max after
the warm-up phase. However, the relationship between TAand
TCdepends heavily on the conditions of operation and
integration into a system. The thermal conditions are influenced
by input voltage, output current, airflow and temperature of
surrounding components and surfaces. TA max is therefore,
contrary to TC max, an indicative value only.
Caution: The installer must ensure that under all operating
conditions TCremains within the limits stated in the table
Temperature specifications.
Notes: Sufficient forced cooling or an additional heat sink allows TA
to be higher than 71 °C (e.g., 85 °C) if TC max is not exceeded.
For -7 or -9 models at ambient temperature TA= 85 °C with only
convection cooling, and the maximum permissible current for each
output is approx. 40% of its nominal value as per the figure below.
Output Protection
Each output is protected against overvoltages which could occur
due to a failure of the internal control circuit. Voltage suppressor
diodes (which under worst case condition may become a short
circuit) provide the required protection. The suppressor diodes are
not designed to withstand externally applied overvoltages.
Overload at any of the outputs will cause a shut-down of all
outputs. A red LED indicates the overload condition.
Parallel or Series Connection
Single or double-output models with equal nominal output voltage
can be connected in parallel without any precautions using
Option T (current sharing).
Single output models and/or main and second outputs of double-
output models can be connected in series with any other (similar)
output.
Notes:
Parallel connection of double output models should include both,
main and second output to maintain good regulation of both
outputs.
Not more than 5 models should be connected in parallel.
Series connection of second outputs without involving their main
outputs should be avoided as regulation may be poor.
Rated output voltages above 36 V need additional measures in
order to comply with the safety requirements for SELV (Safe Extra
Low Voltage)
The maximum output current is limited by the output with the lowest
current limitation if several outputs are connected in series.
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
50 60 70 80 90 100
Io/Io nom
T
A [˚C]
0.9
1.0
Forced cooling
05089_052305
T
A min
T
C max
Convection cooling
Fig. 7
Output current derating versus temperature for -7 and -9
models.
Thermal Protection
A temperature sensor generates an internal inhibit signal which
disables the outputs if the case temperature exceeds TC max.
The outputs are automatically re-enabled when the temperature
drops below this limit.
Continuous operation under simultaneous worst-case conditions
of the following three parameters should be avoided: minimum
input voltage, maximum output power, and maximum
temperature.
Output Voltage Regulation
Fig. 8
Output characteristic V
o1
vs. I
o1
(typ.)
Vo
Vo nom
0.98
0.5
00.5 1.0
Io1
IoL
Io
Io nom
05098_050605
The following figures apply to single-output or double-output
models with parallel-connected outputs.
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 11 of 33 www.power-one.com
Output 1 is under normal conditions regulated to Vo1 nom,
independent of output currents. Vo2 depends upon the load
distribution. If both outputs are loaded with more than 10% of Io
nom, the deviation of Vo2 remains within ±5% of the value of Vo1.
The following 3 figures show the regulation with varying load
distribution.
T wo output s of an S2000 model connected in parallel will behave
like the output of an S1000 model.
Fig. 10
AS - LS2320:
Δ
V
o2
(typ.) vs. I
o2
with different I
01
012345678
Io2
[A]
11.2
11.4
11.6
11.8
12.0
12.2
12.4
12.6
[V] Vo2
Io1 = 6.0 A
Io1 = 4.5 A
Io1 = 3.0 A
Io1 = 1.5 A
Io1 = 0.6 A
05105_060805
01234567
Io2
[A]
14.00
14.25
14.50
14.75
15.00
15.25
15.50
15.75
[V] Vo2
Io1 = 5.00 A
Io1 = 3.75 A
Io1 = 2.50 A
Io1 = 1.25 A
Io1 = 0.50 A
05106_070805
Fig. 11
AS - LS2540:
Δ
V
o2
(typ.) vs. I
o2
with different I
01
[V] Vo2
Io2
[A]
0 0.5 1 1.5 2 2.5 3 3.5 4
23.0
23.5
24.0
24.5
25.0
25.5
26.0 Io1 = 3.0 A
Io1 = 2.0 A
Io1 = 1.0 A
Io1 = 0.5 A
Io1 = 0.3 A
05107_060805
Fig. 12
AS - LS2660:
Δ
V
o2
(typ.) vs. I
o2
with different I
01
Output Voltage Regulation of Double Output Models
Note: If output 2 is not used, we recommend connecting it in
parallel with output 1. This ensures good regulation and efficiency.
V
od
V
od
t
d
t
d
V
o ±1%
V
o ±1
%
t
t
10 μs 10 μs
V
o
0
0.5
1
I
o/
I
o max
05102
Fig. 9
Typical dynamic load regulation of Vo
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 12 of 33 www.power-one.com
Fig. 15
Typical output response as a function of inhibit control
Table 5: Inhibit characteristics
Characteristic Conditions min typ max Unit
V
inh Inhibit
V
o= on
V
i min
-
V
i max –50 0.8 V
voltage
V
o= off 2.4 50
I
inh Inhibit current
V
inh = 0 –400 µA
t
rRise time 30 ms
t
fFall time depending on
I
o
0t
t
0
Inhibit
1
0.1
1
Vo/Vo nom
trtf
06001
Sense Lines
(Only single output models)
Important: Sense lines must always be connected! Incorrectly
connected sense lines may activate the overvoltage limitation,
resulting in a permanent short-circuit of the output.
This feature allows for compensation of voltage drops across the
connector contacts and if necessary, across the load lines. If the
sense lines are connected at the load rather than directly at the
connector, the user should ensure that the voltage differences
specified in the table below are not exceeded. We recommend
connecting the sense lines directly at the female connector.
To ensure correct operation, both sense lines (S+ and S–) should
be connected to their respective power outputs (Vo1+ and Vo1–)
and the voltage difference between any sense line and its
respective power output pin (as measured on the connector)
should not exceed the following values:
Table 6: Maximum voltage compensation allowed using
sense lines
Output Total voltage difference Voltage difference
voltage between sense lines and between
their respective outputs Vo– and S–
5.1 V <0.5 V <0.25 V
12, 15, 24 V <1.0 V <0.25 V
If the output voltages are increased above Vo nom via the R-input
control, option P setting, remote sensing or option T, the output
currents must be reduced accordingly so that Po nom is not
exceeded.
Auxiliary Functions
i Inhibit for Remote On and Off
Note: With open i input the output is disabled.
The outputs may be enabled or disabled by means of a logic
signal (TTL, CMOS, etc.) applied between the inhibit input i and
the negative pin of output 1 (Vo1–). In systems with several
converters, this feature can be used to control the activation
sequence of the converters. If the inhibit function is not required,
connect the inhibit pin 18 to pin 14 to enable the outputs (active
low logic, fail safe).
Vi+
Vi– Vo–
i
Vo+
Iinh
Vinh
06031
1.6
0.8
0
–0.8
–50
Vinh [V]
Iinh [mA]
–30 0–10 10 30 50
2.0
1.2
0.4
0.4
Vinh = 0.8 V
Vo = on Vo = off
Vinh = 2.4 V
06032
Fig. 13
Definition of V
inh
and I
inh
.
Fig. 14
Typical inhibit current I
inh
versus inhibit voltage V
inh
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 13 of 33 www.power-one.com
Programmable Output Voltage (R-Function)
As a standard feature, the converters offer an adjustable output
voltage, identified by letter R in the type designation. The control
input R (pin 16) accepts either a control voltage Vext or a
resistor Rext to adjust the desired output voltage. When not
connected, the control input automatically sets the output
voltage to Vo nom.
a)Adjustment by means of an external control voltage Vext
between pin 16 (R) and pin 14:
The control voltage range is 0 - 2.75 VDC and allows an
output voltage adjustment in the range of approximately
0 - 110% Vo nom.
V
o
V
ext = –––––– • 2.5 V (approximate formula)
V
o nom
b) Adjustment by means of an external resistor:
Depending upon the value of the required output voltage the
resistor shall be connected
Either: Between pin 16 and pin 14 (Vo< Vo nom) to achieve
an output voltage adjustment range of approximately
0 - 100% Vo nom
or: Between pin 16 and pin 12 (Vo > Vo nom) to achieve an
output voltage adjustment range of approximately 100 - 110%
Vo nom.
Warning:
Vext shall never exceed 2.75 VDC.
The value of R'ext shall never be less than the lowest value
as indicated in table R'ext for (Vo > Vo nom)
Notes:
The R-Function excludes option P (output voltage adjustment by
potentiometer).
If the output voltages are increased above Vo nom via R-input
control, option P setting, remote sensing or option T, the output
current(s) should be reduced accordingly so that Po nom is not
exceeded.
With double-output models the second output follows the value of
the controlled main output.
In case of parallel connection the output voltages should be
individually set within a tolerance of 1 - 2%.
Fig. 16
Output voltage control for single-output models AS - LS1000.
R
Vo1+
Vo1–
S–
Vext
Vi+
Vi
Rext
R'ext
14
16
16
14
+
S+
Vo1+
Vo1–
S–
Vi+
Vi
R
12
05074_050905
Table 7a: R
ext
for V
o
< V
o nom
; approximative values (V
i nom,
I
o nom
, series E 96 resistors); R'
ext
= not fitted
V
o nom = 5.1 V
V
o nom = 12 V
V
o nom = 15 V
V
o nom = 24 V
V
o[V]
R
ext [kΩΩ]
V
o[V] 1
R
ext [kΩΩ]
V
o[V] 1
R
ext [kΩΩ]
V
o[V] 1
R
ext [kΩΩ]
0.5 0.432 2 4 0.806 2 4 0.619 4 8 0.806
1.0 0.976 3 6 1.33 4 8 1.47 6 12 1.33
1.5 1.65 4 8 2 6 12 2.67 8 16 2
2.0 2.61 5 10 2.87 8 16 4.53 10 20 2.87
2.5 3.83 6 12 4.02 9 18 6.04 12 24 4.02
3.0 5.76 7 14 5.62 10 20 8.06 14 28 5.62
3.5 8.66 8 16 8.06 11 22 11 16 32 8.06
4.0 14.7 9 18 12.1 12 24 16.2 18 36 12.1
4.5 30.1 10 20 20 13 26 26.1 20 40 20
5.0 200 11 22 42.2 14 28 56.2 22 44 44.2
1First column: Voor Vo1, second column: outputs of double-output models in series connection
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 14 of 33 www.power-one.com
Table 7b: R’
ext
for V
o>
V
o nom
; approximative values (V
i nom
, I
o nom
, series E 96 resistors); R
ext
= not fitted
V
o nom = 5.1 V
V
o nom = 12 V
V
o nom = 15 V
V
o nom = 24 V
V
o[V]
R'
ext [kΩΩ]
V
o[V] 1
R'
ext [kΩΩ]
V
o[V] 1
R'
ext [kΩΩ]
V
o[V] 1
R'
ext [kΩΩ]
5.15 432 12.1 24.2 1820 15.2 30.4 1500 24.25 48.5 3320
5.2 215 12.2 24.4 931 15.4 30.8 768 24.5 49.0 1690
5.25 147 12.3 24.6 619 15.6 31.2 523 24.75 49.5 1130
5.3 110 12.4 24.8 475 15.8 31.6 392 25.0 50.0 845
5.35 88.7 12.5 25.0 383 16.0 32.0 316 25.25 50.5 698
5.4 75 12.6 25.2 316 16.2 32.4 267 25.5 51.0 590
5.45 64.9 12.7 25.4 274 16.4 32.8 232 25.75 51.5 511
5.5 57.6 12.8 25.6 243 16.5 33.0 221 26.0 52.0 442
13.0 26.0 196 26.25 52.5 402
13.2 26.4 169 26.4 52.8 383
1First column: Voor Vo1, second column: outputs of double-output models in series connection
Display Status of LEDs
Vo1 > 0.95 to 0.98Vo1 adj
Vi max Vi ov
Vi min
Vi uv
Vi
Vi abs
OK
i
Vo1 > 0.95 to 0.98Vo1 adj
Io nom IoL
Io
OK
Io L
Vo1 < 0.95 to 0.98Vo1 adj
TC
i
TC max TPTC threshold
Vi inh
i
+50 V
+0.8 V +2.4 V
-50 V
Vinh threshold
Io L
LED off LED on
LED Status undefined
06002_011106
Test Jacks
Test jacks for measuring the output voltage Voor Vo1 are
located at the front of the converter. The positive test jack is
protected by a series resistor (see: Functional Description,
block diagrams). The voltage measured at the test jacks is
slightly lower than the value at the output terminals.
Fig. 18
LEDs
"
OK
"
,
"
i
"
and
"
I
o L"
status versus input voltage
Conditions: I
o
I
o nom
, T
C
T
C max
, V
inh
0.8 V
V
i uv
= undervoltage lockout, V
i ov
= overvoltage lockout
LEDs
"
OK
"
and
"
I
o L"
status versus output current
Conditions: V
i min -
V
i max
, T
C
T
Cmax
, V
inh
0.8 V
LED
"
i
"
versus case temperature
Conditions: V
i min -
V
i max
, I
o
I
o nom
, V
inh
0.8 V
LED
"
i
"
versus V
inh
Conditions: V
i min -
V
i max
, I
o
I
o nom
, T
C
T
C max
R'ext
Rext
14
16
Vo1–
Vo1+
R
Vo2–
Vo2–
Vo2+
Vo2+
12
10
8
6
4+
Vo1
24 V
30 V
48 V
06004_012006
co
Fig. 17
Wiring for output voltage 24 V, 30 V, or 48 V (double-output
models) with both outputs connected in series. A ceramic
capacitor (Co) across the load reduces ripple and spikes.
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 15 of 33 www.power-one.com
typically occur in most installations; especially in battery-driven
mobile applications.
Electromagnetic Compatibility (EMC)
A suppressor diode and/or a metal oxide VDR (depending upon
type) together with an input fuse and an input filter form an
effective protection against high input transient voltages which
RIA 12
(covers also
IEC60571-1
and
EN50155:1995)
Electromagnetic Immunity
Table 8: Immunity type tests
Phenomenon Standard Surge/ Coupling Value Waveform Source Test In Per-
Level mode 1applied imped. procedure oper. form. 2
Supply related A 3+i/–i 3.5
V
batt 2/20/2 ms 0.2 Ω1 positive yes A
surge B 1.5
V
batt 0.1/1/0.1 s surge
Direct transient C +i/c, –i/c 960 Vp10/100 µs 5 Ω5 pos. and 5 neg. yes B
D 41800 Vp5/50 µs impulses
E 3600 Vp0.5/5 µs 100 Ω
F 4800 Vp0.1/1 µs
G 58400 Vp0.05/0.1 µs
Indirect coupled H +o/c, –o/c, 1800 Vp5/50 µs
transient J 3600 Vp0.5/5 µs
K 4800 Vp0.1/1 µs
L 8400 Vp0.05/0.1 µs
Electrostatic IEC/EN 4 6contact discharge 8000 Vp1/50 ns 330 Ω10 positive and yes A
discharge 61000-4-2 air discharge 15000 Vp10 negative
(to case) discharges
Electromagnetic IEC/EN 3
7antenna 20 V/m AM 80% n.a. 80 - 1000 MHz yes A
field 61000-4-3 1 kHz
3 antenna 10 V/m 50% duty cycle, n.a. 900 ±5 MHz yes A
200 Hz repetition
frequency
Fast IEC/EN 4 8capacitive, o/c 2000 Vpbursts of 5/50 ns 50 Ω60 s positive yes A
transients/burst 61000-4-4 i/c, +i/–i 4000 Vp2.5/5 kHz over 60 s negative
direct 15 ms; burst transients per
period: 300 ms coupling mode
Surges IEC/EN 3 i/c 2000 Vp1.2/50 µs 12 Ω5 pos. and 5 neg. yes A
61000-4-5 3 +i/–i 2000 Vp1.2/50 µs 2 Ωsurges per
coupling mode
RF conducted IEC/EN 3 9i, o, signal wires 10 VAC AM 80% 150 Ω0.15 - 80 MHz yes A
immunity 61000-4-6 (140 dBμV) 1 kHz
1i = input, o = output, c = case.
2A = Normal operation, no deviation from specifications, B = Normal operation, temporary deviation from specs possible.
3Only met with customer-specific models, CS (48 V battery) and ES (110 V battery) designed for an extended
Vi
range. Standard DS
models (110 V battery) will not be damaged, but overvoltage lockout will occur during the surge.
4Corresponds to EN 50155:2001, waveform A, and EN 50121-3-2:2000, table 7.2.
5Corresponds to EN 50155:2001, waveform B.
6Corresponds to EN 50121-3-2:2000, table 9.2.
7Corresponds to EN 50121-3-2:2000, table 9.1.
8Corresponds to EN 50121-3-2:2000, table 7.1.
9Corresponds to EN 50121-3-2:2000, table 7.4.
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 16 of 33 www.power-one.com
Fig. 19a
Typical disturbance voltage (peak) at the input according to
EN 55011/22, measured at V
i nom
and I
o nom
(DK1301-7R)
.
Fig. 19b
Typical disturbance voltage (peak) at the input according to
EN 55011/22, measured at V
i
= 230 VAC and I
o nom,
(LK1001-7RD9B1)
.
0
10
20
30
40
50
60
70
80
dBμVLS1301-7R, Peak Vi+, Conducted 0,15 ÷ 30 MHz, Divina, 2006-11-01
EN 55022 B
0.2 0.5 1 2 5 10 20 MHz
50
40
30
20
10
0
30
50
100
200
500
1000
[dBμV/m]
[MHz]
A
B
07077
Fig. 19c
Typical radiated electromagnetic field strength (quasi-peak)
according to EN 55011/22, normalized to a distance of 10 m,
measured at V
i nom
and I
o nom.
Electromagnetic Emission
Note: The Railway Standard, EN50121-3-2:2000 table 3, imposes
much higher limits, which are by far fulfilled.
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 17 of 33 www.power-one.com
Table 10: Temperature specifications, valid for an air pressure of 800 - 1200 hPa (800 - 1200 mbar)
Temperature Standard -7 Option -9
Characteristics Conditions min max min max Unit
T
AAmbient temperature Converter –25 71 –40 71 °C
T
CCase temperature1Operating
–25 95 –40 95
T
SStorage temperature Non-operational –40 100 –55 100
1Overtemperature lockout at
T
C> 95 °C
Table 11: MTBF
Values at specified Model types Ground benign Ground fixed Ground mobile Unit
case temperature 40 °C 40 °C 70 °C 50 °C
MTBF 1AS - LS 500 000 150 000 80 000 50 000 h
Device hours 2500 000
1Calculated in accordance with MIL-HDBK-217F.
2Statistical values, based on an average of 4300 working hours per year and over 3 years in general field use.
1 Covers also EN50155/EN61373 (Category 1, body mounted Class B).
Failure Rates
Immunity to Environmental Conditions
Table 9: Mechanical and climatic stress
Test method Standard Test conditions Status
Ca Damp heat IEC/EN 60068-2-78 Temperature: 40 ±2 °C Converter
steady state MIL-STD-810D sect. 507.2 Relative humidity: 93 +2/-3 % not
Duration: 56 days operating
Ea Shock IEC/EN 60068-2-27 1Acceleration amplitude: 100 gn= 981 m/s2Converter
(half-sinusoidal) MIL-STD-810D sect. 516.3 Bump duration: 6 ms operating
Number of bumps: 18 (3 each direction)
Eb Bump IEC/EN 60068-2-29 Acceleration amplitude: 40 gn= 392 m/s2Converter
(half-sinusoidal) MIL-STD-810D sect. 516.3 Bump duration: 6 ms operating
Number of bumps: 6000 (1000 each direction)
Fc Vibration IEC/EN 60068-2-6 Acceleration amplitude: 0.35 mm (10 - 60 Hz) Converter
(sinusoidal) MIL-STD-810D sect. 514.3 5 gn= 49 m/s2(60 - 2000 Hz) operating
Frequency (1 Oct/min): 10 - 2000 Hz
Test duration: 7.5 h (2.5 h each axis)
Fn Vibration IEC/EN 60068-2-64 Acceleration spectral density: 0.05 gn2/Hz Converter
broad band Frequency band: 5 - 500 Hz operating
random Acceleration magnitude: 4.97 gn rms
(digital control) Test duration: 3 h (1 h each axis)
Kb Salt mist, cyclic IEC/EN 60068-2-52 Concentration: 5% (30 °C) Converter
(sodium chloride Duration: 2 h per cycle not
NaCl solution) Storage: 40 °C, 93% rel. humidity operating
Storage duration: 22 h per cycle
Number of cycles: 3
111 (3U)
168.5
60
4.5
19.7
9.5
29.951.5
30.3
20.3
12.1
10.3
7.0
3.27
7 TE 5 TE
Test jacks
Option P (Vo)
Option D (Vti)
LED OK (green)
LED i (red)
LED IoL (red)
Option D (Vto)
25.9
Front plate Main face Back plate
(171.0 to 171.9)
50
11.8
= Ø 3.5
= Ø 4.1
(+/–)
152
100
M4
55
8
152
8
09004_110705
Measuring point of
case temperature TC
d
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 18 of 33 www.power-one.com
Mechanical Data
Dimensions in mm. The converters are designed to be inserted
into a 19” rack, 160 mm long, according to IEC 60297-3.
Fig. 20
Aluminum case S02 with heat sink, black finish and self-cooling,
weight: Approx. 1.25 kg
Fig. 21
Aluminum case S02 with option B1 (cooling plate), black finish and
self-cooling, weight: Approx. 1.15 kg
Note:
–d 15 mm, recommended clearance to next part in order to
ensure proper air circulation at full power.
Free air location: the converter should be mounted with fins in
a vertical position to achieve maximum airflow through the
heat sink.
European
Projection
111 (3U)
17.3 133.4
168
101
5
47.2
158
5
M 4
5
Measuring point of
case temperature TC
50
(171.0 to 171.9)
3.27
7 TE 4 TE
09003_110705
Note: Long case with option B2, elongated by 60 mm for 220
mm rack depth, is available on request with a customer-specific
part number (no LEDs and no test jacks).
Table 12: H15 connector pin allocation
Pin Connector type H15
No. AS to LS1000 AS to LS2000
4 Vo1+ Pos. output 1 Vo2+ Pos. output 2
6 Vo1+ Vo2+
8 Vo1– Neg. output 1 Vo2– Neg. output 2
10 Vo1– Vo2–
12 S+ Sense Vo1+ Pos. output 1
14 S– Sense Vo1– Neg. output 1
16 R 1Control of
V
oR1Control of
V
o1
18 i Inhibit i Inhibit
20 D 3Save data D 3Safe data
V3ACFAIL
22 T 5Current share T 5Current share
24 2Protective earth Protective earth
26 Vi+ N 4Pos. input Vi+ N 4Pos. input
28 Neutral line 4Neutral line 4
30 Vi– L 4Neg. input Vi– L 4Neg. input
32 Phase line 4Phase line 4
1Not connected, if option P is fitted.
2Leading pin (pre-connecting).
3Option D excludes option V and vice versa. Pin not connected unless
option D or V is fitted.
4LS models.
5Not connected, unless option T is fitted.
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 19 of 33 www.power-one.com
Safety and Installation Instructions
Connector Pin Allocation
The connector pin allocation table defines the electrical
potentials and the physical pin positions on the H15/H15 S4
connector. Pin no. 24 (protective earth) is a leading pin, ensuring
that it makes contact first.
Installation Instructions
The S Series converters are components, intended exclusively for
inclusion within other equipment by an industrial assembly
operation or by professional installers. Installation must strictly
follow the national safety regulations in compliance with the
enclosure, mounting, creepage, clearance, casualty, markings and
segregation requirements of the end-use application.
Fig. 22
View of converter’s male connector
Connection to the system shall be made via the female connector
H15 (see:
Accessories
)
.
Other installation methods may not meet
the safety requirements.
The converters are provided with pin 24 ( ), which is reliably
connected with the case. For safety reasons it is essential to
connect this pin to protective earth. See:
Safety of Operator
Accessible Output Circuit
.
Input pins 30 and 32 are internally fused. Since this fuse is
designed to protect the converter in case of an overcurrent and
does not necessarily cover all customer needs, an external fuse
suitable for the application and in compliance with the local
requirements might be necessary in the wiring to one or both input
potentials, pins 26 and 28, and/or 30 and 32.
432
Type H15
Fixtures for connector
retention clips
(see Accessories)
10090
Important: When the inhibit function is not in use, pin no. 18 (i)
should be connected to pin no. 14 (S–/Vo1–) to enable the output(s).
Do not open the converters, or guarantee will be invalidated.
Due to high current values, some models provide two internally
parallel connected contacts for certain paths (pins 4/6, 8/10, 26/28
and 30/32). It is recommended to connect load and supply to both
female connector pins of each path in order to keep the voltage
drop across the connector pins at an absolute minimum and to
avoid overstress of the connector contacts with currents higher
than 8 A.
Make sure that there is sufficient airflow possible for convection
cooling. This should be verified by measuring the case
temperature when the converter is installed and operated in the
end-use application. The maximum specified case temperature
TCmax shall not be exceeded. See also Thermal Consid-erations.
If the end-product is to be UL certified, the temperature of the main
isolation transformer should be evaluated as part of the end-
product investigation.
Check for hazardous voltages before altering any connections.
Ensure that a converter failure (e.g., by an internal short-circuit)
does not result in a hazardous condition. See also: Safety of
Operator-Accessible Output Circuits.
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 20 of 33 www.power-one.com
Table 14: Isolation
Characteristic Input to Output to Output to Unit
case + output(s) case output
Electric Factory test >1 s 2.8 11.4 0.14 kVDC
strength AC test voltage equivalent to factory test 2.0 1.0 0.1 kVAC
test voltage
Insulation resistance at 500 VDC 300 2300 2100 MΩ
1In accordance with EN 50116 and IEC/EN 60950 subassemblies are pretested with 5.6 kVDC.
2Tested at 500 VDC.
Isolation
The electric strength test is performed in the factory as routine
test in accordance with EN 50116, IEC/EN 60950 and UL 1950
and should not be repeated in the field. Power-One will not
honor any guarantee claims resulting from electric strength field
tests.
LS-models Operated at Greater than 63 Hz
Above 63 Hz the earth leakage current may exceed 3.5 mA, the
maximum specified in IEC/EN 60950. The built-in Y-caps are
only approved for 100 Hz. Frequencies greater than 350 Hz
are only permitted for Vi 200 VAC.
Characteristic Class I Unit
LS1000, LS2000
Maximum earth Permissible according to IEC/EN 60950 3.5 mA
leakage current Specified value at 264 V, 50 Hz 1.43
Table 13: Leakage Currents for LS-models
Standards and Approvals
The converters are UL recognized according to UL 1950,
CAN/CSA C22.2 No. 950-95, and TÜV approved to IEC/EN
60950 standards.
The converters correspond to Class I equipment and have been
evaluated for:
Building in,
Basic insulation between input and case based on 250 V and
double or reinforced insulation or an earthed part between
input and output.
The use in a pollution degree 2 environment,
Connecting the input to a primary or secondary circuit which
is subject to a maximum transient rating of 2500 V.
The converters are subject to manufacturing surveillance in
accordance with the above mentioned UL and ISO 9001:2000
standards.
Railway Applications
The S Series converters have been designed according to
the Railway Standards EN50155 and EN50121. All boards
and components are coated with a protective lacquer.
Cleaning Agent s
In order to avoid possible damage, any penetration of
cleaning fluids must be prevented, since the power
supplies are not hermetically sealed.
Protection Degree
Condition: Female connector fitted to the converter.
IP 30: All models except those with option P and option
D, or V with potentiometer.
IP 20: All models exhibiting a potentiometer.
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 21 of 33 www.power-one.com
AC-DC
front
end
DC-DC
con-
verter
Mains Battery SELV
Earth connection
+
~
~
10044_082605
Max. 150 VAC or VDC for AK, BK
Max. 250 VAC or VDC for CK, DK, EK, FK, LK
Fuse
Fuse
Max. 150 VAC or VDC for AK, BK
Max. 250 VAC or VDC for CK, DK, EK, FK, LK
Table 15: Safety concept leading to a SELV output circuit
Conditions Front end Result DC-DC converter Result
Nominal Minimum required grade DC output voltage Minimum required Types Measures to achieve the Safety status
supply of insulation, to be pro- from the front end safety status of the specified safety status of of the DC-DC
voltage vided by the AC-DC front front end output the output circuit converter
end, including mains circuit output circuit
supplied battery charger
Mains Functional 100 V. The Primary circuit AS a) Double or reinforced SELV circuit
150 VAC (no electrical insulation nominal voltage BS insulation based on
between the mains between any the mains voltage
supply voltage and the output pin and (provided by the DC-DC
DC-DC converter input) earth is 150 V converter) AND
(AC or DC) b) earthed case 3
Mains 250 V The CS
250 VAC nominal voltage DS
between any ES
output pin and FS
earth is 250 V
(AC or DC)
Basic 250 V Unearthed AS a) Supplementary insulation,
hazardous voltage BS based on 250 VAC AND
secondary circuit CS b) double or reinforced
DS insulation 2(provided by
ES DC-DC converter) AND
FS c) earthed case 3
Earthed a) Double or reinforced
hazardous voltage insulation 2(provided by
secondary circuit the DC-DC converter) AND
b) earthed case 3
Double or reinforced 60 V SELV circuit
4
120 V TNV-3 circuit Basic insulation (provided
by the DC-DC converter) 4
1 The front end output voltage should match the specified input voltage range of the DC-DC converter.
2 Based on the maximum nominal output voltage from the front end.
3 The earth connection has to be provided by the installer according to the relevant safety standards, e.g. IEC/EN 60950.
4 Earthing of the case is recommended, but not mandatory.
Safety of Operator-Accessible Output Circuits
If the output circuit of a DC-DC converter is operator-accessible,
it shall be a SELV circuit according to safety standard
IEC/EN 60950.
The following table shows some possible installation
configurations, compliance with which causes the output circuit
of a DC-DC converter to be a SELV circuit according to IEC/EN
60950 up to a configured output voltage (sum of nominal voltages
if in series or +/– configuration) of 36 V.
Fig. 23
Schematic safety concept.
Use earth connection as per the table below.
Table 16: Safety concept leading to a SELV output circuit
Conditions AC-DC converter Installation Result
Nominal voltage Grade of insulation Measures to achieve the resulting Safety status of the AC-DC
between input and output safety status of the output circuit converter output circuit
provided by the AC-DC converter
Mains Double or reinforced Earthed case 1and installation SELV circuit
250 VAC according to the applicable standards
1The earth connection has to be provided by the installer according to the relevant safety standards, e.g. IEC/EN 60950.
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 22 of 33 www.power-one.com
If the output circuit of a AC-DC converter is operator-accessible,
it shall be a SELV circuit according to the related IEC/EN 60950
safety standards.
The following table shows a possible installation configuration,
compliance with which causes the output circuit of an LS Series
AC-DC converter to be a SELV circuit according to IEC/EN
60950 up to a configured output voltage (sum of nominal voltages
if in series or +/– configuration) of 36 V.
If the LS converters are used as DC-DC converters, please refer to
the previous section.
AC-DC
con-
verter
Mains SELV
Earth connection
+
~
~
10021
Fuse
Fuse
Fig. 24
Schematic safety concept. Use fuses and earth
connection as per: Installation Instructions and table:
Safety concept leading to a SELV output circuit.
Description of Options
Table 17: Survey of options
Option Function of Option Characteristics
-9 Extended operational ambient temperature range
T
A= –40 to 71 °C
E Electronic inrush current limitation circuitry Active inrush current limitation for CK, DK, EK
P Potentiometer for fine adjustment of output voltage Adjustment range +10/–60% of
V
o nom (R input not connected)
D 1Input and/or output undervoltage monitoring circuitry Safe data signal output (versions D0 - DD)
V 1, 2Input (and output) undervoltage monitoring circuitry ACFAIL signal according to VME specs (versions V0, V2, V3)
T Current sharing Interconnect T-pins if paralleling outputs (5 converters max.)
B1/B2 Cooling plate Replaces standard heat sink, allowing direct chassis-mounting
1Option D excludes Option V and vice versa.
2Only available for
V
o= 5.1 V.
Table 18: Inrush current characteristics with option E
(DC-DC converters)
Characteristics CS DS ES FS Unit
Vi nom, Io nom Input voltage 60 110 220 48 V
Iinr p Peak inrush 6.8 7.4 14.6 4.5 A
current
tinr Inrush current 18 14 16 22 ms
duration
Vi max, Io nom Input voltage 140 220 380 100 V
Iinr p Peak inrush 9.3 14.5 25.3 7.5 A
current
tinr Inrush current 20 14 12 23 ms
duration
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 23 of 33 www.power-one.com
Option -9: Extended Temperature Range
Option -9 extends the operational ambient temperature range
from –25 to 71 °C to 40 to 71 °C. The power supplies provide
full nominal output power with convection cooling. Option -9
excludes inrush current limitation by NTC.
Option E: Inrush Current Limiter
CS/DS/ES/FS/LS types may be supplemented by an electronic
circuit (option E, replacing the standard built-in NTC) to achieve
an enhanced inrush current limiting function. Option E is
mandatory for -9 models.
CS models fitted with option E and option D6 (input voltage
monitoring) meet the standard ETS 300132-2 for 48 VDC supply
voltage. Option D6 (externally adjustable via potentiometer from
36.0 to 40.5 V) is necessary to disable the converter at low input
voltages, avoiding an excessive input current. Option D6
threshold level should be adjusted to 44.0 - 50.0 V for 60 V
nominal supply systems (refer to the description of option D). The
D output can be connected directly to the inhibit input.
Note: Subsequent switch-on cycles at startup are limited to max.
10 cycles during the first 20 seconds (cold model) and then to
max. 1 cycle every 8 seconds.
Input Filter
Control
Converter
FET
Ci
RI
RS
10017_111105
Rectifier (only AC-DC models)
Fig. 25
Option E block diagram
Current limiting resistance = R
S
+ R
I= 15 Ω
(all models)
I [A]
Vi/RV
<30
t [ms]
Capacitor Ci
fully charged
Normal operation
(current limiting
circuit is fully
conducting)
0
0
Ii = Pi/Vi
11039_052605
Fig. 26
Inrush current with option E (DC-DC converters)
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 24 of 33 www.power-one.com
Table 19: Inrush current characteristics with option E (AC-DC converters)
Characteristics LS Unit
V
= 230 VAC min typ max
I
inr p Peak inrush current 25.3 A
t
inr Inrush current duration 35 50 ms
15
Ii [A]
10
5
0
–5
–10
–15
020 40 60 80
t [ms]
tinr
Capacitor C
i
fully charged
Normal operation
(FET fully conducting)
20
10065_102005
Fig. 27
Inrush current with option E
(LS models, Vi = 230 VAC, fi = 50 Hz, Po= Po nom)
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 25 of 33 www.power-one.com
Load
1
1
1
2
2
S+
Vo+
Vo–
S–
Vi+
Vi
T
Vi+
Vi
S+
Vo+
Vo–
S–
T
1
Max. 5 converters in parallel connection
11036_012006
Converter
Converter
Fig. 29
Paralleling of single-output models using option T with the
sense lines connected at the load
1Leads should have equal length and cross sections and should
run in the same cable loom.
2Diodes for redundant operation.
Vo+
Vo–
Vo+
Vo–
Load
Vo+
Vo–
11003_102005
Fig. 28
An example of poor wiring for connections in parallel
(unequal length of load lines)
Option T: Current Sharing
This option ensures that the output currents are
approximately shared between all paralleled converters,
hence increasing system reliability. To use this facility,
simply interconnect the T pins of all converters and make
sure that the reference pins for the T-pin (S- for the S1000
or Vo1– for S2000) are also connected together. The load
lines should have equal length and cross section to ensure
equal voltage drop s. Not more than 5 converters should be
connected in parallel. The R-pins should be left in an open-
circuit condition. If not, prior to paralleling the Vo1 outputs
should be individually adjusted within 1 to 2%. Parallel
connection of converters with option P is not
recommended.
Option P: Potentiometer
The potentiometer allows for an output voltage adjustment
in the range of +10/–60% of Vo nom. It is accessible
through a hole in the front cover. This feature enables
compensation of voltage drops across the connector and
wiring. Option P is not recommended if models are
connected in parallel.
In double-output models both outputs are influenced by the
potentiometer setting. If option P is fitted, the R-pin 16 is
not connected.
Note: If the output voltage is increased above Vo nom via the
R-input control, option P setting, remote sensing, or option T,
the output current(s) should be reduced accordingly so that
Po nom is not exceeded.
Load
Max. 5 converters in parallel connection
+–
Power bus
Vo2–
Vo2+
Vo1–
Vo1+
T
Vo2–
Vo2+
Vo1–
Vo1+
T
Converter
Converter
11037_012006
Fig. 30
Paralleling of double output models with the outputs
connected in series, and using option T in an application
with a power bus. Note that the signal at the T-pins is
referenced to Vo1-.
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 26 of 33 www.power-one.com
Option D: Undervoltage Monitor
The input and/or output undervoltage monitoring circuit operates
independently of the built-in input undervoltage lockout circuit. A
logic "low" (JFET output) or "high" signal (NPN output) is
generated at pin 20 as soon as one of the monitored voltages
drops below the preselected threshold level Vt. The return for
this signal is Vo1–. The D output recovers when the monitored
voltage(s) exceed(s) Vt +Vh. The threshold levels Vti and Vto
are either adjustable by a potentiometer, accessible through a hole
in the front cover, or factory adjusted to a fixed value specified by
the customer.
Option D exists in various versions D0 - DD as shown in the
following table.
Table 20: Undervoltage monitor functions
Output type Monitoring Minimum adjustment range Typical hysteresis
V
h[% of
V
t]
of threshold level
V
tfor
V
t min -
V
t max
JFET NPN
V
i
V
o1
V
ti
V
to
V
hi
V
ho
D1 D5 no yes - 3.5 - 40 V 1- 2.5 - 0.6
D2 D6 yes no
V
i min -
V
i max 1- 3.4 - 0.4 -
D3 D7 yes yes
V
i min -
V
i max 1(0.95 - 0.985
V
o1)23.4 - 0.4 "0"
D4 D8 no yes - (0.95 - 0.985
V
o1)2- "0"
D0 D9 no yes - 3.5 - 40 V 3- 2.5 - 0.6
yes no
V
i min -
V
i max 3, 4 - 3.4 - 0.4 -
yes yes
V
i min -
V
i max 3, 4 3.5 - 40 V 33.4 - 0.4 2.5 - 0.6
yes yes
V
i min -
V
i max 3, 4 (0.95 - 0.985
V
o1)23.4 - 0.4 "0"
-DDyesyes
V
i min -
V
i max 13.5 - 40 V 13.4 - 0.4 2.5 - 0.6
1 Threshold level adjustable by potentiometer
2 Fixed value tracking if
V
o1 is adjusted via R-input, option P or sense lines.
3 The threshold level is permanently adjusted according to customer specification ±2% at 25 °C. Any value within the
specified range is possible, but causes a new customer-specific type designation.
4 Adjusted at
I
o nom
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 27 of 33 www.power-one.com
NPN output (D5 - DD):
Pin 20 (D) is internally connected via the collector-emitter
path of an NPN transistor to Vo1+ or Vo+. VD <0.4 V
(logic low) corresponds to a monitored voltage level (Vi
and/or Vo1) > Vt+Vh. The current IDthrough pin 20
should not exceed 20 mA. This output is not protected
against external overvoltages. VDshould not exceed 40 V.
V
i,
V
o1 status D output,
V
D
V
ior
V
o1 <
V
t high, H,
I
D25 µA at
V
D= 40 V
V
iand
V
o1 >
V
t +
V
hlow, L,
V
D0.4 V at
I
D= 20 mA
JFET output (D0 - D4):
Pin 20 (D) is internally connected via the drain-source path
of a JFET (self-conducting type) to Vo1+ or Vo+.
VD 0.4 V (logic low) corresponds to a monitored voltage
level (Viand/or Vo1) <Vt. The current IDthrough the JFET
should not exceed 2.5 mA. The JFET is protected by a
0.5 W Zener diode of 8.2 V against external overvoltages.
V
i,
V
o1 status D output,
V
D
V
ior
V
o1 <
V
t low, L,
V
D0.4 V at
I
D= 2.5 mA
V
iand
V
o1 >
V
t+
V
hhigh, H,
I
D25 µA at
V
D= 5.25 V
Fig. 31
Option D1 - D0: JFET output, I
D
2.5 mA
Table 21: D-output logic signals
Version of D
V
i<<
V
tresp.
V
o<<
V
t
V
i>>
V
t+
V
hresp.
V
o>>
V
tConfiguration
D1, D2, D3, D4, D0 low high JFET
D5, D6, D7, D8, D9, DD high low NPN
Vo1+
Vo1–
D
V
D
I
D
R
p
Input
11007
Vo1+
Vo1–
D
V
D
I
D
R
p
Input
11006
Fig. 32
Option D5 - DD: NPN output, V
o1
40 V, I
D
20 mA
Threshold tolerances and hysteresis:
If Viis monitored, the internal input voltage after the input
filter is measured. Consequently, this voltage differs from
the voltage at the connector pins by the voltage drop ΔVti
across the input filter. The threshold levels of the D0 and
D9 options are factory-adjusted at nominal output current
Io nom and at TA= 25 °C. The value of ΔVti depends upon
the input voltage range (CS, DS, ..), threshold level Vt,
temperature and input current. The input current is a
function of the input voltage and the output power.
Fig. 33
Definition of V
ti, Δ
V
t i
and
Δ
V
hi
(JFET output)
ΔVti Vhi
VD low
VD
VD high
Vi
P
o
= P
o nom
P
o
= 0
P
o
= 0
Vti
P
o
= P
o nom
11021
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 28 of 33 www.power-one.com
D-signal with respect to input and output voltage versus time:
Fig. 34
Relationship between V
i
, V
o1
, V
D
, V
o1
/V
o nom
versus time
0
1
0.95
0
Vi [V DC]
0
t
t
t
tlow min4tlow min4thigh min
th1
Vti +Vhi
Vti
Input voltage failure Switch-on cycle Input voltage sagSwitch-on cycle and subsequent
input voltage failure
VD high
VD low
VD
0
JFET
NPN
t
Vo1
Vo1 nom
VD high
VD low
VD
tlow min4
th1
0
0
VD high
VD low
VD
0
JFET
NPN
Vo1
VD high
VD low
VD
tlow min4
Vto
3
Output voltage failure
0
ID high
ID low
ID
t
0
ID high
ID low
ID
t
t
t
t
3
2
33 33
Vo1 nom
Vto +Vho
Input voltage monitoring
Output voltage monitoring
11008
1 Hold-up time see:
Electrical Input Data
2 With output voltage monitoring, hold-up time
t
h= 0.
3 The signal will remain high if the D output is connected
to an external source.
4
t
low min = typically 130 ms.
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 29 of 33 www.power-one.com
Table 23: Undervoltage monitor functions
V output Monitoring Minimum adjustment range Typical hysteresis
V
h[% of
V
t]
(VME compatible) of threshold level
V
tfor
V
t min
- V
t max
V
i
V
o1
V
ti
V
to
V
hi
V
ho
V2 yes no
V
i min -
V
i max 13.4 - 0.4
V3 yes yes
V
i min -
V
i max 10.95 - 0.985
V
o1 23.4 - 0.4 "0"
V0 yes no
V
i min -
V
i max 3, 4 3.4 - 0.4
yes yes
V
i min -
V
i max 3, 4 0.95 - 0.985
V
o1 23.4 - 0.4 "0"
1 Threshold level adjustable by potentiometer.
2Fixed value between 95% and 98.5% of
V
o1 (tracking).
3Adjusted at
I
o nom.
4 Fixed value, resistor-adjusted (±2% at 25 °C) acc. to customer's specifications; individual type number is determined by Power-One.
Table 22: Available internal input capacitance and factory potentiometer setting of V
ti
with resulting hold-up time
Types AS BS FS CS DS ES LS Unit
C
i min 0.83 0.3 1.2 0.66 0.26 0.21 0.21 mF
V
t i 9.5 19.5 39 39 61 97 120 VDC
t
h0.1 0.1 5.3 1.9 1.8 4.3 6.4 ms
Option V: ACFAIL Signal (VME)
Available only for models with Vo= 5.1 V.
This option defines an undervoltage monitoring circuit for the
input and main output voltage. It generates an ACFAIL signal
(V signal) which conforms to the VME standard.
The low state level of the ACFAIL signal is specified at a sink
current of IV48 mA to VV0.6 V (open-collector output of an
NPN transistor). The pull-up resistor feeding the open-collector
output should be placed on the VME backplane.
After the ACFAIL signal has gone low, the VME standard
requires a hold-up time (th) of at least 4 ms before the 5.1 V
output drops to 4.875 V when the output is fully loaded. The
hold-up time is provided by the internal input capacitance.
Consequently, the working input voltage and the threshold level
(Vti) should be adequately above the minimum input voltage
(Vi min) of the converter so that enough energy is remaining in
the input capacitance. If the input voltage is below the required
level, an external hold-up capacitor (Ci ext) should be added.
Formula for threshold level for desired value of
t
h:
2 •
P
o• (
t
h+ 0.3 ms) • 100
V
ti = ––––––––––––––––––––– +
V
i min2
C
i min η
Formula for the external input capacitor:
2 •
P
o• (
t
h+ 0.3 ms) • 100
C
i ext = –––––––––––––––––––––– –
C
i min
η• (
V
ti 2
V
i min2)
where as:
C
i min = internal input capacitance [mF]
C
i ext = external input capacitance [mF]
P
o= output power [W]
η= efficiency [%]
t
h= hold-up time [ms]
V
i min = minimum input voltage [V] 1
V
ti = threshold level [V]
1Min. input voltage according to
Electrical Input Data
. For output voltages
V
o>
V
o nom, the minimum input voltage increases proportionally to
V
o/
V
o nom.
Remarks:
Option V2 and V3 can be adjusted by potentiometer to a threshold
level between Vi min and Vi max. A decoupling diode should be
connected in series with the input of AS - FS converters to avoid
the input capacitance discharging through other loads connected
to the same source voltage.
V
t+
V
h. The threshold level
V
ti is either adjustable by
potentiometer, accessible through a hole in the front cover,
or adjusted during manufacture to a determined customer
specified value.
Versions V0, V2, and V3 are available as shown below.
Option V operates independently of the built-in input
undervoltage lockout circuit. A logic "low" signal is generated at
pin 20 as soon as one of the monitored voltages drops below the
preselected threshold level
V
t. The return for this signal is Vo1–.
The V output recovers when the monitored voltage(s) exceed(s)
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 30 of 33 www.power-one.com
V output (V0, V2, V3):
Connector pin V is internally connected to the open collector of
an NPN transistor. The emitter is connected to Vo1- or Vo-.
VV0.6 V (logic low) corresponds to a monitored voltage level
(Viand/or Vo1) <Vt. The current IVthrough the open collector
should not exceed 50 mA. The NPN output is not protected
against external overvoltages. VVshould not exceed 60 V.
V
i,
V
o1 status V output,
V
V
V
ior
V
o1 <
V
t low, L,
V
V0.6 V at
I
V= 50 mA
V
iand
V
o1 >
V
t+
V
hhigh, H,
I
V25 µA at
V
V= 5.1 V
Fig. 35
Output configuration of options V0, V2, and V3
Vo1+
Vo1–
V
V
V
I
V
R
p
Input
11009
Threshold tolerances and hysteresis:
If Viis monitored, the internal input voltage is measured af ter the
input filter. Consequently, this voltage differs from the voltage at
the connector pins by the voltage drop DVti across the input
filter. The threshold level of option V0 is adjusted during
manufacture at Io nom and TA= 25 °C. The value of ΔVti
depends upon the input voltage range (AS, BS, etc.), threshold
level Vt, temperature and input current. The input current is a
function of input voltage and output power.
ΔVti Vhi
VV low
VV
VV high
Vi
P
o
= P
o nom
P
o
= 0
P
o
= 0
Vti
P
o
= P
o nom
11023
Fig. 36
Definition of V
ti
, ΔV
ti
and V
hi
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 31 of 33 www.power-one.com
3
5.1 V
4.875 V
0
Vi [VDC]
0
t
t
Vti + Vhi
Vti
Input voltage failure Switch-on cycle Input voltage sagSwitch-on cycle and subsequent
input voltage failure
VV high
VV low
VV
0
V2
t
Vo1
0
VV high
VV low
VV
0
V2
Vi
Vti
4
Output voltage failure
0
VV high
VV low
VV
3
Vti + Vhi
tlow min 2 tlow min 2
tlow min 2
33
4
4
VV high
VV low
VV
0
V3
t
3
tlow min 2
tlow min 2
33
th 1
2.0 V
th 1
4
3
4
tlow min 2
V3
5.1 V
4.875 V
0
Vo1
2.0 V
Input voltage monitoring
Output voltage monitoring
11010
t
t
t
t
Fig. 37
Relationship between V
i
, V
o1
, V
V
, I
V
and V
o1
/V
o nom
versus time.
1 VME request: minimum 4 ms
2
t
low min = 40 - 200 ms, typically 80 ms
3
V
Vlevel not defined at
V
o1 <2.0 V
4 The V signal drops simultaneously with the output voltage. If
the pull-up resistor
R
Pis connected to Vo1+. The V signal
remains high if
R
Pis connected to an external source.
Options B1/B2: Cooling Plate
Where a cooling surface is available, we recommend the use
of a cooling plate (option B1) instead of the standard heat sink.
The mounting system should ensure sufficient cooling
capacity to guarantee that the maximum case temperature
T
C max is not exceeded. The cooling capacity is calculated by:
(100% – η)
P
Loss = –––––––––– •
V
o
I
o
η
Efficiency ηsee:
Model Selection
Elongated case for 220 mm rack depth: Option B2
Dimensions see
Mechanical Data
Chassis mounting brackets CMB-S
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 32 of 33 www.power-one.com
Accessories
A variety of electrical and mechanical accessories are available
including:
Front panels for 19" DIN-rack: Schroff 16 TE /3U,
[HZZ00831] and 16 TE /6U [HZZ00832], or Intermas
16 TE /3U [HZZ00731].
Mating H15/H15 S4 connectors with screw, solder, fast-on or
press-fit terminals.
Cable connector housing: Screw version [HZZ00141] or
retention clip version [HZZ00142].
Connector retention clips (2x) [HZZ01209].
Connector retention brackets CRB [HZZ01216].
Coding clips for connector coding [HZZ00202].
Chassis mounting plate CMB-S [HZZ00616] for fastening to a
chassis with only front access.
DIN-rail mounting assembly DMB-K/S [HZZ00615].
Wall-mounting plate K02 [HZZ01213] for models with option
B1.
Additional external input or output filters.
Battery temperature sensor [S-KSMH...] for use of the
converter as a battery charger. Different battery charact-
eristics can be selected.
For additional accessory product information, see the accessory
data sheets listed with each product series or individually at
www.power-one.com through the following menus: “Select
Products”, “Download Data Sheets & Applications Notes”, or
with each model in the product overviews.
H15 female connector,
code key system
Front panels
DIN mounting assembly DMB-K/S
Connector retention bracket CRB
Connector retention clip
NUCLEAR AND MEDICAL APPLICATIONS - Power-One products are not designed, intended for use in, or authorized for use as critical components
in life support systems, equipment used in hazardous environments, or nuclear control systems without the express written consent of the respective
divisional president of Power-One, Inc.
TECHNICAL REVISIONS - The appearance of products, including safety agency certifications pictured on labels, may change depending on the date
manufactured. Specifications are subject to change without notice.
20 to 30 Ncm
S Series Data Sheet
100 Watt AC-DC and DC-DC Converters
APR 26, 2006 revised to SEP 25, 2006 Page 33 of 33 www.power-one.com
EC Declaration of Conformity
We
Power-One AG
Ackerstrasse 56, CH-8610 Uster
declare under our sole responsibility that K and S Series AC-DC and DC-DC
converters carrying the CE-mark are in conformity with the provisions of the Low
Voltage Directive (LVD) 73/23/EEC of the European Communities.
Conformity with the directive is presumed by conformity wih the following
harmonized standards:
EN 61204:1995 (= IEC 61204:1993, modified)
Low-voltage power supply devices, DC output - Perfomance characteristics
and safety requirements
EN 60950:2000 (= IEC 60950:2000)
Safety of information technology equipment
The installation instructions given in the data sheet describe correct installation
leading to the presumption of conformity of the end product with the LVD. All K
and S Series AC-DC and DC-DC converters are components, intended
exclusively for inclusion within other equipment by an industrial assembly
operation or by professional installers. They must not be operated as stand alone
products.
Hence conformity with the Electromagnetic Compatibility Directive 89/336/EEC
(EMC Directive) needs not to be declared. Nevertheless, guidance is provided in
most product application notes on how conformity of the end product with the
indicated EMC standards under the responsibility of the installer can be achieved,
from which conformity with the EMC directive can be presumed.
Uster, 24 May 2005 Power-One AG
Rolf Baldauf Johann Milavec
VP Engineering Director Projects and IP