ACDC 175 Watts CLC Series xppower.com * High Efficiency Resonant Topology * Medical Safety Approvals (M Versions) * 12 V Fan Output * Remote Sense * 5V Standby Option * Remote On/Off & Power Good Signal Options * 3 Year Warranty Specification Input General * 85-264 VAC (120-370 VDC), derate output power 10% <90 VAC Input Frequency * 47-63 Hz Input Current * 3.0 A typical at 115 VAC, full load 1.5 A typical at 230 VAC, full load Inrush Current * 40 A max at 230 VAC, cold start at 25 C Power Factor * EN61000-3-2, class A Earth Leakage Current * 475 A 264 VAC at 60 Hz, 230 A maximum at 264 VAC at 60 Hz (-M) Input Protection * Internal T5 A 250 V fuse in line Internal T5 A 250 V fuse in line and neutral (-M) Input Voltage Output Output Voltage Output Voltage Trim Initial Set Accuracy Minimum Load * * * * Start Up Delay * Start Up Rise Time Hold Up Time Drift Line Regulation Load Regulation Over/Undershoot Transient Response * * * * * * * Ripple & Noise * Overvoltage Protection Overload Protection Short Circuit Protection Temperature Coefficient Remote Sense Remote On/Off (Inhibit/Enable) (Option -A) * * * * 12-48 V (see tables) 5% 1% V1, 5% V2, 3% V3 0.1 A required on V1 to maintain regulation of V2 1.5 s typical, see longform datasheet for more details 5 ms typical 16 ms min at 115 VAC 0.2% after 20 min warm up 0.5% max 1% V1, 5% V2 & V3 max 5% typical 4% max. deviation, recovery to within 1% in 500 s for a 50-75-50% load change 1% pk-pk V1, others 2%, 20 MHz bandwidth 115-140% Vnom, recycle input to reset 110-150% V1 only Continuous trip and restart (hiccup mode) 0.05%/C * Compensates for 0.5 V total voltage drop * Uncommitted isolated optocoupler diode, powered diode inhibits V1 & V2 Efficiency Isolation Switching Frequency Signals (Option -A) MTBF Power Density * 87% typical * 3000 VAC Input to Output 4000 VAC Input to Output (-M) 2 x MOPP 1500 VAC Input to Ground 1 x MOPP 500 VAC Output to Ground * 70 kHz typical * Power OK - open collector, Remote On/Off, 5 V Standby * 390 kHrs per MIL-HDBK-217F at 25 C, GB * 9.0 W/in3 Environmental Operating Temperature * 0 C to +70 C derate linearly from +50 C at 2.5%/C to 50% load at +70 C Cooling * Forced-cooled >10 CFM Operating Humidity * 95% RH, non-condensing Storage Temperature * -40 C to +85 C Operating Altitude * 3000 m Shock * 30 g pk, half sine, 6 axes Vibration * 2 g rms, 5 Hz to 500 Hz, 3 axes EMC & Safety Low Voltage PSU EMC * EN61204-3, high severity level Emissions * EN55011/22 level B conducted EN55011/22 level A radiated Harmonic Currents * EN61000-3-2, class A Voltage Flicker * EN61000-3-3 Radiated Immunity * EN61000-4-3, level 3 Perf Criteria A EFT/Burst * EN61000-4-4, level 3 Perf Criteria A Surge * EN61000-4-5, installation class 3 Perf Criteria A Conducted Immunity * EN61000-4-6, level 3 Perf Criteria A Dips & Interruptions * EN61000-4-11, 30% 10 ms, 60% 100 ms, 100% 5000 ms Perf Criteria A, B, B EN60601-1, 30% 500ms, 60% 100ms, 100% 10ms, 100% 5000ms (-M) Perf Criteria A, A (with 50% load), A, B Safety Approvals * EN60601-1, ANSI/AAMI ES60601-1, CSA22.2 No.60601-1 per cUL, Including Risk Management, EN60950-1, UL60950-1 Output Power(1) 175 175 175 175 Output Voltage V1 W W W W 12.0 24.0 28.0 48.0 Fan Output V2 Output Current V1 VDC VDC VDC VDC 13.90 6.90 6.25 3.50 A A A A 12.0 12.0 12.0 12.0 V/0.5 V/0.5 V/0.5 V/0.5 A A A A Standby Supply V3 (optional) 5.0 V/0.5 A 5.0 V/0.5 A 5.0 V/0.5 A 5.0 V/0.5 A Model Number(2,3) CLC175US12 CLC175US24 CLC175US28 CLC175US48 Notes 1. 10 CFM airflow. 2. For medical version add, suffix `-M' to model number. 3. For 5 V standby (V3), Power OK & Inhibit, add suffix `-A' to model number. 4. For cover with Top Fan assembly add `-TF' to model number e.g. CLC175US12-TF, CLC175US12-ATF, CLC175US12-MTF or CLC175US12-MATF. Mechanical Details 5.00 (127.0) 0.22 (5.7) 1.30 (33.0) 4.55 (115.6) 0.20 (5.1) Input Connector J1 Pin 1 Line Pin 2 Neutral 0.25"Faston Earth 3.00 (76.2) 1.90 (48.3) 0.61 (15.6) 1.11 (28.3) 0.23 (5.7) 0.20 (5.1) 4 x o0.156 (3.96) Mounting Holes o0.312 (7.92) Clearance Top & Bottom Fan Cover J1 mates with Molex housing 09-50-1031 and Molex series 5194 crimp terminals. 2.50 (63.6) 2.55 (64.8) 0.25 Faston Ground Tab V Adj. 0.14 (3.5) Pin Pin Pin Pin Pin Pin Pin Pin 0.19 (4.8) SMD component height 0.18 (4.6) 5.50 (139.7) Output Connector J2 1 +V1 2 +V1 3 +V1 4 +V1 5 RTN 6 RTN 7 RTN 8 RTN J2 mates with Molex housing 09-50-1081 and Molex series 5194 crimp terminals. Input Connector 3.50 (88.9) 0.25 (0.6) Faston Ground Terminal Output Connector 2.00 (50.7) Signal Connector J3 Pin 1 +5V Standby Pin 2 Logic GND Pin 3 Logic GND Pin 4 Power OK Pin 5 Inhibit HI Pin 6 Inhibit LO Pin 7 +Sense Pin 8 -Sense Pin 9 +Vout Pin 10 -Vout J3 mates with JST housing PHDR-10VS and JST SPHD001T-P0.5 crimp terminals. 4 x M3 x 0.5 THD 0.16 (4.0) Max Screw Penetration 1.97 (50.0) 0.77 (19.5) 0.39 (9.9) Fan Connector J4 Fan +(12V) Fan - J4 mates with Molex housing 22-01-1024 and Molex series 5103 crimp terminals. 4.724 (120.0) Notes 2 x M3 x 0.5 THD 0.16 (4.0) Max Screw Penetration 0.39 (9.9) Pin 1 Pin 2 0.98 (25.0) 1. All dimensions in inches (mm). Tolerance .xx = 0.02 (0.50); .xxx = 0.01 (0.25) 2. Weight: 0.7 lbs (317 g) approx. 3. For thermal derating, please refer to longform datasheet. 4.72 (120.0) 21-May-12 ACDC CLC175 Models and Ratings