ecofast
ECOFAST System Manual 11/2004
.
System
ECOFAST
Manual
Order Number
3RK1703-0BB18-0AA1
Edition 11/2004
GWA 4NEB 950 5228-02
System Description 1
Product Family 2
Installation Guidelines 3
Installation 4
Connection 5
Commisioning 6
Technical Data 7
Dimension Drawings 8
Order Numbers 9
Questions and Answers A
ECOFAST Pilot Projects B
Glossary
Safety Guidelines
This manual contains notices which you should observe to ensure your own personal safety as well as to avoid prop-
erty damage. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol,
notices referring only to property damage are not designated by a safety alert symbol. Depending on the danger
level, the warnings will be displayed in descending sequence as follows.
When several danger levels apply, the notices of the highest level (lower number) are always displayed. If a notice
refers to personal damages with the safety alert symbol, another notice may be added as a warning of potential prop-
erty damage.
Qualified Personnel
The device/system may only be set up and operated in conjunction with this documentation. Only qualified person-
nel should be allowed to install and work on the equipment. Qualified persons are defined as persons who are au-
thorized to commission, ground and tag circuits, equipment and systems in accordance with established safety
practices and standards.
Intended Use
Please note the following:
Trademarks
All designations marked with ® are registered trademarks of Siemens AG. Other designations in this documentation
might be trademarks which, if used by third parties for their purposes, might infringe upon the rights of the propri-
etors.
Danger
indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Warning
indicates an imminently hazardous situation which, if not avoided, could result in death or serious injury.
Caution
used with the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in minor
or moderate injury.
Caution
used without safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in
property damage.
Notice
indicates a potential situation which, if not avoided, may result in an undesirable result or state.
Warning
This device and its components may only be used for the applications described in the catalog or technical descrip-
tion, and only in connection with devices or components from other manufacturers approved or recommended by
Siemens.
This product can only function correctly and safely if it is transported, stored, set up and installed correctly, and ope-
rated and maintained as recommended.
Copyright Siemens AG 2004 All rights reserved.
The reproduction, transmission or use of this document or its contents is not permitted wit-
hout express written authority. Offenders will be liable for damages. All rights, including
rights created by patent grant or registration of a utility model or design, are reserved.
Disclaimer of Liability
We have checked the contents of this manual for agreement with the hardware and software
described. Since deviations cannot be precluded entirely, we cannot guarantee full agree-
ment. However, the data in this manual are reviewed regularely and any necessary correc-
tions included in subsequent editions. Suggestions for improvement are welcomed.
Siemens AG
Automation and Drives
Postfach 4848, D-90327 Nürnberg
© Siemens AG 2004
Subject to change without prior notice
Siemens Aktiengesellschaft
ECOFAST System Manual
GWA 4NEB 950 5228-02 iii
Introduction and Notes on Using the Manual
Purpose of the manual
This manual is intended to serve as a reference document. The information it contains will
help you operate the ECOFAST system with the PROFIBUS-DP and AS-Interface field
buses.
Topics
This manual consists of instruction chapters and reference chapters. It covers the following
topics, among others:
System Description
Product Family
Installation Guidelines
Installation
Connections
Commisioning
Technical Data
Dimension Drawings
Order Numbers
Questions and Answers
ECOFAST Pilot Projects
•Glossary
Note
Specifications
This manual only describes shared components of the ECOFAST system.
Notice
Important information requiring particular attention is enclosed between two horizontal lines.
ECOFAST System Manual
iv GWA 4NEB 950 5228-02
Service and Support
Technical Assistance: Telephone: +49 (0) 911-895-5900 (8:00 - 17:00 CET)
Fax: +49 (0) 911-895-5907
E-mail: technical-assistance@siemens.com
Internet: www.siemens.de/lowvoltage/technical-assistance
Technical Support: Telephone: +49 (0) 180 50 50 222
Correction sheet
A correction sheet is attached at the end of this manual. Please enter any suggestions for
improvements, additions or corrections there and return the sheet to us. In doing so, you can
help us improve the next edition.
ECOFAST System Manual
GWA 4NEB 950 5228-02 v
Contents
Introduction and Notes on Using the Manual.................................................................................................. iii
1 ECOFAST System Description ............................................................................................................. 1-1
1.1 Philosophy of the ECOFAST System ....................................................................................... 1-1
1.1.1 Requirements Specified for Innovative Automation and Drive Systems .................................. 1-2
1.1.2 Desina and Field Bus Certificates ............................................................................................ 1-3
1.1.3 ECOFAST certified and ECOFAST integrated ......................................................................... 1-3
1.2 ECOFAST ES Software............................................................................................................ 1-4
1.3 The ECOFAST Basic System................................................................................................... 1-4
1.3.1 Topology of the Network ........................................................................................................... 1-5
1.3.2 Overview of Interfaces .............................................................................................................. 1-6
2 Product Family ....................................................................................................................................... 2-7
2.1 Power & Control Module (PCM) ............................................................................................... 2-7
2.1.1 Tasks of the Power & Control Module (PCM) ........................................................................... 2-7
2.1.2 Device Versions ........................................................................................................................ 2-8
2.1.3 PCM Order Numbers ................................................................................................................ 2-9
2.2 Alternative Power Supply ....................................................................................................... 2-10
2.2.1 Simple Energy Unit (SEU) ...................................................................................................... 2-10
2.2.2 ET 200S Motor Starter ............................................................................................................ 2-12
2.3 Power Tee Clamp Connector ................................................................................................. 2-13
2.4 Hybrid Field Bus Connections ................................................................................................ 2-15
2.5 Data Tee Plug Connector ....................................................................................................... 2-17
2.6 Discriminating Module and Maintenance Switch .................................................................... 2-18
2.6.1 Discriminating Module ............................................................................................................ 2-18
2.6.2 Maintenance Switch with M12 Connector .............................................................................. 2-19
3 Installation Guidelines ......................................................................................................................... 3-21
3.1 Installation Guidelines for PROFIBUS-DP with ECOFAST Hybrid Field Bus Cable .............. 3-21
3.2 Installation Guidelines for PROFIBUS-DP with ECOFAST Hybrid Field Bus Cable
(Fiber-optic Conductors)......................................................................................................... 3-22
3.3 Guidelines for PROFIBUS-DP Standard Cables .................................................................... 3-24
3.3.1 Potential Equalization ............................................................................................................. 3-24
3.3.2 Cable Shielding ...................................................................................................................... 3-25
3.4 PNO Installation Guidelines.................................................................................................... 3-27
3.5 Power Bus Installation Versions ............................................................................................. 3-28
3.5.1 Unassembled set-up with power tee clamp connector and power cable ................................ 3-28
3.5.2 Connecting Consumers with a Spur Cable ............................................................................. 3-29
3.5.3 ET 200X Sub-Segmente with EM 300 Motor Starter .............................................................. 3-30
3.5.4 Possible Power Distribution with Discriminating Modules ...................................................... 3-32
ECOFAST System Manual
vi GWA 4NEB 950 5228-02
3.5.5 Line Protection in Power Bus Segment for Motor Starters Without Thermal Motor Model
(Installation in the Vicinity of the Motor) .................................................................................. 3-33
3.6 Installation Versions for Switching Devices and Control Circuit Devices................................ 3-35
4 Installation .............................................................................................................................................. 4-1
4.1 Power & Control Module........................................................................................................... 4-1
4.1.1 Installation of the IP65 Version ................................................................................................. 4-1
4.1.2 Installation of the Cabinet Installation Version (IP00) ............................................................... 4-2
4.2 Alternative Power supply .......................................................................................................... 4-3
4.2.1 Simple Energy Unit (SEU) ........................................................................................................ 4-3
4.2.2 ET 200S Motor Starter .............................................................................................................. 4-3
4.3 Power Tee Clamp Connector ................................................................................................... 4-4
4.4 Hybrid Field Bus Connections .................................................................................................. 4-5
4.5 Discriminating Module and Maintenance Switch ...................................................................... 4-6
4.5.1 Discriminating Module .............................................................................................................. 4-6
4.5.2 Maintenance Switch .................................................................................................................. 4-7
5 Connections ........................................................................................................................................... 5-1
5.1 Power & Control Module........................................................................................................... 5-1
5.1.1 Connections of the IP65 Version .............................................................................................. 5-1
5.1.2 Connections of the Cabinet Installation Version ....................................................................... 5-3
5.2 Alternative Power Supply.......................................................................................................... 5-6
5.2.1 Connections of the Simple Energy Unit (SEU) ......................................................................... 5-6
5.2.2 ET 200S Motor Starter .............................................................................................................. 5-6
5.3 Power Tee Clamp Connector ................................................................................................... 5-7
5.4 Hybrid Field Bus Connections .................................................................................................. 5-8
5.5 Data Tee Plug Connector ....................................................................................................... 5-14
5.5.1 Pin Assignment ....................................................................................................................... 5-14
5.6 Discriminating Module and Maintenance Switch .................................................................... 5-15
5.7 General Wiring and Interfaces................................................................................................ 5-16
5.7.1 Rules for Wiring ...................................................................................................................... 5-16
5.7.2 Power Cables, Preassembled at One End ............................................................................. 5-17
5.7.3 AS-i Interface .......................................................................................................................... 5-21
6 Commissioning ...................................................................................................................................... 6-1
6.1 Power & Control Module........................................................................................................... 6-1
6.1.1 Diagnostics ............................................................................................................................... 6-2
6.2 Alternative Power Supply.......................................................................................................... 6-3
6.2.1 Simple Energy Unit (SEU) ........................................................................................................ 6-3
6.2.2 ET 200S motor starter .............................................................................................................. 6-3
6.3 Hybrid Field Bus Connections .................................................................................................. 6-4
6.3.1 Passive Hybrid Field Bus Connection for Supply ..................................................................... 6-5
6.3.2 Passive Hybrid Field Bus Connection for Conducting .............................................................. 6-6
6.3.3 Active Hybrid Field Bus Connection for Supply ........................................................................ 6-7
ECOFAST System Manual
GWA 4NEB 950 5228-02 vii
6.3.4 Active Hybrid Field Bus Connection for Conducting ................................................................. 6-8
6.3.5 Cascading of the Active Hybrid Field Bus Connections ........................................................... 6-9
6.3.6 Power Supply of the Bus Terminating Connector ..................................................................... 6-9
6.3.7 Active Hybrid Field Bus Connection for Supply ...................................................................... 6-10
6.3.8 Active Hybrid Field Bus Connection for Supply ...................................................................... 6-11
6.3.9 Conveyor Section With Hybrid Field Bus Connections for Supply and Conducting ............... 6-12
6.3.10 Installation System with PROFIBUS-DP - Cu ......................................................................... 6-13
6.3.11 PROFIBUS-DP – Fiber-optic Cable ........................................................................................ 6-14
6.3.12 PROFIBUS-DP (Cu) and Passive Hybrid Field Bus Connections with 2 Separate
Power Supplies ....................................................................................................................... 6-15
6.3.13 PROFIBUS-DP (Cu) and Active Hybrid Field Bus Connections with 2 Separate
Power Supplies ....................................................................................................................... 6-16
6.3.14 PROFIBUS-DP CU and Active Hybrid Field Bus Connections with 2 Separate
Data Supplies ......................................................................................................................... 6-17
6.4 Discriminating Module and Maintenance Switch .................................................................... 6-18
7 Technical Data ........................................................................................................................................ 7-1
7.1 Power & Control Module........................................................................................................... 7-1
7.1.1 IP65 Version ............................................................................................................................. 7-1
7.1.2 IP00 Version (Control Cabinet Version) ................................................................................... 7-4
7.2 Alternative Power Supplies....................................................................................................... 7-6
7.2.1 Simple Energy Unit (SEU) ........................................................................................................ 7-6
7.2.2 ET 200S Motor Starter .............................................................................................................. 7-6
7.3 Hybrid Field Bus Connections .................................................................................................. 7-7
7.4 Data Tee Plug Connector ......................................................................................................... 7-8
7.5 Discriminating Module ............................................................................................................ 7-10
8 Dimension Drawings ............................................................................................................................. 8-1
8.1 Power & Control Module........................................................................................................... 8-1
8.1.1 IP65 Version ............................................................................................................................. 8-1
8.1.2 IP00 Version (Control Cabinet Version) ................................................................................... 8-2
8.2 Alternative Power Supplies....................................................................................................... 8-3
8.2.1 Simple Energy Unit (SEU) ........................................................................................................ 8-3
8.2.2 ET 200S Motor Starter .............................................................................................................. 8-5
8.3 Power Tee Clamp Connector ................................................................................................... 8-6
8.4 Hybrid Field Bus Connections .................................................................................................. 8-7
8.5 Data Tee Plug Connector ......................................................................................................... 8-8
8.6 Discriminating Module and Maintenance switch....................................................................... 8-9
9 Order Numbers ....................................................................................................................................... 9-1
9.1 Motor Starters (Reversing Starters).......................................................................................... 9-1
9.2 Motor Connection Cables ......................................................................................................... 9-2
9.3 Power Cables ........................................................................................................................... 9-3
9.4 Power & Control Modules (Infeed Modules)............................................................................. 9-4
ECOFAST System Manual
viii GWA 4NEB 950 5228-02
9.5 Simple Energy Unit (SEU) ........................................................................................................ 9-4
9.6 Discriminating Modules............................................................................................................. 9-5
9.7 Maintenance Switch.................................................................................................................. 9-5
9.8 Hybrid Field Bus Cables ........................................................................................................... 9-5
9.9 AS-Interface Shaped Cable...................................................................................................... 9-6
9.10 Hybrid Field Bus Connections .................................................................................................. 9-7
9.11 Connectors ............................................................................................................................... 9-7
9.12 Project Engineering Software and Documentation................................................................... 9-9
9.13 Tools, Connector Sets, Configuration..................................................................................... 9-10
A Questions and Answers ........................................................................................................................A-1
A.1 Frequently Asked Questions..................................................................................................... A-1
B ECOFAST Pilot Projects ........................................................................................................................B-1
B.1 Production Line for SIRIUS 2 - Siemens Cham........................................................................ B-1
B.2 Configuration in the Automotive Industry - Production Planning .............................................. B-4
Glossary
ECOFAST System Manual
GWA 4NEB 950 5228-02 ix
Tables
Table 2-1: PCM device versions...................................................................................................................... 2-9
Table 2-2: Device versions: Simple Energy Unit............................................................................................ 2-11
Table 2-3: Versions of power tee clamp connectors...................................................................................... 2-13
Table 2-4: Sealing sets for power tee clamp connectors............................................................................... 2-13
Table 2-5: Hybrid field bus connection versions ............................................................................................ 2-16
Table 2-6: Discriminating module versions.................................................................................................... 2-19
Table 3-1: Permissible line length of a bus segment based on the baud rate ............................................... 3-22
Table 3-2: Permissible line lengths in the optical PROFIBUS-DP network.................................................... 3-23
Table 4-1: Installing the PCM, IP65 Version.................................................................................................... 4-1
Table 4-2: Installing the PCM, Cabinet Installation Version............................................................................. 4-2
Table 4-3: Installing the power tee clamp connector ....................................................................................... 4-4
Table 4-4: Installing the hybrid field bus connection........................................................................................ 4-5
Table 4-5: Required components..................................................................................................................... 4-6
Table 4-6: Installing the discriminating module................................................................................................ 4-7
Table 5-1: Pin assignment of the Han Q4/2 pin/socket.................................................................................... 5-3
Table 5-2: Pin assignment of the hybrid field bus connection.......................................................................... 5-3
Table 5-3: Wiring of the PCM........................................................................................................................... 5-4
Table 5-4: Stripped lengths, cross-sections, terminal assignment................................................................... 5-5
Table 5-5: Connections for passive hybrid field bus connection (IP20 side) ................................................. 5-10
Table 5-6: Connections for active hybrid field bus connection (IP20 side) .................................................... 5-10
Table 5-7: Wiring the hybrid field bus connection .......................................................................................... 5-11
Table 5-8: Wiring of the Fast Connect Block ................................................................................................. 5-11
Table 5-9: Stripped lengths, cross-sections, terminal assignments............................................................... 5-13
Table 5-10: Pin assignment of the Han Q4/2 pin/socket.................................................................................. 5-15
Table 5-11: Rules for wiring............................................................................................................................. 5-17
Table 5-12: Preparing connecting leads with Han Q4/2 .................................................................................. 5-20
Table 6-1: Sequence of steps for commissioning the PCM, IP65 version....................................................... 6-1
Table 6-2: Sequence of steps for commissioning the PCM, control cabinet version....................................... 6-1
Table 6-3: Diagnostics - missing voltages ....................................................................................................... 6-2
Table 6-4: Diagnostics - signal states.............................................................................................................. 6-3
Table 6-5: Procedure for commissioning the hybrid field bus connection........................................................ 6-4
Table 6-6: Diagnostics for active hybrid field bus connections ........................................................................ 6-4
Table 6-7: Sequence of steps for commissioning the discriminating module/maintenance switch................ 6-18
ECOFAST System Manual
xGWA 4NEB 950 5228-02
ECOFAST System Manual
GWA 4NEB 950 5228-02 1-1
ECOFAST System Description 1
1.1 Philosophy of the ECOFAST System
ECOFAST - An integrated connection system for data and power on the field level
The ECOFAST system (Energy and Communication Field Installation System) sets new stan-
dards whenever machines and plants need to be equipped with automation, control & distri-
bution and drive technology. The central elements of the ECOFAST philosophy are extensive
decentralization and modularization of the installation system and comprehensive diagnostics
on the component level.
ECOFAST links all components of an automation system together using an integrated con-
nection technique for data and power that complies with the high IP65 degree of protection.
ECOFAST is thus an integral part of "Totally Integrated Automation" and open from the point
of view of both manufacturers and users.
Fig. 1-1: Typical components of an automation system
ELMO pump
SIMATIC S7
COMBIMASTER -
Motor/converter unit ELMO-G side-channel compressor
ECOFAST -
Motor/starter unit
SIMATIC ET200X -
Components
ECOFAST System Description
Philosophy of the ECOFAST System
ECOFAST System Manual
1-2 GWA 4NEB 950 5228-02
1.1.1 Requirements Specified for Innovative Automation and Drive Systems
Short phases for offering, planning and configuring machines and plants
Rapid installation and assembly
Quick and easy commissioning
High system availability
Short phases for offering, planning and configuring machines and plants
Modular planning process for machines and plants
Offers prepared by combining prefabricated modules
Use of CAD/CAE macros
Use of standardized bus systems such as PROFIBUS-DP and AS-Interface
Rapid installation and assembly
Cabinetless installation systems with a high degree of protection
Use of prefabricated and tested functional units
Smaller system footprint
Rapid installation on site
Standardized connection method for power and data lines
Quick and easy commissioning
Potential fault sources reduced to a minimum thanks to standardized connectors
Comprehensive diagnostics on the device and over the bus
Improved EMC because the contact unit and the drive are linked together directly
High system availability
Shorter downtimes because devices can be replaced quickly and easily
No need to interrupt the power and field buses in order to replace a device
Automatic parameterization if a device is replaced
Comprehensive status and diagnostic information
Transfer of operating parameters, such as current values or status signals
ECOFAST System Manual
GWA 4NEB 950 5228-02 1-3
ECOFAST System Description
Philosophy of the ECOFAST System
1.1.2 Desina and Field Bus Certificates
Fig. 1-2: Desina and Field Bus Certificates
Advantages
Common connection method for all modules
PROFIBUS-DP connected using Han Brid connectors
AS-Interface connected using the insulation displacement method
Power connected with HAN Q4/2 connectors
Recommended by Profibus International (PNO) and
Verein Deutscher Werkzeugfabriken VDW (DESINA)
1.1.3 ECOFAST certified and ECOFAST integrated
Fig. 1-3: ECOFAST certified and ECOFAST integrated certificates
ECOFAST certified
The new “ECOFAST certified” certificate, which is assigned by an accredited test laboratory,
guarantees reliable planning. It confirms that devices from different manufacturers are com-
patible with ECOFAST specifications.
ECOFAST integrated
Another user-friendly and time-saving feature. Plans and quantity/parts lists are created along
with the entire system documentation for ECOFAST ES.
Using an export function, they can then be easily integrated for further CAD processing. In
addition to Siemens components, devices from other manufacturers can also be integrated in
this configuration tool. Their integration and conformity is confirmed by the “ECOFAST inte-
grated” certificate.
ECOFAST System Description
ECOFAST ES Software
ECOFAST System Manual
1-4 GWA 4NEB 950 5228-02
1.2 ECOFAST ES Software
The ECOFAST ES configuration tool supports power-engineering system design with the fol-
lowing range of functions:
Graphical configuration of the consumers, cables, and switching/protection functions
Power bus dimensioning by automatically determining cable cross-sections and automatic
dimensioning of the switching/protection elements
Power-engineering design and testing according to the relevant standards and today’s
generally accepted practices
Creation of documentation: circuit diagram of the power bus, quantity/parts lists
1.3 The ECOFAST Basic System
Fig. 1-4: The ECOFAST basic system
Operator control
and monitoring
e. g. OP 27
Motor starter
motor
plugged in
IP20 component
e. g.
SIMOCODE-DP
Power & Control
module (PCM)
ET 200X
COMBIMASTER
MM 411
Engineering software
ECOFAST ES
ECOFAST System Manual
GWA 4NEB 950 5228-02 1-5
ECOFAST System Description
The ECOFAST Basic System
1.3.1 Topology of the Network
Block diagram
The block diagram below shows a possible topology of the ECOFAST network:
Fig. 1-5: Block diagram of the network topology
Power & control module (PCM)
Supplies power up to 690 V
Generates 24 V for interfaces to the field bus and the sensors
Generates 24 V for actuators
(can be switched by EMERGENCY STOP modules in the power & control module)
Integrates EMERGENCY STOP functionality
Power bus
The consumers are supplied by the power bus via power tee connectors.
Field bus
The DP master supplies the DP protocol to the hybrid line (fiber-optic or Cu). ECOFAST
motor starters allow the stations on the PROFIBUS-DP to be connected without interruption
to the data tee connector.
The AS-i master supplies the AS-i protocol to the AS-i line. The stations on the AS-Interface
are connected using the insulation displacement method.
Motor
starter
Infeed
Cable types
1 Power
2 Spur
3 Motor
4 Motor (freq. converter)
5 ET200 sub-segment
6 ET200 power
7 ET200 motor
Assembly type
Pre-assembled: On one side, on both sides
Cable with 1 or 2 connectors
Length to be selected in the grid
Cut-to length: Cable without connectors
Motor
starter
Motor
starter Motor
starter
Frequ.
conv. Discr.
mod.
Discr.
mod.
ECOFAST System Description
The ECOFAST Basic System
ECOFAST System Manual
1-6 GWA 4NEB 950 5228-02
1.3.2 Overview of Interfaces
Diagram
The diagram below shows an overview of the system interfaces using the example of a motor
starter:
Fig. 1-6: Overview of Interfaces
Field Bus Interfaces
ECOFAST components feature the following field bus interfaces, depending on the device
version:
Fig. 1-7: Field bus interfaces
*3RK1303-2AS54-.... motor starters only
Motor connector Digital inputs Data tee connector
Data connector
Motor terminal
Data terminal
Power connection Power tee connector
Local device interface*
Hybrid field bus
cable
Local
device
interface
Power cable
PROFIBUS-DP PROFIBUS-DP interface
with data terminal,
data tee connector,
data connector optionally for
copper cable (Cu)
or fiber-optic cable
AS-i interface
with insulation displacement technology
for yellow AS-i line (data and 24 V non-
switched) and black AS-i line (AUX PWR:
24 V DC switched)
AS-i
AUX PWR
AS-Interface
ECOFAST System Manual
GWA 4NEB 950 5228-02 2-1
Product Family 2
2.1 Power & Control Module (PCM)
2.1.1 Tasks of the Power & Control Module (PCM)
The PCM performs the following tasks in the ECOFAST system:
Supplying the connected ECOFAST components via two Han Q4/2 sockets with 400 V AC
power
Short-circuit protection with the S2 circuit-breaker
Supplying the connected ECOFAST components via two Han Brid sockets with
- 24 V DC switched (DC24V-S): This voltage is not always present. It is used to control
the switching elements (e.g. contactor).
- 24 V DC non-switched (DC24V-NS): This voltage is always present. It is used to supply
power to the electronic ECOFAST components and sensors and interrogate auxiliary
contacts.
- PROFIBUS-DP
Supplying the AS-Interface profile lines with 24 V DC (switched) (black, AUX PWR) and 24
V DC (non-switched) (yellow, AS-i) via AS-Interface.
Protection and monitoring
PLC function
- Central SIMATIC S7 module: CPU 313-2 DP,
16 DI + 16 DO x 24 V DC with 64K memory card or
- SIMATIC S7 slave module: ET 200M with
digital input output module: SM 323 16 DI + 16 DO x 24 V DC
A program for controlling the PCM is installed in the CPU at the factory. You can also
store the user program for controlling your system here.
For more information, refer to
“System Software for S7 300/400, System and Standard Functions Reference Manual”.
EMERGENCY STOP function with contactor safety combination
- Main switch function, rotary actuator
- SIGUARD safety combination 3TK2 8... or
- Safety at work 3RK1 1...
- Stop category: 0 to EN 60204-1
(uncontrolled shutdown by means of immediate switch-off of power to the machine
actuator components)
- Category: 4 according to EN 954-1
Product Family
Power & Control Module (PCM)
ECOFAST System Manual
2-2 GWA 4NEB 950 5228-02
2.1.2 Device Versions
The PCM is available in a housing version with degree of protection IP65 and for control cab-
inet mounting with degree of protection IP00.
Set-up
Depending on the device version, the PCM comprises the following components:
PLC (DP master, DP slave, AS-i master)
3TK28 (SIGUARD) safety combination or AS-i monitor
24 V DC (switched (DC24V-S)) and 24 V DC (non-switched (DC24V-NS))
24 V DC (switched (AUX PWR)) and 30 V DC (non-switched (AS-i)) for AS-Interface
24 V DC power supplies
Safe separate supply according to PELV.
The 24 V DC power supplies (switched (DC24V-S) and non-switched (DC24V-NS)) are avail-
able in two different versions. Features to take into consideration during configuration:
Version 1: SIDAC power supply
- Equipped with a safety isolating transformer
- Very high EMC resistance
- Very robust
Version 2: SITOP power supply
- Very high control accuracy for output voltage
- Settable voltage level
- Lightweight
Fig. 2-1: Power & Control Modules (PCM) IP65 and IP00
ECOFAST System Manual
GWA 4NEB 950 5228-02 2-3
Product Family
Power & Control Module (PCM)
2.1.3 PCM Order Numbers
Power and Control Module (PCM), version IP65 Order no.
Housing dimensions (W x H x D):
Overall dimensions w/o external connector (W x H x D):
550 x 850 x 255 mm
600 x 920 x 310 mm
Bus connection Safety system Generation of aux. voltage
PROFIBUS master with S7-300 CPU
313C-2 DP
SIGUARD
safety contactor
combination
SIDAC DC 24 V,
10 A (NS), 10 A (S)
4FB2 111- 2 A ..1-0AA0
PROFIBUS master with S7-300 CPU
313C-2 DP + AS-i master with AS-i
power supply 2.4 A
4FB2 121-2A ..1-0AA0
AS-Interface
Safety at Work
4FB2 112-2A ..1-0AA0
SITOP DC 24 V,
10 A (NS), 10 A (S)
4FB2 112-2A ..2-0AA0
PROFIBUS slave with ET 200M SIGUARD
safety contactor
combination
SIDAC DC 24 V,
10 A (NS), 10 A (S)
4FB2 111- 2 A ..1-0AA1
SITOP DC 24 V,
10 A (NS), 10 A (S)
4FB2 111- 2 A ..2-0AA1
Power and Control Module (PCM), control cabinet mounting
Housing dimensions (W x H x D):
Overall dimensions w/o external connector (W x H x D):
550 x 850 x 255 mm
600 x 920 x 310 mm
Bus connection Safety system Generation of aux. voltage
PROFIBUS master with S7-300 CPU
313C-2 DP
SIGUARD
safety contactor
combination
SIDAC DC 24 V,
10 A (NS), 10 A (S)
4FB2 111-2A ..1-0AA2
PROFIBUS master with S7-300 CPU
313C-2 DP + AS-i master with AS-i
power supply 2.4 A
4FB2 121-2A ..1-0AA1
AS-Interface
Safety at Work
4FB2 112-2A ..1-0AA1
SITOP DC 24 V,
10 A (NS), 10 A (S)
4FB2 112-2A ..2-0AA1
PROFIBUS slave mit ET 200M SIGUARD
safety contactor
combination
SIDAC DC 24 V,
10 A (NS), 10 A (S)
4FB2 111-2A ..1-0AA3
SITOP DC 24 V,
10 A (NS), 10 A (S)
4FB2 111-2A ..2-0AA3
Main power supply Breaking capacity External back-up fuse*)
16 A 50 kA 100 A A0
20 A 50 kA 125 A B0
25 A 50 kA 125 A C0
32 A 50 kA 125 A D0
40 A 50 kA 160 A E0
Unregulated 1
Regulated 2
Table 2-1: PCM device versions
*) External back-up fuse
If the short-circuit current at the installation location exceeds Icu = 100 kA, a back-up fuse (gL/gG) with the maximum
value specified in the table is required.
Max. input voltage: 415 V AC.
Product Family
Alternative Power Supply
ECOFAST System Manual
2-4 GWA 4NEB 950 5228-02
2.2 Alternative Power Supply
2.2.1 Simple Energy Unit (SEU)
For applications with an external 24 V auxiliary power supply or which require a different auto-
mation structure, it is not necessary to use a complete PCM module with incoming supply,
auxiliary power supply generation and automation component.
In these cases we recommend using a circuit-breaker, two contactors and two cable through-
feeds as a "Simple Energy Unit" (SEU) which can be mounted in existing control cabinets.
The SEU is used in a IP65 housing. The 24 V auxiliary power and the wiring including the
EMERGENCY STOP must be provided by the plant.
Fig. 2-2: Simple Energy Unit (SEU)
Circuit-breaker
Contactor
Contactor
EMERGENCY STOP
EMERGENCY STOP
ECOFAST System Manual
GWA 4NEB 950 5228-02 2-5
Product Family
Alternative Power Supply
Device versions
The SEU is available for the following supply voltages: 8 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A.
The frame sizes S00 and S0 are provided for 8 A.
With the exception of the version 8 A with frame size S00, the SEUs correspond to type of
coordination 2, i.e. in case of a short circuit, the contactor and the overload relay must not
endanger either personnel or the plant and must be suitable for further use.
SEU
Type
Circuit-breaker Contactor with
Auxiliary Switch
Type of coordination/Short-
Circuit Breaking Capacity
Order No. IN [A]
S00 3RV1011-1HA10 8.00 3RT1015-1BB44-3MA Type of coordination 1/Iq=50 kA
S0 3RV1021-1HA10 8.00 3RT1024-1BB44-3MA Type of coordination 2/Iq=130 kA
S2 3RV1031-4AA10 16.00 3RT1026-1BB44-3MA0 Type of coordination 2/Iq=130 kA
S2 3RV1031-4BA10 20.00 3RT1026-1BB44-3MA0 Type of coordination 2/Iq=130 kA
S2 3RV1031-4DA10 25.00 3RT1034-1BB44 Type of coordination 2/Iq=100 kA
S2 3RV1031-4EA10 32.00 3RT1034-1BB44 Type of coordination 2/Iq=100 kA
S2 3RV1031-4FA10 40.00 3RT1035-1BB44 Type of coordination 2/Iq=100 kA
S2 3RV1031-4HA10 50.00 3RT1036-1BB44 Type of coordination 2/Iq=100 kA
Table 2-2: Device versions: Simple Energy Unit
Product Family
Alternative Power Supply
ECOFAST System Manual
2-6 GWA 4NEB 950 5228-02
2.2.2 ET 200S Motor Starter
For applications with an external 24 V auxiliary power supply or which require a different auto-
mation structure, it is not always necessary to use a complete PCM module with incoming
supply, auxiliary power supply generation and automation component.
In these cases, an ET 200S motor starter can be used as an alternative to the SEU, which
can protect and switch a complete chain. In combination with the terminal and the power
module, they form a completely wired unit. Up to 5 expansions (16 A each) can be achieved
by linking terminal blocks.
All parameterizations, messages and switching commands possible in ET 200S can be trans-
mitted via profi bus for automation.
Fig. 2-3: Overview: ET 200S as incoming supply
IM 151
F-Kit 1
DS
A2A1 A3
TM-PF30 S47-B1
PM-X
TM-X15S27-01
Power module motor starter
Terminal
module
400 V Power bus 400 V
EMERGENCY
STOP
ON
PM-D
F1
ECOFAST System Manual
GWA 4NEB 950 5228-02 2-7
Product Family
Power Tee Clamp Connector
2.3 Power Tee Clamp Connector
Tasks
Power tee clamp connectors connect ECOFAST components with the power bus. The power
bus is not interrupted when the ECOFAST components are unplugged.
Two different versions are available:
Power tee clamp connector with Han Q4/2 socket. This version connects the power bus
with the load.
Power tee-tee clamp connector with Han Q4/2 socket. This version connects the power
bus with two loads. As an alternative, a further power bus segment can be fed via the sec-
ond Han Q4/2 socket.
The clamp connectors may be inserted anywhere within the wiring chain. The round cable is
contacted via insulation displacement or screw-type terminals without interrupting the wires.
Cables with individual wires according to DIN VDE 0281/0295 with conductor cross sections
ranging from 2.5 to 6 mm2 are suitable for use.
Versions
The following versions are currently available:
Seals for Power Tee Clamp Connectors
Suitable seal sets are required for the power tee clamping connectors to attain degree of pro-
tection IP65/67. A seal set contains two seals, which are available with different internal diam-
eters depending on the external diameter of the round cable used.
ECOFAST power cables with 7 x 2.5 mm2 and 5 x 4 mm2 have an external diameter of
approx. 15 mm. If a power tee clamp connector is the last connector on the power bus, i.e. if
the power cable is not continued, the cable throughfeed has to be sealed with a filler plug.
Sealing sets are not supplied with the power tee clamp connector. They must be ordered sep-
arately.
The following sealing sets are currently available:
Order no. Version
3RK1911-2BF01 Power tee clamp connector Han Q4/2, cable cross section 2.5 – 4 mm2
3RK1911-2BF02 Power tee clamp connector Han Q4/2, cable cross section 4 – 6 mm2
3RK1911-2BG02 Power tee-tee clamp connector Han Q4/2, cable cross section 4 – 6 mm2
Table 2-3: Versions of power tee clamp connectors
Order No. Round cable/mm ø
3RK1911-5BA00 10 to 13
3RK1911-5BA10 13 to 16
3RK1911-5BA20 16 to 19
3RK1911-5BA30 19 to 22
3RK1911-5BA50 Filler plug
Table 2-4: Sealing sets for power tee clamp connectors
Product Family
Power Tee Clamp Connector
ECOFAST System Manual
2-8 GWA 4NEB 950 5228-02
Design
Fig. 2-4: Power tee/tee-tee clamp connector
Fixing lug
Power tee clamp connector (cover open)
Terminal block with clamping screws
Sealing for round cable
or filler plug*)
Sealing for round cable
or filler plug*)
Cover
Power tee clamp connector
Han Q4/2-socket
to the load e. g. motor starter
*) not supplied
Sealing for round cable
or filler plug*)
Sealing for round cable
or filler plug*)
Cover
Fixing lug
Power tee-tee clamp connector
Han Q4/2-sockets
to the load e. g. motor starter
Deckelbefestigungslasche
ECOFAST System Manual
GWA 4NEB 950 5228-02 2-9
Product Family
Hybrid Field Bus Connections
2.4 Hybrid Field Bus Connections
Tasks
In the ECOFAST system, hybrid field bus connections act as an interface between the control
cabinet/terminal box (IP20) and the field bus level (IP65/67).
In the ECOFAST system, hybrid field bus connections perform the following functions:
Supply:
- data via RS 485, shielded copper cable (Cu) or fiber-optic cable.
- 2 x 24 V DC, switched (S) and non-switched (NS).
Conducting:
- data via RS 485, shielded copper cable (Cu) or fiber-optic cable.
- 2 x 24 V DC, switched (S) and non-switched (NS).
Repeater function
Media converter
Installation
Hybrid field bus connections always have 2 channels (2 Han-Brid on the IP65 side).
Depending on the device version, the hybrid field bus connection comprises the following
components:
IP65 side (field bus level)
- Han-Brid pin/socket for conducting
- Han-Brid socket/socket for supplying IP20 to IP65
IP20 side (in control cabinet)
- Terminal block for 2 x 24 V DC (switched and non-switched)
- PROFIBUS-DP: Shielding terminals and A/B terminals or SUB-D socket (9-pin) or
Fast-Connect.
Fig. 2-5: Hybrid field bus connections
3RK1911-1AB32
IP65 side (field bus level, external) IP20 side (in control cabinet)
Example:
Conducting:
fiber-optic cable
Notice
Please observe the set-up recommendations for PROFIBUS-DP (see chapter 3.2).
Product Family
Hybrid Field Bus Connections
ECOFAST System Manual
2-10 GWA 4NEB 950 5228-02
Versions
The following versions are currently available:
Passive and active
Passive means that the signals are not regenerated. The IP20 and IP65 sides are electri-
cally connected.
Active means that the signals are regenerated (repeater function). The IP20 and IP65
sides are electrically isolated for versions with a fiber-optic cable.
24 V DC non-switched supply voltage (NS)
This voltage is required for:
supplying the electronics (in the case of the active versions)
transfer connection
24 V DC switched supply voltage (S)
This voltage is required for:
transfer connection
Order No. Function Segment 1/2 – Medium PROFIBUS-DP – IP20
3RK1911-1AA22 Supply (passive) Socket/socket (copper) A/B terminals
3RK1911-1AA32 Conducting (passive) Pin/socket (copper) A/B terminals
3RK1911-1AB22 Supply (active) Socket/socket (fiber-optic cable) SUB-D socket
3RK1911-1AB32 Conducting (active) Pin/socket (fiber-optic cable) SUB-D socket
3RK1911-1AE22 Supply (active) Socket/socket (copper) SUB-D socket
3RK1911-1AE32 Conducting (active) Pin/socket (copper) SUB-D socket
3RK1911-1AF22 Supply (passive) Socket/socket (copper) Fast-Connect
3RK1911-1AF32 Conducting (passive) Pin/socket (copper) Fast-Connect
Table 2-5: Hybrid field bus connection versions
ECOFAST System Manual
GWA 4NEB 950 5228-02 2-11
Product Family
Data Tee Plug Connector
2.5 Data Tee Plug Connector
Definition
Data tee plug connectors connect the components of an automation system with
PROFIBUS DP
Two data tee plug connectors are available in the ECOFAST system:
- Data tee plug connector with copper cable (PROFIBUS-DP Cu)
- Data tee plug connector with fiber-optic cable (PROFIBUS-DP LWL)
Non-switched supply voltage 24 V DC (DC24V-NS)
Switched supply voltage 24 V DC (DC24V-S)
Non-switched supply voltage 24 V DC
This voltage is required for
supplying the electronics in the motor starter
interrogating the auxiliary contacts
Switched supply voltage 24 V DC
This voltage is required for
controlling the switching elements (e.g. contactor)
Fig. 2-6: Data tee plug connector
Product Family
Discriminating Module and Maintenance Switch
ECOFAST System Manual
2-12 GWA 4NEB 950 5228-02
2.6 Discriminating Module and Maintenance Switch
2.6.1 Discriminating Module
The discriminating module performs the following tasks in the ECOFAST system:
Protecting the line when the cross-section is reduced
Expanding the system with the same or a smaller line cross-section
Switching off part of the system selectively in the event of an overload or short circuit
Disconnecting part of the system and securing this operating status with padlocks
Set-up
The discriminating module comprises a circuit-breaker, mains switch and alarm switch.
The discriminating module has the following connections:
Han Q4/2 pin for supplying the power
Han Q4/2 socket for conducting the power
M12 connector for check-back contact
Fig. 2-7: Set-up of the discriminating module
Han Q4/2 socket
Han Q4/2 pin
M12 connector
Check-back contact
M12 connector
Check-back contact
ECOFAST System Manual
GWA 4NEB 950 5228-02 2-13
Product Family
Discriminating Module and Maintenance Switch
Device versions
Discriminating modules are available in three different device versions:
2.6.2 Maintenance Switch with M12 Connector
The maintenance switch in the ECOFAST system is based on the 3LD2164-1GP51 standard
main switch (type: black/gray).
The rated current is 25 A. The maintenance switch is equipped with an HAN Q4/2 connecting
unit (pin insert) for the power supply infeed. The power is transferred via a 0.5 m Ölflex 110H
cable and an HAN Q4/2 socket. The switching status can be checked via the built-in M12 con-
nector (pin) (DESINA Spec_11).
Maintenance switch with M12 connector, rated current 25 A:
6AG1264-1GP51-6AA0
Fig. 2-8: Maintenance switch with M 12 connector (pin) for check-back
Device version Current Order No.
1 25 A 3RK1911-4AB25
2 16 A 3RK1911-4AB16
3 8 A 3RK1911-4AB08
Table 2-6: Discriminating module versions
Product Family
Discriminating Module and Maintenance Switch
ECOFAST System Manual
2-14 GWA 4NEB 950 5228-02
ECOFAST System Manual
GWA 4NEB 950 5228-02 3-1
Installation Guidelines 3
3.1 Installation Guidelines for PROFIBUS-DP with
ECOFAST Hybrid Field Bus Cable
ECOFAST hybrid field bus cable
ECOFAST hybrid field bus cables are suitable for trailing. They are shielded with two copper
cores for PROFIBUS-DP and four 1.5 mm2 copper cores for 24 V DC switched (DC24V-S)
and 24 V DC non-switched (DC24V-NS).
What is a bus segment?
The PROFIBUS-DP consists of at least one bus segment. Each bus segment has at least two
stations, of which at least one is a DP master.
Maximum configuration of a bus segment
A bus can consist of up to 32 stations, all physically connected by means of an ECOFAST
hybrid field bus cable.
You must connect the bus terminating connector at the beginning and end of the bus.
Fig. 3-1: Set-up of a bus segments with RS 485
Power & Control Module (P&CM) with
Terminating resistor, connected internally
ECOFAST hybrid field bus cable Bus terminating connector
Data tee plug
Station 1
Station 2 Station 3 Station 4 Station 32
Station 33 Station 34 Station 35 Station 64
2 x 24 V DC
Screw cap
Power cable
Segment 1
Segment 2
3~
- PLC
- 2 x 24 V DC Supply
- 400 V AC main power supply
or segment 2!
or
segment 2
3/PE-50/60 Hz;
400 V AC connector
2 x 24 V DC and data
Installation Guidelines
Installation Guidelines for PROFIBUS-DP with ECOFAST Hybrid Field Bus Cable (Fiber-optic Conductors)
ECOFAST System Manual
3-2 GWA 4NEB 950 5228-02
Key data of a bus segment
The maximum line length of a bus segment depends on the baud rate that is used:
.
3.2 Installation Guidelines for PROFIBUS-DP with ECOFAST
Hybrid Field Bus Cable (Fiber-optic Conductors)
ECOFAST hybrid field bus cable
ECOFAST hybrid field bus cables are suitable for trailing. They have two plastic fiber-optic
conductors for PROFIBUS-DP and four 1.5 mm2 copper cores for 24 V DC switched
(DC24V-S) and 24 V DC non-switched (DC24V-NS).
Connection to PROFIBUS-DP
If you want to bridge long distances with the field bus regardless of the baud rate, or if distur-
bance fields must not be allowed to interfere with data traffic on the bus, you should use fiber-
optic cables instead of copper cables.
The PROFIBUS-DP stations are connected to the PROFIBUS-DP by means of
Separate data tee plug connectors with fiber-optic cables (PROFIBUS-DP LWL)
Integrated plug connectors, e.g. ET 200X base module BM143
Advantages and applications
Fiber-optic cables have the following advantages compared to electrical conductors:
Electrical isolation of the PROFIBUS-DP components
Insensitivity to electromagnetic interference (EMC)
No electromagnetic radiation into the environment
Additional grounding and shielding measures can consequently be dispensed with
No need to comply with minimum distances from other lines on account of EMC
No need for equipotential bonding jumpers
No need for lightning protection elements
Maximum permissible line lengths are no longer dependent on the baud rate
Baud rate Max. line length of a segment [m]
9.6 to 187.5 kBaud 1000
500 kBaud 400
1.5 MBaud 200
3 to 12 MBaud 100
Table 3-1: Permissible line length of a bus segment based on the baud rate
ECOFAST System Manual
GWA 4NEB 950 5228-02 3-3
Installation Guidelines
Installation Guidelines for PROFIBUS-DP with ECOFAST Hybrid
Optical PROFIBUS-DP network with line topology
The optical PROFIBUS-DP network is designed with a line topology. The PROFIBUS-DP sta-
tions are connected together in pairs by means of DESINA hybrid field bus cables. If one
PROFIBUS-DP station fails, the line topology means that all downstream DP slaves are no
longer accessible to the DP master. Faults can thus be easily localized.
Fig. 3-2: Optical PROFIBUS-DP network with line topology
Baud rate
The optical PROFIBUS-DP network with a line topology can be operated with the following
baud rates:
9.6, 19.2, 45.45, 93.75, 187.5, 500 kbaud, 1.5 and 12 Mbaud.
Line lengths
If fiber-optic cables are used, the length of the transmission link is independent of the baud
rate.
Every PROFIBUS-DP station connected to the optical PROFIBUS-DP network has a repeater
functionality. The distances specified below therefore refer to the distance between two neigh-
boring PROFIBUS-DP stations in the line topology.
The maximum line length between two PROFIBUS-DP stations is dependent on the type of
fiber-optic cable that is used.
Power & Control Moduel (P&CM) with
ECOFAST Hybrid field bus cable Bus terminating connector
Data tee plug
Station 1
Station 2 Station 3 Station 4 Station 32
Station 33 Station 34 Station 35 Station 64
2 x 24 V DC
Screw cap
Power cable
Segment 1
Segment 2
3~ - PLC
- 2 x 24 V DC supply
- 400 V AC main power supply
or
segment 2
3/PE-50/60 Hz;
400 V AC
2 x 24 V DC and data
connector
Fiber-optic cable Max. line length
between 2 stations [m]
Projection to 1 network
(= 32 stations) [m]
ECOFAST
hybrid field bus cable
50 1550
Table 3-2: Permissible line lengths in the optical PROFIBUS-DP network
Installation Guidelines
Guidelines for PROFIBUS-DP Standard Cables
ECOFAST System Manual
3-4 GWA 4NEB 950 5228-02
3.3 Guidelines for PROFIBUS-DP Standard Cables
3.3.1 Potential Equalization
When do differences in potential occur?
Differences in potential can occur, for example, when different mains supplies are used.
Damage may be caused to the system as a result of potential differences between various
system parts if:
programmable controllers and inputs/outputs are connected by potentialbonded couplings,
or
cable shields are connected at both ends and grounded to different parts of a system.
Avoiding potential differences
It is important to install potential equalization lines in order to minimize potential differences
and ensure the functionality of the electronic components.
When and why do you need potential equalization?
Potential equalization has the following advantages:
Devices with a grounded interface may be destroyed as a result of potential differences.
The shielding of the PROFIBUS cable must not be used for potential equalization. This is
the case, however, with any parts of the system that are linked together via the cable
shield, but are connected to different grounding points.
Potential equalization is a precondition of lightning protection.
Rules for potential equalization
Note the following points:
The smaller the impedance of the potential equalization line, the higher the efficiency of
potential equalization.
If shielded signal cables are installed between certain parts of the system and are connec-
ted at both ends to ground/protective conductors, it is important to ensure that the impe-
dance of the additional potential equalization line is not in excess of 10% of the shield
impedance.
Use connectors with large contact areas to connect the potential equalization conductors
to the ground/protective conductor.
Protect the potential equalization conductors against corrosion.
Use potential equalization conductors made of copper or galvanized steel.
Route the potential equalization conductors in such a way that the areas bounded by the
potential conductor and the signal lines are as small as possible.
Use equipotential bonding conductors made of copper or galvanized steel.
Notice
Equipotental bonding conductors are not necessary if the parts of the system are connected
to each other exclusively by means of fiber-optic cables.
ECOFAST System Manual
GWA 4NEB 950 5228-02 3-5
Installation Guidelines
Guidelines for PROFIBUS-DP Standard Cables
3.3.2 Cable Shielding
Definition
Shielding is a means of weakening (attenuating) magnetic, electric and electromagnetic inter-
ference fields.
Interference currents on cable shields are diverted to ground via the shield busbar, which
forms a conductive connection with the housing. It is particularly important to ensure a low-
ohmic connection to the protective conductor, as otherwise the interference currents themsel-
ves may become a source of interference.
Measures for cable shielding
Note the following points:
If possible, use only cables with braided shields. The shield density should be more than
80%. Avoid using cables with foil shielding, because tensile and compressive loads at the
attachments can easily damage the foil. The result is a reduction in shield efficiency.
Always connect the cable shields at both ends. It is only when the shielding is connected
at both ends that interference suppression is effective at the high end of the frequency
range.
Exceptions: It may be better to connect the shield at one end only, if
- for some reason it is not possible to install potential equalization lines,
- analog signals (in the low mV or A range) are transmitted, or
- foil shielding (static shields) is used.
Note, however, that if the shield is connected at one end only it can suppress only low-
frequency interference.
Connect the shield of the data line to the plug body.
If the system is installed for stationary operation, it is advisable to remove the insulation
from the shielded cable without interruption and connect the cable to the shielding/protec-
tive conductor busbar.
Notice
If a potential difference occurs between the grounding points, an equalization current can
flow through a shield connected at both ends.
In this case, install an additional potential equalization line.
Installation Guidelines
Guidelines for PROFIBUS-DP Standard Cables
ECOFAST System Manual
3-6 GWA 4NEB 950 5228-02
Correct Shield Installation
Observe the following points:
Use cable clamps made of metal to secure the braided shield.
The enclosing clamps must hold a large part of the shield and make good contact (see
Figure).
Connect the shield to a shield busbar immediately adjacent to the point where the cable
enters the cabinet.
Fig. 3-3: Securing shielded cables with cable clamps and cable ties (schematic diagram)
ECOFAST System Manual
GWA 4NEB 950 5228-02 3-7
Installation Guidelines
PNO Installation Guidelines
3.4 PNO Installation Guidelines
PNO installation guidelines
Please comply with the PROFIBUS-DP/FMS Installation Guidelines of the PROFIBUS-Nut-
zerorganistation (user organization) when using electrical networks. They describe important
measures to be taken as regards the wiring, cabling and commissioning of PROFIBUS net-
works.
Publisher
PROFIBUS-Nutzerorganisation e. V.
Haid-und-Neu-Straße 7
76131 Karlsruhe, Germany
Tel: ++49(0) 721 / 9658 590
Fax: ++49(0) 721 / 9658 589
Internet: http//www.profibus.com
Guideline order number: 2.111
Installation Guidelines
Power Bus Installation Versions
ECOFAST System Manual
3-8 GWA 4NEB 950 5228-02
3.5 Power Bus Installation Versions
3.5.1 Unassembled set-up with power tee clamp connector and power cable
Installation
The consumers are connected to the power bus via the power tee clamp connector. The
power cable is installed in one piece in the plant. In the set-up shown in the figure below, only
one HAN Q4/2 connector set has to be assembled at the beginning and at the end of the
power cable.
Benefits
In principle, any cable with a diameter between 10 mm and 22 mm can be used in accor-
dance with requirements.
The power tee clamp connector can be connected at any point.
Diagram
Fig. 3-4: Set- up with power tee clamp connector
Connector with
socket insert
PCM/SEU/ET 200S
Supply
Main power Power tee clamp connector with
Han Q4/2 socket for consumer
Power cable
(cut to length)
Possible components:
Power cable Power tee clamp connector
Connector set
with pin insert
to connect PCM
Connector set
with socket insert
to connect the
final consumer
(cut to length)
Passende Dichtungssätze
+
alternatively: Power tee clamp connector
+ fillet plug
Power tee-tee clamp connector with
Han Q4/2 socket for consumer
Spur cable
Starter
ECOFAST System Manual
GWA 4NEB 950 5228-02 3-9
Installation Guidelines
Power Bus Installation Versions
3.5.2 Connecting Consumers with a Spur Cable
Set-up
The consumers are connected to the power bus via a spur cable and a power tee clamp con-
nector.
The spur cable can be ordered preassembled.
Diagram
Fig. 3-5: Set-up of sub-segment
Power tee clamp connector
with Han Q4/2 socket
Spur cable
preassembled
Installation Guidelines
Power Bus Installation Versions
ECOFAST System Manual
3-10 GWA 4NEB 950 5228-02
3.5.3 ET 200X Sub-Segmente with EM 300 Motor Starter
Installation
When using 200X sub-segments with an EM300 motor starter, an ET 200X is connected to
the power bus using an ET 200X sub-segment cable and a power tee clamp connector.
The sub-segment cable can be ordered preassembled.
Diagram
Fig. 3-6: Set-up of sub-segment
Power tee clamp connector
with Han Q4/2 socket
ET 200X
EM 300 EM 300 EM 148-FC
sub-segment cable
preassembled
Power bus
(Han Q4/2 – Han Q8/0)
Notice
The ET 200X sub-segment cable can only be used for ET 200X sub-segments that are
equipped with at least one EM300 motor starter. The ET 200X sub-segment cable features
a phase displacement for connecting the EM300 motor starters to the power bus. The motor
starters are always connected to the power bus.
ECOFAST System Manual
GWA 4NEB 950 5228-02 3-11
Installation Guidelines
Power Bus Installation Versions
Guidelines for the ET 200X Sub-Segment
Distributed ET 200X peripheral devices can be integrated in the ECOFAST system. The follo-
wing rules, however, must be followed:
An ET 200X sub-segment comprises the ET 200X sub-segment cable and a distributed
ET 200X peripheral device with at least one feeder.
A maximum of 6 motor starters or frequency converters can be used in one ET 200X sub-
segment.
Motor starters must be installed on the base module upstream of frequency convertors
(see diagram).
The EM300 motor starters are connected to the motor with a preassembled line (line type:
ET 200X motor).
The EM148-FC frequency converters are connected to the motor with a preassembled line
(line type: ET 200X FU motor).
The preassembled ET 200X power cables must be used for connecting the ET 200X sub-
segment to the power bus and for transferring the power.
Notice
The ET 200X sub-segment cable and the power cable for transferring the power are two
separate cables. They can only be used for their intended purpose.
Installation Guidelines
Power Bus Installation Versions
ECOFAST System Manual
3-12 GWA 4NEB 950 5228-02
3.5.4 Possible Power Distribution with Discriminating Modules
Diagram
The diagram below shows the possible power distribution arrangements with discriminating
modules:
Fig. 3-7: Possible power distribution with discriminating modules
1. ECOFAST consumer without a discriminating module directly in the power bus segment
backbone.
2. Discriminating module directly in the power bus segment backbone. Connection to ECO-
FAST consumer via spur cable with Han Q4/2 pin/socket.
3. The ECOFAST consumer and the discriminating module form a power bus sub-segment.
They are connected directly to each other without a cable. Connection to the power bus
segment backbone via spur cable with Han Q4/2 pin/socket.
4. ECOFAST consumer decoupled via discriminating module in the power bus segment
backbone.
s
s
s
s
s
s
s
s
Power cable
3/PE-50/60 Hz
400 V AC
ECOFAST
consumer
ECOFAST
consumer ECOFAST
consumer
Discriminating
Input:
Han Q4/2 pin
Output:
Han Q4/2 socket
12 3
4
Spur cable
Spur cable
module
Notice
The discriminating module cannot be connected without a cable if ECOFAST motor starters
are operated with the PROFIBUS-DP field bus.
ECOFAST System Manual
GWA 4NEB 950 5228-02 3-13
Installation Guidelines
Power Bus Installation Versions
3.5.5 Line Protection in Power Bus Segment for Motor Starters Without
Thermal Motor Model (Installation in the Vicinity of the Motor)
Diagram
The power bus segment to be protected contains motor feeders with:
Motor starters that only have motor protection with a temperature sensor, and
Motors with motor supply leads (installation in the vicinity of the motor). The motor supply
lead is not protected by the motor starter.
In this case, the maximum permissible current-carrying capacity of the motor supply lead
must be set on the next upstream protection module:
Variant A: discriminating module, circuit-breaker
Variant B: PCM, circuit-breaker F1.
The following diagram shows the set-up:
Fig. 3-8: Line protection for motor starters without thermal motor model
Power Cable
3/PE-50/60 Hz
400 V AC
Discriminating module
Motor starter
Motor supply lead
Motor
Motor protection:
Temperature sensor
No
thermal Motor model
No
full Motor protection
PCM
Supply
Mail power
Motor starter
Motor supply lead
Motor
Motor protection:
Temperature sensor
No
thermal Motor model
No
full Motor protection
Variant A
Variant B
Installation Guidelines
Power Bus Installation Versions
ECOFAST System Manual
3-14 GWA 4NEB 950 5228-02
Example
Motor starter used: ECOFAST motor starter
Order No.: 3RK1323-2AS51-1AA3
Motor supply lead: 1.5 mm2(max. current-carrying capacity: 18.5 A)
Installation type: E (reduction factor: 0.650 at 30 °C)
Setting value: 12 A
Variant A: 16 A and 25 A discriminating modules must be opened so that
they can be set.The 8 A discriminating module limits the cur-
rent to 8 A (nothing is set).
Variant B: The PCM must be opened so that it can be set.
ECOFAST System Manual
GWA 4NEB 950 5228-02 3-15
Installation Guidelines
Installation Versions for Switching Devices and Control Circuit
3.6 Installation Versions for Switching Devices and Control Circuit
Devices
Legend for switching devices and control circuit devices
Motor
Switching device
Frequency converter, R2SS load regulator
Power tee clamp connector
HanDrive
Spur cable (Han Q4/2 pin – socket)
Sub-segment line (Han Q4/2 pin – Han Q8/0 socket)
Motor line, both ends Han 10E, unshielded
Motor line, both ends Han 10E, shielded
Motor line Han Q8/2 pin – Han 10E socket
unshielded/shielded, assembled by user.
As an alternative instead of Han 10E socket, open cable end
in motor terminal box with M-screw fitting.
Installation Guidelines
Installation Versions for Switching Devices and Control Circuit Devices
ECOFAST System Manual
3-16 GWA 4NEB 950 5228-02
Switching device, plugged in (only motor starters, soft starters)
Fig. 3-9: Plugged in switching device (only motor starters, soft starters)
Switching device in the vicinity of the motor (only motor starters, soft starters)
Fig. 3-10: Switching device in the vicinity of the motor (only motor starters, soft starters)
Switching device with
plugged in
power tee clamp connector
Switching device with
displaced
power tee clamp connector
(spur cable)
Switching device with
plugged in
power tee clamp connector
Switching device with
displaced
power tee clamp connector
(spur cable)
ECOFAST System Manual
GWA 4NEB 950 5228-02 3-17
Installation Guidelines
Installation Versions for Switching Devices and Control Circuit
Control circuit device, plugged in (R2SS load regulator, MMI 411 frequency converter)
Fig. 3-11: Control circuit device, plugged in (R2SS load regulator, MMI 411 frequency converter)
Control circuit device in the vicinity of the motor (R2SS load regulator, MMI 411 frequency con-
verter)
Fig. 3-12: Control circuit device in the vicinity of the motor (R2SS load regulator, MMI 411 frequency
converter)
Control circuit device
plugged in
power tee clamp connector
Control circuit device
displaced
power tee clamp connector
(spur cable)
Control circuit device
plugged in
power tee clamp connector
Control circuit device
displaced
power tee clamp connector
(spur cable)
Installation Guidelines
Installation Versions for Switching Devices and Control Circuit Devices
ECOFAST System Manual
3-18 GWA 4NEB 950 5228-02
ET 200X Sub-segment (with EM 300 motor starter and EM148C frequency converter)
Fig. 3-13: ET 200X Sub-segment (with EM 300 motor starter and EM148C frequency converter)
ET 200X- EM 300 EM 148-FC
ECOFAST System Manual
GWA 4NEB 950 5228-02 4-1
Installation 4
4.1 Power & Control Module
4.1.1 Installation of the IP65 Version
Installation
Warning
Hazardous electrical voltages! These may cause electric shock and burns. Disconnect the
system and device from the power supply before starting work.
Notice
Refer to the information in the operating instructions.
Step Description
1
2
Table 4-1:Installing the PCM, IP65 Version
The PCM is designed for wall mounting.
Choose a flat surface.
Allow the specified minimum clearance to
guarantee adequate convection.
*)
PCM with PROFIBUS-DP interface on the
left-hand side: If you want to connect a PRO-
FIBUS-DP cable with a straight plug, you
must allow a clearance of approx. 150 mm
around this plug.
400
PCM
400
100*) 100
150*
Drill 4 holes for the screws.
8
4 x
695
576
Installation
Power & Control Module
ECOFAST System Manual
4-2 GWA 4NEB 950 5228-02
4.1.2 Installation of the Cabinet Installation Version (IP00)
Installation
3 Screw the screws into the wall. The screws should protrude approx. 5 mm to
enable the PCM to be mounted.
4 Hook the PCM onto the screws. Make sure it is fastened so that it is absolutely
secure (it is very heavy!).
5 Tighten the screws.
Step Description
Table 4-1:Installing the PCM, IP65 Version
Warning
Hazardous electrical voltages! These may cause electric shock and burns. Disconnect the
system and device from the power supply before starting work.
Notice
Refer to the information in the operating instructions.
Step Description
1
2
Table 4-2:Installing the PCM, Cabinet Installation Version
The PCM is designed to be installed in
control cabinets. The degree of pro-
tection of the control cabinet must be
at least IP32.
Drill 4 holes for the screws.
8
4 x
809
350
ECOFAST System Manual
GWA 4NEB 950 5228-02 4-3
Installation
Alternative Power supply
4.2 Alternative Power supply
4.2.1 Simple Energy Unit (SEU)
To install the circuit-breaker or contactor, please follow the operating instructions enclosed
with the device.
4.2.2 ET 200S Motor Starter
To install the ET 200S motor starter, please refer to the manual in the 6ES7151-1AA10-8AA0
documentation package.
3 Screw the screws into the cabinet. The screws should protrude approx. 5 mm to
enable the PCM to be mounted.
4 Hook the PCM onto the screws. Make sure it is fastened so that it is absolutely
secure (it is very heavy!).
5 Tighten the screws.
Step Description
Table 4-2:Installing the PCM, Cabinet Installation Version
Installation
Power Tee Clamp Connector
ECOFAST System Manual
4-4 GWA 4NEB 950 5228-02
4.3 Power Tee Clamp Connector
Procedure for installing the power tee clamp connectors
Warning
Hazardous electrical voltages! These may cause electric shock and burns. Disconnect the
system and device from the power supply before starting work.
Notice
Refer to the information in the operating instructions.
Step Procedure
1 Connect the power tee clamp connector to the Han Q4/2 power terminal on the
matching mating component (e.g. the consumer or the power supply). Secure
the connection with the locking device.
2 If required, you can screw the fixing lugs on the power tee clamp connector onto
a flat surface using screws with a diameter of 5 mm.
3 Loosen the four screws in the cover. Open the cover.
4 Unscrew the clamping screws.
5 Strip the insulation from the power cable over a length of approximately 130 mm.
Take care not to damage the insulation of the individual wires!
6 Place the seal around the round cable in such a way that there is approx. 10 mm
of unstripped cable between the seal and the stripped part of the cable.
7 Insert the individual wires in the insulation displacement terminations. Make sure
the terminals are assigned correctly.
8 Insert the throughfeeds with the round cable. Align the stripped part of the cable
centrally inside the housing.
9 Firmly secure the clamping screws. The individual wires are bonded via the insu-
lation displacement terminations.
10 Close the cover. The power tee clamp connector is now installed and connected.
Tabelle 4-3: Installing the power tee clamp connector
111
1111
1
1
222
22222
2
3333 3333
3
444
4444
4
4
130
ECOFAST System Manual
GWA 4NEB 950 5228-02 4-5
Installation
Hybrid Field Bus Connections
4.4 Hybrid Field Bus Connections
Step Description
1
2
3
Tabelle 4-4: Installing the hybrid field bus connection
80
90
Cut out the required section (90 mm x 80 mm) on the
control cabinet.
Note that the wall thickness must not exceed 5 mm.
Place the hybrid field bus connection into the cut-
out section.
S
ecure t
h
e
h
y
b
r
id
fi
e
ld
b
us connect
i
on
using the quick-clamping devices by
tightening the four screws.
4 x
Installation
Discriminating Module and Maintenance Switch
ECOFAST System Manual
4-6 GWA 4NEB 950 5228-02
4.5 Discriminating Module and Maintenance Switch
4.5.1 Discriminating Module
The table below lists the required components:
Installation
Item Ordering data Order No.
1 Discriminating Module 3RK1911-4AA..
depending on the version
2 2 fixing screws (dia. 4 mm), if necessary nuts,
spring washers, plain washers
3 Power line with Han Q4/2 socket
(discriminating module at input)
preassembled or prepared by customer
3RK1911-0..
depending on the length and
cross-section
4 Power line with Han Q4/2 pin
(discriminating module at output)
preassembled or prepared by customer
3RK1911-0..
depending on the length and
cross-section
5 Optional: sensor cable
6 Optional: Line end covers for sealing open ends of
lines (1 set = 10 pieces)
3RK1901-1MN00
Tabelle 4-5: Required components
Warning
Hazardous electrical voltages! These may cause electric shock and burns. Disconnect the
system and device from the power supply before starting work.
Notice
Refer to the information in the operating instructions.
ECOFAST System Manual
GWA 4NEB 950 5228-02 4-7
Installation
Discriminating Module and Maintenance Switch
To install the discriminating module, carry out the following steps:
4.5.2 Maintenance Switch
To install the maintenance switch, please follow the instructions enclosed with the device.
Step Description
1 Choose a flat surface for installation. You can choose any mounting position.
2
3 Screw the discriminating module onto the flat surface.
4 Connect the discriminating module to the power line with the Han Q4/2 pin
(discriminating module at the output).
Secure the connections with the locking devices.
6 Connect the discriminating module to the power line with the Han Q4/2 socket
(discriminating module at the input).
Secure the connections with the locking devices.
Tabelle 4-6: Installing the discriminating module
Drill 2 holes for the screws.
4
2 x
105
250
145
Installation
Discriminating Module and Maintenance Switch
ECOFAST System Manual
4-8 GWA 4NEB 950 5228-02
ECOFAST System Manual
GWA 4NEB 950 5228-02 5-1
Connections 5
5.1 Power & Control Module
5.1.1 Connections of the IP65 Version
Connections and throughfeeds on the underside of the PCM
Fig. 5-1: Connections and throughfeeds on the underside of the PCM
Warning
Hazardous electrical voltages! These may cause electric shock and burns. Disconnect the
system and device from the power supply before starting work.
Notice
Refer to the information in the operating instructions.
2 x Han-Brid sockets
for PROFIBUS-DP
and 2 x 24 V DC per channel
4 x M screwed gland
Access possible here for round cables
supplied
looped
through
400 V AC
400 V AC
2 x Han Q4/2 sockets
for supplying the power bus (400 V AC)
Cable throughfeeds
(access possible here,
e. g. for sensors)
PROFIBUS-DP
Main power
Main power
X10
X2 X3
Connections
Power & Control Module
ECOFAST System Manual
5-2 GWA 4NEB 950 5228-02
Connections on the inside
Fig. 5-2: Connections on the inside of the PCM
Schematic diagram
Fig. 5-3: Schematic diagram for wiring the PCM
X01 power supply
Supplying and looping through the main power.
Terminal block N/L1/L2/L3/PE
X08 terminal block
X08
X01
X01 terminal block
(N/L1/L2/L3/PE)
for start, EMERGENCY STOP,
AS-Interface for main power
Safety lock
Safety lock
Main switch
X01 terminal block
X08 terminal block (concealed)
F1 circuit breaker
X2/X3 Han Q4/2 sockets
X10 Han-Brid sockets (concealed)
Notice
All 5 conductors (N/L1/L2/L3/PE) must be wired.
ECOFAST System Manual
GWA 4NEB 950 5228-02 5-3
Connections
Power & Control Module
X2/X3 main circuit output
Output: 2 Han Q4/2 sockets, pin assignment acc. to DESINA:
PROFIBUS-DP field bus:X10
2 x hybrid field bus socket connections, pin assignment acc. to DESINA:
5.1.2 Connections of the Cabinet Installation Version
Connections on the front side of the PCM
Fig. 5-4: Connections on the front side of the PCM (Cabinet Installation Version)
Pin Assignment Comment
1 Phase L1
2 Phase L2
3 Phase L3
4 Neutral N
PE
11 Reserved
12 Reserved
Table 5-1: Pin assignment of the Han Q4/2 pin/socket
Pin Assignment Comment
1 + 24 V Non switched
2 0 V DC Corresponds to 1
3 0 V DC Corresponds to 4
4 + 24 V Switched
A/B Field bus
Table 5-2: Pin assignment of the hybrid field bus connection
X01 terminal block
(N/L1/L2/L3/PE)
Power supply
X08 terminal block
for start and
EMERGENCY STOP
X2/X3 terminal block
Output
Main circuit
400 V AC
X10 terminal block
2 x 24 V DC
(switched and
non switched)
PROFIBUS-DP
2 x 9-pin
SUB-D sockets
X08
X01
X2/X3X10
Connections
Power & Control Module
ECOFAST System Manual
5-4 GWA 4NEB 950 5228-02
X01 power supply
Supplying and looping through the main power.
Terminal block N/L1/L2/L3/PE
X2/X3 main circuit output
To supply the power bus
2 x terminal block N/L1/L2/L3/PE
PROFIBUS-DP
2 x 9-pin SUB-D socket directly on PLC
Wiring
Notice
All 5 conductors (N/L1/L2/L3/PE) must be wired.
Step Description
1 Strip the lines. For more information about the stripped lengths, cross-sections
and terminal assignments, refer to the table on the next page.
In the case of the IP65 model, please open the door of the PCM first. To do so,
unlock the two safety locks and turn the main switch counter clockwise.
2 Insert the lines for Start, EMERGENCY STOP and, if necessary, the AS-Inter-
face through the M screwed glands on the underside and into the PCM up to the
X08 terminal block. Connect the lines to the X08 terminal block with Cage
Clamps.
3 Insert the lines for the main power through the M screwed glands on the under-
side and into the PCM up to the X01 terminal block. Connect the lines to the X01
terminal block with cage clamps.
4 Connect the hybrid field bus cables (maximum of 2) to the X10 if you are using a
PCM with PROFIBUS-DP
5 Connect a maximum of 2 power cables to X2 and X3.
6 Attach suitable screw caps to the underside of any unused throughfeeds to
attain degree of protection IP65. Close the screw cap of the MPI plug on the left-
hand side.
7 This completes wiring. Close the F1 circuit-breaker.
Table 5-3: Wiring of the PCM
ECOFAST System Manual
GWA 4NEB 950 5228-02 5-5
Connections
Power & Control Module
Stripped lengths, cross-sections, terminal assignment
Table 5-4: Stripped lengths, cross-sections, terminal assignment
X08
X08 / 1-2 3-4 5 (+) 6 (–) 7 (+) 8 (–) X01 / L1 L2 L3 N PE
AS-i AUX PWR
0.08 ... 4 mm² 0.08 ... 4 mm² 0.2 ... 16 mm2
AWG 28...12 AWG 28...12 AWG 24...6
IP65
4FB2 111-2A...-0AA0 xx—— x
4FB2 121-2A...-0AA0 xx x x x
4FB2 111-2A...-0AA1 xx—— x
4FB2 112-2A...-0AA0 xxx x
IP00
4FB2 111-2A...-0AA2 xx—— x
4FB2 121-2A...-0AA1 xx x x x
4FB2 111-2A...-0AA3 xx—— x
4FB2 112-2A...-0AA1 xxx x
IP00
X10 / 1-2 3-4 X2/X3 L1 L2 L3 N PE
24 V DC
+NS/–NS
24 V DC
+S/–S
0.08 ... 4 mm² 0.08 ... 4 mm² 0.2 ... 10 mm2
AWG 28...12 AWG 28...12 AWG 24...8
9Start 17
917
917
912
912
912
2
31
X01
Cage Clamp
Connections
Alternative Power Supply
ECOFAST System Manual
5-6 GWA 4NEB 950 5228-02
5.2 Alternative Power Supply
5.2.1 Connections of the Simple Energy Unit (SEU)
Fig. 5-5: Wiring diagram of a SEU (example) under the responsibility of the user
5.2.2 ET 200S Motor Starter
Fig. 5-6: Wiring scheme of a ET 200S motor starter (example) under the responsibility of the user
13513
14
6
42
A2( )
A1(+) 21 31 43
44
3222
13513
14
6
42
A2( )
A1(+) 21 31 43
44
3222
135
462
I
v
I
v
I
v
L1 L2 L3
T1 T2 T3
Power IN 400 V
Power OUT 400 V
Power ON
Check-back
Start
EMERGENCY
STOP
24 V
Circuit-breaker
Contactor with
auxiliary switch
1L1
1L2
1L3
400 V AC
F01F03
16 A
PE
PE
Fault Fault
L+
M
1
8
2
9
1L+
2L+
1M
2M
3
4
5
6
8
1L+ 24 V DC
1M
1L1
3L2
5L3
2L+ 24 V DC
2M
4
10
5
11
A1+
A2
N
PE
2T1
4T2
6T3
PE
N
PE
2T1
4T2
6T3
PM-D DS1-x DS1-x
PE/NPE/N
IM 151
E 108.1
E 108.0
E 108.3
S 110.0
E 108.5
E 108.4
E 108.7
S 110.4S 110.2 S 110.2
Power supply
Electronics
Power supply
Contactor
PROFIBUS-DP
ECOFAST System Manual
GWA 4NEB 950 5228-02 5-7
Connections
Power Tee Clamp Connector
5.3 Power Tee Clamp Connector
Connections
Fig. 5-7: Pin assignment for power tee clamp connector
Warning
Hazardous electrical voltages! These may cause electric shock and burns. Disconnect the
system and device from the power supply before starting work.
Notice
Refer to the information in the operating instructions.
1
2
3
4
5
6
Termminal Assignment Core No.*
1 Phase L1
2 Phase L2
3 Phase L3
PE
4 Neutral conductor N
5 Reserved
6 Reserved
222
333
444
111
555
666
Power tee clamp connector
Terminal numbers and Han Q4/2 pin numbers
do not have the same assignment
1
2
4
5
11
22
44
333
55
Caution
Note that core numbers and terminal numbers are not
identical for preassembled power cables.
* Core No.
Connections
Hybrid Field Bus Connections
ECOFAST System Manual
5-8 GWA 4NEB 950 5228-02
5.4 Hybrid Field Bus Connections
Connections on the IP65 side
Fig. 5-8: Connections on the IP65 side
Connections on the IP20 side
Fig. 5-9: Connections on the IP20 side
pin socket
IP65 side (field bus level, external)
Conducting
Conducting
Cu
LWL
Han-Brid
Supply
Cu
Supply
LWL
socket socket
Han-Brid
IP20 side (in control cabinet)
Terminal block for 2 x 24 V DC (S and NS)
Shield clamp
Terminals A2 (green)/B2 (red)
Terminal block for 2 x 24 V DC (S and NS)
SUB-D socket
for PROFIBUS-DP
for PROFIBUS-DP
Channel 2
Terminal block for 2 x 24 V DC (S und NS) Insulation displ. terminals
for PROFIBUS-DP
Channel 2
A2 (green)/B2 (red)
for PROFIBUS-DP
Channel 1
A1 (green)/B1 (red)
III
III
Terminals A1 (green)/B1 (red)
for PROFIBUS-DP
Channel 1
Fast-Connect-Block
for PROFIBUS-DP
ECOFAST System Manual
GWA 4NEB 950 5228-02 5-9
Connections
Hybrid Field Bus Connections
Connections for PROFIBUS-DP and 2 x 24 V DC (IP65 side)
2 x Han-Brid socket/socket or pin/socket, pin assignment acc. to DESINA:
Fig. 5-10: Pin assignment for hybrid field bus connection (IP65 side)
1
23
4
A1 B1
23
4
A2 B2
1
Pin Socket
Pin Assignment Comment
1 +24 V DC Non switched
2 0 V DC Corresponds to 1
3 0 V DC Corresponds to 4
4 +24 V DC Switched
Field bus
A1/A2 Line A
field bus
B1/B2 Line B
field bus
Shield
field bus
1
23
4
RxD TxD
23
4
RxD TxD
1
Copper
Fiber-optic cable Pin Assignment Comment
1 +24 V DC Non switched
2 0 V DC Corresponds to 1
3 0 V DC Corresponds to 4
4 +24 V DC Switched
TxD Field bus
transmitter
Fiber-optic cable
field bus
RxD Field bus
receiver
Fiber-optic cable
field bus
Pin Socket
Connections
Hybrid Field Bus Connections
ECOFAST System Manual
5-10 GWA 4NEB 950 5228-02
Connections for passive hybrid field bus connection (IP20 side)
Connections for active hybrid field bus connection (IP20 side)
Connection Assignment Comment
Klemmenblock 24 V
+NS +24 V DC Non switched
–NS 0 V DC Corresponds to +NS
–S 0 V DC Corresponds to +S
+S +24 V DC Switched
Terminal block A/B for PROFIBUS-DP
A1/A2 Line A field bus
B1/B2 Line B field bus
Shield field bus
Fast-Connect-Block for PROFIBUS-DP
A1/A2 Line A field bus
(green)
B1/B2 Line B field bus
(red)
Shield field bus
Table 5-5: Connections for passive hybrid field bus connection (IP20 side)
AB
green
red
Connection Assignment Comment
Terminal block 24 V
+NS +24 V DC Non switched
– NS 0 V DC Corresponds to +NS
– S 0 V DC Corresponds to +S
+S +24 V DC Switched
SUB-D socket for PROFIBUS-DP
1 Shield
2—
3 RxD/TxD-P (+)
4 CNTR-P
5DGND
6VP
7—
8 RxD/TxD-N (–)
Table 5-6: Connections for active hybrid field bus connection (IP20 side)
1
6.
9.
5
Pin
Channel 1
Channel 2
ECOFAST System Manual
GWA 4NEB 950 5228-02 5-11
Connections
Hybrid Field Bus Connections
Wiring
Steps for connecting the "Fast Connect Block"
Step Description
1 Strip the lines. For more information on stripped lengths, cross-sections, and ter-
minal assignments, refer to the table on the next page.
2 Use the Cage Clamps to connect the 24 V DC cables (S and NS) to the 24 V DC
terminal block.
Passive hybrid field bus connection Active hybrid field bus connection
3 Use the Cage Clamps to connect the
PROFIBUS-DP cables to terminals
A1/B1 and A2/B2.
Connect the PROFIBUS-DP cable to
the 9-pin SUB-D socket.
4 Connect the shield to the shield termi-
nals.
5 If you want to connect a bus terminating connector, this must be supplied with
24 V DC. To do so, jumper terminals S1 and S2 of the non-switched (NS) 24 DC
(see below).
6 This completes the wiring.
Table 5-7: Wiring the hybrid field bus connection
Step Description
1 Prepare the bus cable according to the
drawing.
Do not strip the cable ends!
2 Unsrew the locking srew, open the cover
and then lift the terminal block.
3 Insert the cable end into the terminal and
push the terminal block back down.
The bus cable is contacted vi the insula-
tion piercing termination.
4 Close the cover and tighten the locking
srew.
The shield is contacted via the pressure
of the cover and the cable is relieved
from strain.
5 This completes the wiring.
Table 5-8: Wiring of the Fast Connect Block
15
8
Connections
Hybrid Field Bus Connections
ECOFAST System Manual
5-12 GWA 4NEB 950 5228-02
Schematic diagram
Fig. 5-11: Schematic diagram for wiring the hybrid field bus connection
Passive hybrid field bus connection Active hybrid field bus connection
2 x 24 V DC 2 x 24 V DC
9-pole
SUB-D socket
Shield terminals
A1 B1 A2 B2
+NS –NS –S +S
S1
S2
Jumpers for supplying
24 V DC NS
24 V DC S
S1 with 2 x 24 V DC
24 V DC wiring:
Passive hybrid field bus connection (Fast-Connect Block)
ECOFAST System Manual
GWA 4NEB 950 5228-02 5-13
Connections
Hybrid Field Bus Connections
Stripped lengths, cross-sections, terminal assignments
Table 5-9: Stripped lengths, cross-sections, terminal assignments
2 x 24 V DC
+NS –NS – S + S
PROFIBUS-DP
A1 B1 A2 B2
PROFIBUS-DP
"Fast-Connect"
PROFIBUS-DP
9-pin SUB-D
3RK1911-1AA22 x x
3RK1911-1AA32 x x
3RK1911-1AF22 x x
3RK1911-1AF32 x x
3RK1911-1AB22 x x
3RK1911-1AB32 x x
3RK1911-1AE22 x x
3RK1911-1AE32 x x
9
1.5 mm²
AWG 15
999
AB
green
red
Cage Clamp
2
31
A1B1
A2 B2
S1
S2
1
2
Cage Clamp
Connections
Data Tee Plug Connector
ECOFAST System Manual
5-14 GWA 4NEB 950 5228-02
5.5 Data Tee Plug Connector
5.5.1 Pin Assignment
Fig. 5-12: Pin assignment for the data tee plug connector/core assignment for the hybrid field bus
cable
Pin Assignment Color*)
1 +24 V DC non switched Black 1
2 0 V DC non switched Black 2
3 0 V DC switched Black 3
4 +24 V DC switched Black 4
A Line A field bus Green
B Line B field bus Red
Shield field bus
Data tee connector PROFIBUS-DP Cu
1
23
4
AB
23
4
AB
1
1
23
4
RD TD
23
4
RD TD
1
Pin Assignment Color*)
1 +24 V DC non switched Black 1
2 0 V DC non switched Black 2
3 0 V DC switched Black 3
4 +24 V DC switched Black 4
TD Fiber-optic cable field bus -
transmitter
see Fig.
below
RD Fiber-optic cable field bus -
receiver
see Fig.
below
Data tee connector PROFIBUS-DP fiber-optic cable
Pin Socket
Input Output
OF field bus
Data plug
connector
(socket)
Data plug
connector
(pin)
*) Core colors of the DESINA
hybrid field bus cable
RD TD
RD TD RD TD RD TD
Pin Socket
Input Output
Assignment of the fiber-optic field bus
ECOFAST System Manual
GWA 4NEB 950 5228-02 5-15
Connections
Discriminating Module and Maintenance Switch
5.6 Discriminating Module and Maintenance Switch
Power bus connection
Input: Han Q4/2 pin
Output: Han Q4/2 socket
Pin assignment acc. to DESINA:
Check-back
Fig. 5-13: M 12 connector (pin) for check-back signals
Warning
Hazardous electrical voltages! These may cause electric shock and burns. Disconnect the
system and device from the power supply before starting work.
Notice
Refer to the information in the operating instructions.
Pin Assignment Comment
1 Phase L1 Switched
2 Phase L2 Switched
3 Phase L3 Switched
4 Neutral conductor N Looped through
11 Reserved
12 Reserved
PE, ground Looped through
Table 5-10: Pin assignment of the Han Q4/2 pin/socket
1
4
2
3
5
red
black
yellow
NO NC
C
Connections
General Wiring and Interfaces
ECOFAST System Manual
5-16 GWA 4NEB 950 5228-02
5.7 General Wiring and Interfaces
5.7.1 Rules for Wiring
Selecting the power leads
The core cross-section of the power leads must be matched to the respective ambient condi-
tions. The decisive factors for choosing the core cross-section are as follows:
set current on the device
installation method
ambient temperature
type of material (PVC, rubber)
For PVC power leads installed in a cable duct, for example, the maximum current carrying
capacity as a function of ambient temperature is as follows:
Warning
Hazardous electrical voltages! These may cause electric shock and burns. Disconnect the
system and device from the power supply before starting work.
Notice
Refer to the information in the operating instructions.
øTU 30 °C 40 °C 45 °C 50 °C 55 °C
1.5 mm2 14 A 12.2 A 11.1 A 9.9 A 8.5 A
2.5 mm2 19 A 16.5 A 15.0 A 13.5 A 11.6 A
4.0 mm2 26 A 22.6 A 20.5 A 18.5 A 15.9 A
6.0 mm2 33 A 28.7 A 26.0 A 23.4 A 20.1 A
Table 5-11: Reduction values for installation type B2 with three loaded cores
ECOFAST System Manual
GWA 4NEB 950 5228-02 5-17
Connections
General Wiring and Interfaces
Observe the following rules when carrying out wiring:
Unused Connections
Close off unused connections with screw caps; this is the only way of ensuring degree of pro-
tection IP65. Order number 3 RK1 902-0CJ00 (10 screw caps) or 3 RK1 902-0CK00 (1 screw
cap).
5.7.2 Power Cables, Preassembled at One End
Power cables which are preassembled at one end are available in different lengths (see
appendix for order numbers). One end of the cable is fitted with a power plug connector with
pins. The other end is free. Here, you can strip the cores and, for example, attach a plug con-
nector or terminal block.
.
Fig. 5-14: Numbers printed on the power cable cores
Rules for flexible cables Data
Current carrying capacity of the plug connection as a function of
the connectable core cross-sections and ambient temperature Tu =
55 °C 40 °C
1.5 mm2
2.5 mm2
4.0 mm2
6.0 mm2
12 A
20 A
30 A
48 A
15 A
25 A
35 A
54 A
Permissible outer diameter of the cable sealing
insert Green
Red
White
7.0 to 10.5 mm
9.0 to 13.0 mm
11.5 to 15.5 mm
Length of insulation to strip from cores 8 mm
Length of insulation to strip from cable sheath 20 mm
Table 5-12: Rules for wiring
1
2
4
5
11
22
44
333
55
Numbers are printed on the cores for identification
purposes.
The core number/pin assignments are specified in the
following two sections.
Connections
General Wiring and Interfaces
ECOFAST System Manual
5-18 GWA 4NEB 950 5228-02
Power cables, preassembled at one end with Han Q4/2 pin
Fig. 5-15: Power cables, preassembled at one end with Han Q4/2 pin
Pin Core no. Assignment
1 2 Phase L1
2 3 Phase L2
3 4 Phase L3
4 1 Neutral N
11 5 Reserved
12 6 Reserved
PE (yellow/green)
12
34
11 12
ECOFAST System Manual
GWA 4NEB 950 5228-02 5-19
Connections
General Wiring and Interfaces
Power cables, preassembled at one end with Han 10E pin
Fig. 5-16: Motor supply leads preassembled at one end with Han 10E pin
Notice
Shielded motor supply leads must be used for frequency converters.
Pin Core no.
(7-core)
Core no.
(11-core) Assignment
1 1 1 Phase L1
2 2 2 Phase L2
3 3 3 Phase L3
4 4 Brake (reference potential)
5— 5Brake
6 4 6 Winding terminal W2
7 5 7 Winding terminal U2
8 6 8 Winding terminal V2
9 9 Temperature sensor (terminal a)
10 10 Temperature sensor (terminal b)
PE (yellow/green)
Connections
General Wiring and Interfaces
ECOFAST System Manual
5-20 GWA 4NEB 950 5228-02
Preassembled power cables (e. g. spur cable)
To prepare power cables, you need a crimping tool (soldering is possible as an alternative)
and the accessories listed in the table.
Power cables with Han Q4/2
Han Q4/2 power connectors
The power connectors consist of the following components:
Fig. 5-17: Han Q4/2 power connector
To connect the main power to the motor
starter/power connector,
To loop through the main power from the
power connector,
you need...
a flexible Cu cable
5 x 2.5 mm2 (3 conductors + N + PE)
5 x 4 mm2 (3 conductors + N + PE)
5 x 6 mm2 (3 conductors + N + PE)
Han Q4/2 socket (straight)
2.5 mm2: 3RK1911-2BR50
4.0 mm2: 3RK1911-2BR10
6.0 mm2: 3RK1911-2BR30
Han Q4/2 pin (straight)
2.5 mm2: 3RK1911-2BS60
4.0 mm2: 3RK1911-2BS20
6.0 mm2: 3RK1911-2BS40
Han Q4/2 socket (angular)
2.5 mm2: 3RK1911-2BE50
4.0 mm2: 3RK1911-2BE10
6.0 mm2: 3RK1911-2BE30
Han Q4/2 pin (angular)
2.5 mm2: 3RK1911-2BF60
4.0 mm2: 3RK1911-2BF20
6.0 mm2: 3RK1911-2BF40
Table 5-13: Preparing connecting leads with Han Q4/2
Connector housing Connector housing
Socket insert
Jacks Contact pins
Pin insert
Han Q4/2 socket
for looping through the main power
for connecting the main power
Han Q4/2 pin
ECOFAST System Manual
GWA 4NEB 950 5228-02 5-21
Connections
General Wiring and Interfaces
5.7.3 AS-i Interface
Connection Techniques
The following AS-i cables are used:
Yellow AS-i cable for AS-i communication and non-switched 24 V DC auxiliary power for
supplying sensors and electronics
Black AUX PWR AS-i cable for switched 24 V DC auxiliary power for supplying actuators
The diagram below shows the position and coding of the AS-i cables on the motor starter:
Fig. 5-18: AS Interface
Contacting
The AS-i cables are contacted automatically using the insulation piercing method when the
AS-i cover is screwed on.
Fig. 5-19: Contacting the AS-i cables
AS-i
AUX PWR
AS-i cable
Communication and
non switched auxiliary power
Switched auxiliary power
Motor starter
AS-i cover
AS-i (–)
AUX PWR (–)
AUX PWR (+)
AS-i (+)
AS-i
AUX PWR
AS-i Cover
Connections
General Wiring and Interfaces
ECOFAST System Manual
5-22 GWA 4NEB 950 5228-02
24 V DC voltage supply (AS-i) non-switched (yellow AS-i cable)
This voltage is constantly available. It is required for:
supplying the electronics in the motor starter
interrogating the auxiliary contacts
The voltage is not disconnected in the event of an EMERGENCY STOP or safety shutdown,
thereby ensuring that the system can always communicate with the ECOFAST component.
24 V DC voltage supply (AUX PWR) switched (black AS-i cable)
This voltage is not constantly available. It is only required for:
driving the switching elements, e.g. a contactor
The voltage can be disconnected in the event of an EMERGENCA STOP or safety shutdown
(category 1 according to EN 954-1), so that all switching elements are safely disconnected
with the connected motors.
Response to undervoltage (24 V DC < 18.5 V) and power failure:
In the event of prolonged undervoltage or power failure > 20 ms, the switching elements
and the brake output are disconnected.
When the power supply is restored, the disconnection command and the associated signal
bits and error bits are acknowledged automatically.
ECOFAST System Manual
GWA 4NEB 950 5228-02 6-1
Commissioning 6
6.1 Power & Control Module
IP65 Version:
Control cabinet version:
Warning
Hazardous electrical voltages! These may cause electric shock and burns. Disconnect the
system and device from the power supply before starting work.
Notice
Refer to the information in the operating instructions.
Step Description
1 Turn the rotary switch on the front of the CPU to “RUN”.
2 If you are using motor starters without a thermal motor model and with a motor
supply lead (installation in the vicinity of the motor), also observe the line protec-
tion guidelines in 3.5.5 on page 3-13.
3 Close the door of the PCM and lock both safety locks. Turn the main switch
clockwise.
4 Switch on the 400 V AC main power supply.
5 Switch on the PCM.
6 Reset the external EMERG. STOP if necessary and actuate the external start
switch. The power bus(es) and the field bus(es) are now supplied with power.
7 Configure the AS-i monitor if necessary. The factory-assigned password is
“ECOFAST”. Note the information below.
Table 6-1: Sequence of steps for commissioning the PCM, IP65 version
Step Description
1 If you are using motor starters without a thermal motor model and with a motor
supply lead (installation in the vicinity of the motor), also observe the line protec-
tion guidelines in 3.5.5 on page 3-13.
2 Switch on the 400 V AC main power supply.
3 Reset the external EMERG. STOP if necessary and actuate the external start
switch. The power bus(es) and the field bus(es) are now supplied with power
Table 6-2: Sequence of steps for commissioning the PCM, control cabinet version
Commissioning
Power & Control Module
ECOFAST System Manual
6-2 GWA 4NEB 950 5228-02
lll.
6.1.1 Diagnostics
Missing voltages
4 Configure the AS-i monitor if necessary. The password assigned in the factory is
“ECOFAST”. Note the information below.
Step Description
Table 6-2: Sequence of steps for commissioning the PCM, control cabinet version
Notice
The AS-i monitor “measures” the connected cables and saves the configuration. During
commissioning, the factory default configuration is still stored. For this reason, the system
displays a prompt after you have entered your password because the system has to be
reconfigured.
Voltage missing Shown by Potential fault Cause
400 VAC D1/D2 E0.0 OFF Q1 OFF
D1/D2 E0,1 OFF Q1 OFF Overload
D1/D2 E0.2 OFF Q1 OFF Short circuit
D1/D2 E0.3 OFF K1 and/or K2 AUS EMERGENCY STOP,
24 V internal, D5 or K5
24 V internal All OFF Q1 OFF
All OFF F1 OFF
F2/ channel 4 red F2 Overload
F2/ channel 4 red F2, blade-type fuse
defective
Short circuit
24 V switched D1/D2 E0.4, D1/D2
E0.7 OFF
K3 and/or K4 OFF D5 or K5,
EMERGENCY STOP
D1/D2 E0.7 OFF F2/ channel 1 red Overload
D1/D2 E0.7 OFF F2/ channel 1 red, blade-
type fuse defective
Short circuit
24 V non switched D1/D2 E0.6 OFF F2/ channel 3 red Overload
D1/D2 E0.6 OFF F2/ channel 3 red, blade-
type fuse defective
Short circuit
24 V AS-i switched D1/D2 E1.1, D1/D2
E0.4
K3 and/or K4 OFF D5 or K5,
EMERGENCY STOP
E1.1 F2/ channel 2 Overload
E1.1 F2/ channel 2, blade-type
fuse defective
Short circuit
30 V AS-i non switched D5 or D3 G2 Overload
Table 6-3: Diagnostics - missing voltages
ECOFAST System Manual
GWA 4NEB 950 5228-02 6-3
Commissioning
Alternative Power Supply
Signal states
6.2 Alternative Power Supply
6.2.1 Simple Energy Unit (SEU)
For the commissioning of the circuit breakers and the contactors please refer to the instruc-
tions enclosed with the device.
6.2.2 ET 200S motor starter
For the commissioning of the motor starter ET 200S please refer to the manual in the
6ES7151-1AA10-8AA0 documentation package.
Signal Was fehlt? Möglicher Fehler Ursache
D1/D2 E 0.0 OFF All OFF Q1 OFF
D1/D2 E 0.1 OFF All OFF Q1 Overload
D1/D2 E 0.2 OFF All OFF Q1 Short circuit
D1/D2 E 0.3 OFF 400 VAC K1, K2 OFF D5(K5), EMERGENCY
STOP, 24 V internal
D1/D2 E 0.4 OFF 24 V switched
24 V AS-i K3, K4 OFF D5(K5), EMERGENCY
STOP, 24 V internal, F2/
channel 1
D1/D2 E 0.5 OFF 400 V, 24 V switched,
24 V AS-i
K1, K2, K3, K4 EMERGENCY STOP
D1/D2 E 0.6 OFF 24 V non switched F2/ channel 3 F2/ channel 3 over-
loaded
D1/D2 E 0.7 OFF 24 V switched F2/ channel 1 F2/ channel 2 over-
loaded
D1/D2 E 1.0 OFF All OFF F1 OFF Overload, Short circuit
D1/D2 E 1.1 OFF 24 V AS-i F2/ channel 2 Overload, Short circuit
F2/ channel 1 red ON 24 V switched F2/ channel 1 Overload, Short circuit
F2/ channel 2 red ON 24 V AS-i F2/ channel 2 Overload, Short circuit
F2/ channel 3 red ON 24 V non switched F2/ channel 3 Overload, Short circuit
F2/ channel 4 red ON All OFF F2/ channel 4 Overload, Short circuit
Table 6-4: Diagnostics - signal states
Commissioning
Hybrid Field Bus Connections
ECOFAST System Manual
6-4 GWA 4NEB 950 5228-02
6.3 Hybrid Field Bus Connections
To commission the hybrid field bus connections carry out the following steps:
Diagnostics
Certain faults are highlighted by 2 LEDs for the active hybrid field bus connections. The LEDs
are located on the IP20 side (in the control cabinet) in front of the SUB-D socket.
Fig. 6-1: Diagnostics LEDs for active hybrid field bus connections
Examples of typical hybrid field bus connections are listed on the following pages.
Step Description
1 Connect up to 2 hybrid field bus cables.
2 Close the control cabinet.
3 Attach bus terminating connectors or screw caps to any unused connections.
4 Switch on the main power.
Table 6-5: Procedure for commissioning the hybrid field bus connection
Fault Display/LED Remedy
No supply voltage from
24 V DC (NS)
LED green OFF Connect 24 V DC (NS) supply
voltage
No supply voltage from
24 V DC (NS)
LED yellow OFF Connect 24 V DC (NS) supply
voltage
No signal from master Check signal cable from mas-
ter for interruption
Baud rate not recognized Plug in bus terminating
connnector
Baud rate not recognized LED yellow flickers Plug in bus terminating
connnector
Check bus station in direction
of master fault
Table 6-6: Diagnostics for active hybrid field bus connections
LED yellow
LED green
ECOFAST System Manual
GWA 4NEB 950 5228-02 6-5
Commissioning
Hybrid Field Bus Connections
6.3.1 Passive Hybrid Field Bus Connection for Supply
Fig. 6-2: 3RK1911-1AA22 passive hybrid field bus connection (socket/socket)
Typical set-up:
IP20 (inside):
PLC/DP master/PROFIBUS-DP via RS 485
Power supply for switched/non-switched voltage
Passive hybrid field bus connection for combining
PROFIBUS-DP (Cage Clamp) + power supplies (Cage Clamp)
Segment divided between left and right
IP65 (in the field):
Supply to PROFIBUS-DP in RS 485 in the left and right segments via Han Brid (sockets)
Left and right bus terminating connectors on the last data tee Connectors of the left and
right segments
Supply to the power supplies (NS + S) via Han Brid (sockets)
Cage Clamp
non switched (NS)
switched (S)
Cage Clamp
Han-Brid Hybrid field bus connection Bus terminating
right
Slave 4
left
Note:
SIMATIC
PROFIBUS standard cable
IP20 (inside)
IP65 (in the field)
Hybrid field bus cable RS 485
Slave 3
e. g. 6ES7 9720BA50-0AA0
Supply: 3RK1911-1AA22 (socket/socket) connector
segment
e. g. 6XV1830-7BH30
segment
Bus terminating
connectors are
plugged directly
onto the data tee
connector
e. g. CPU 315-2 DP
Power supply
Commissioning
Hybrid Field Bus Connections
ECOFAST System Manual
6-6 GWA 4NEB 950 5228-02
6.3.2 Passive Hybrid Field Bus Connection for Conducting
Fig. 6-3: 3RK1911-1AA32 passive hybrid field bus connection (pin/socket)
Typical set-up: Integration of an operator panel (OP)
IP20 (inside):
PROFIBUS-DP and power supply to the components separated by the hybrid field bus
connection
Standard PROFIBUS-DP line connected to the hybrid field bus connection with Cage
Clamp
PROFIBUS-DP line connected to the component with a 9-pole SUB-D RS 485 bus plug
Power supply to the component (e.g. operator panel) connected to the hybrid field bus
connection with Cage Clamp (NS + S)
Standard IP20 component (e.g. operator panel)
IP65 (in the field):
Supply to PROFIBUS-DP in RS 485 and power supply via the hybrid field bus line to the
pins of the hybrid field bus connection. PROFIBUS-DP and power supplies conducted into
the hybrid field bus line via the sockets of the hybrid field bus connection
Left and right bus terminating connectors on the last data tee connectors
Bus plug
e. g. OP 27
Slave 4
non switched (NS)
PROFIBUS standard cable
PROFIBUS-DP
Cage Clamp Cage Clamp
IP20 (inside)
e. g. Power & Control Module (P&CM)
IP65 (in the field)
Hybrid field bus connection
Han-Brid
Bus terminating
Slave 5
Hybrid field bus cable RS 485
2 x 24 V DC
Station 1
Slave 3
3~
e. g. 6ES7972-0BA50-0XA0
RS 485
Conducting: 3RK1911-1AA32 (pin/socket)
connector
e. g. 6XV1830-7BH30
Note:
Bus terminating
connectors are
plugged directly
onto the data tee
connector
ECOFAST System Manual
GWA 4NEB 950 5228-02 6-7
Commissioning
Hybrid Field Bus Connections
6.3.3 Active Hybrid Field Bus Connection for Supply
Fig. 6-4: 3RK1911-1AB22 active hybrid field bus connection (socket/socket)
Typical set-up:
IP20 (inside):
PLC/DP master/PROFIBUS-DP via RS 485
Power supply for switched/non-switched voltage
Active hybrid field bus connection for combining PROFIBUS-DP 9-pin SUB-D
(socket) + power supplies (terminals)
Segment divided left and right
IP65 (in the field):
PROFIBUS-DP supply with fiber-optic cables in the segment (left/right) via versatile link
module
Bus terminating connector (left/right) on the last data tee connector
Power supply (NS + S) via Han-Brid (sockets)
SIMATIC
e. g. CPU 315-2 DP
Power supply
non switched (NS)
Cage Clamp
Hybrid field bus connection
Supply: 3RK1911-1AB22 (socket/socket)
Cap
Slave 4Slave 3
Hybrid field bus fiber-optic cable
e. g. 6XV1830-6DH30
Cap
Han-Brid
IP65 (in the field)
IP20 (inside)
PROFIBUS standard cable
PROFIBUS-DP
RS 485
Sub-D
switched (S)
Commissioning
Hybrid Field Bus Connections
ECOFAST System Manual
6-8 GWA 4NEB 950 5228-02
6.3.4 Active Hybrid Field Bus Connection for Conducting
Fig. 6-5: 3RK1911-1AB32 active hybrid field bus connection (pin/socket)
Typical set-up: integrating an operator panel (OP)
IP20 (inside)
Active hybrid field bus connection for separating PROFIBUS-DP and converting fiber-optic
cable to RS 485 + power supplies (NS + S) for the components
Standard PROFIBUS-DP cable connected to hybrid field bus connection with 9-pin SUB-D
socket
PROFIBUS-DP cable connected to the component with 9-pin SUB-D bus plug
Component power supply (e.g. for operator panel) connected to hybrid field bus connec-
tion with cage clamp (NS + S)
Standard IP20 component (e.g. operator panel)
IP65 (in the field):
Supply to PROFIBUS-DP with fiber-optic cables and power supplies via hybrid field bus
line to pins of hybrid field bus connection
PROFIBUS-DP and power supplies conducted to hybrid field bus line via sockets of hybrid
field bus connection
Screw caps (left and right) on the last data tee connector
non switched (NS)
Cage Clamp
Hybrid field bus connection
Cap
Slave 5Slave 3
Cap
Han-Brid
IP65 (in the field)
IP20 (inside)
PROFIBUS-DP switched (S)
RS 485 Sub-D
Conducting: 3RK1911-1AB32 (pin/socket)
Hybrid field bus fiber-optic cable
e. g. 6XV1830-6DH30
PROFIBUS standard cable
Bus plug
e. g. 6ES7 972-0BB11-0XA0 e. g. OP 27
Slave 4
Station 1
2 x 24 V DC
3~
e. g. Power & Control Module (PCM)
ECOFAST System Manual
GWA 4NEB 950 5228-02 6-9
Commissioning
Hybrid Field Bus Connections
6.3.5 Cascading of the Active Hybrid Field Bus Connections
The active hybrid field bus connections 3RK1911-1AE22 and 3RK1911-1AE32, as well as
3RK1911-1AB22 and RK1911-1AB32 have only one repeater function from IP20 (S2) to IP67
(S1, S1’) and vice versa. Not between S1 and S1’.
S1 and S1’ are only looped through internally.
6.3.6 Power Supply of the Bus Terminating Connector
All bus terminating connectors that are connected at the IP67 side have to be supplied via a
24 V DC operating voltage, i.e. the voltage (+NS and -NS) applied, for example, at segment
S1’, must be jumpered to segment S1 at the terminal.
Without a terminating resistor, safe data operation cannot be guaranteed.
Fig. 6-6: Schematic diagram of the use of bus terminating connectors
SPS
+S –S –NS +NS
BU BU
S1 S1‘
S1
S1‘
S1‘
R
R
R
R
+S –S –
NS +NS
Sti BU
S1 S1‘
R
Slave
MBK
R
Slave
MBK
2 m
20 m
200 m
5 m
S1
S1‘
S1‘
SPS
+S –S –NS
BU BU
S1 S1‘
S1
S1‘
S1‘
R
R
R
R
+S –S –NS
Sti BU
S1 S1‘
S1
S1‘
S1‘
R
Slave
MBK
R
Slave
MBK
2 m
20 m
200 m
5 m
Commissioning
Hybrid Field Bus Connections
ECOFAST System Manual
6-10 GWA 4NEB 950 5228-02
6.3.7 Active Hybrid Field Bus Connection for Supply
Fig. 6-7: 3RK1911-1AE22 active hybrid field bus connection (socket/socket)
Typical set-up:
IP20 (inside):
PLC/DP master/PROFIBUS-DP via RS 485
Power supply for switched/non-switched voltage
Active hybrid field bus connection for combining PROFIBUS-DP 9-pin SUB-D
(socket) + power supplies (Cage Clamp)
Segment divided left and right
IP65 (in the field):
PROFIBUS-DP supply with RS 485 in the segment (left and right) via Han-Brid (sockets)
Bus terminating connector (left/right) on the last data tee connector
Power supply (NS + S) via Han-Brid (sockets)
Cage Clamp
Slave 4Slave 3
IP65 (in the field)
IP20 (inside)
Hybrid cable RS 485
non
switched (NS)
Power supply
Bus terminating
connector
Hybrid feld bus connection
Supply: 3RK1911-1AE22 (socket/socket)
SIMATIC
e. g. CPU 315-2 DP
PROFIBUS-DP
RS 485 switched (S)
SUB-D
Note:
Bus terminating
connectors are
plugged directly
onto the data tee
connector
ECOFAST System Manual
GWA 4NEB 950 5228-02 6-11
Commissioning
Hybrid Field Bus Connections
6.3.8 Active Hybrid Field Bus Connection for Supply
Fig. 6-8: 3RK1911-1AE22 active hybrid field bus connection (socket/socket)
Typical set-up:
IP20 (inside):
PLC/DP master with PROFIBUS-DP via RS 485
Power supply for several non-switched and independently-switched voltages (creation of
several EMERGENCY STOP circuits, disconnection of individual segments) via cage
clamp
Linear design of PROFIBUS DP on the inside (IP20) of the hybrid field bus connections
with terminating resistors for the last 9-pin SUB-D connector of the hybrid field bus con-
nection and on the CP of SIMATIC S7
IP65 (in the field):
PROFIBUS-DP supply with RS 485 in three segments (left/right) via Han-Brid (sockets)
Bus terminating connector (left/right) on the last data tee connector
Power supply (NS + S) via Han-Brid (sockets)
Power supply
SIMATIC S7
switched (S)
segment 1/2/3
non
switched. (NS)
segment 1-3
3RK1911-1AE22
Segment 1
left
Segment 1
right
Segment 2
left
Segment 2
right
Segment 3
left
Segment 3
right
PROFIBUS-DP
RS 485
Hybrid field bus cable
6XV1830-7AHxx
9-pin SUB-D
e. g. 6ES7972-0BA50-0AA0
PROFIBUS-DP
RS 485
(socket/socket)
Commissioning
Hybrid Field Bus Connections
ECOFAST System Manual
6-12 GWA 4NEB 950 5228-02
6.3.9 Conveyor Section With Hybrid Field Bus Connections for Supply and
Conducting
Fig. 6-9: Conveyor section with hybrid field bus connections for supply and conducting
SIMATIC S7
Internal bus station
2 x 24 V DC
SV
non switched
switched
RS 485
Hybrid field bus connection
ET 200X-RS 485
Slave 6
FU
M
PROFIBUS DP
M
PROFIBUS standard cable
Bus terminating connector
Hybrid field bus connection
Slave 5 Slave 7
OP in local box ET 200S in local box
OP 27
Hybrid field bus cable RS 485
Slave 3 Slave 4
Bus terminating connector
M
Conducting: 3RK1911-1AA32
pin/socket
e. g. ET 200S/M
RS 485
Supply: 3RK1911-1AA22
socket/socket
ECOFAST System Manual
GWA 4NEB 950 5228-02 6-13
Commissioning
Hybrid Field Bus Connections
6.3.10 Installation System with PROFIBUS-DP - Cu
Fig. 6-10: Installation method with PROFIBUS-DP – Cu
Typical application: Installation system withPROFIBUS DP in Cu
Power & Control Module (PCM) with
Terminating resistor
Bus terminating
Main power cable
PROFIBUS
e. g. CPU 315-2DP
Hybrid field bus cable RS 485
Data tee
Right segment
Left segment
Right segment
Left segment
Slave 3 Slave 4 Slave 5 Slave 9
Slave 11 Slave 12 Slave 32Slave 10
3~
connector
- PLC
- 2 x 24 V DC supply
- 400 V AC main power supply
PROFIBUS CONNECTOR
connected internally
or left segment
connector
or left segment
3/PE-50/60 Hz
400 V AC
CONNECTOR
2 x 24 V cc
Bus terminating connector
Commissioning
Hybrid Field Bus Connections
ECOFAST System Manual
6-14 GWA 4NEB 950 5228-02
6.3.11 PROFIBUS-DP – Fiber-optic Cable
Fig. 6-11: Installation system with PROFIBUS DP fiber-optic cable
Slave 3 Slave 4 Slave 5
Slave 11Slave 10 Slave 12
Slave 9
Slave 32
e. g. CPU 315-2DP
2 x 24 V cc
Typical application: Installation system with PROFIBUS DP fiber-optic cable
Power & Control Module (PCM) with
Terminating resistor
Screw cap
Main power cable
Hybrid field bus fiber-optic cable
Right segment
Data tee
Left segment
connector
Right segment
Left segment
PROFIBUS
- PLC
- 2 x 24 V DC supply
- 400 V AC main power supply
or left segment
or left segment
3/PE-50/60 Hz
400 V AC
CONNECTOR
PROFIBUSCONNECTOR
connected internally
3~
Screw cap
ECOFAST System Manual
GWA 4NEB 950 5228-02 6-15
Commissioning
Hybrid Field Bus Connections
6.3.12 PROFIBUS-DP (Cu) and Passive Hybrid Field Bus Connections with
2 Separate Power Supplies
Fig. 6-12: PROFIBUS-DP (Cu) and passive hybrid field bus connections with 2 separate power sup-
plies
Slave 5 Slave 6 Slave 8 Slave 9
Typical application: Installation system with PROFIBUS DP (Cu) and passive hybrid field bus connections with 2 separate power supplies
e. g. CPU 315-2 DP 2 x 24 V DC
Power supply
switched
non switched
e. g. OP 27
The power supply is not jumpered
Power supply
Slave 7
on the hybrid field bus connection
on Slave 7
=> Segment 1 supplies the OP (Slave 7)
=> Segment 2 of the hybrid field bus
connectopn on Slave 7 is supplied
by the second power supply
Bus terminating
Hybrid field bus cable RS 485
switched
non switched
Slave 3 Slave 4
2 x 24 V DC
connector
with power
M
M
MMMM
BBAA+S -NS +NS
S1S1
S1S1
BBAA+S -S -NS +NS IP20
IP65
IP20
IP65
-S
+S -S -NS +NS
+S -NS +NS-S
S1S1
S1S1
3RK1911-1AA32
3RK1911-1AA 22
Commissioning
Hybrid Field Bus Connections
ECOFAST System Manual
6-16 GWA 4NEB 950 5228-02
6.3.13 PROFIBUS-DP (Cu) and Active Hybrid Field Bus Connections with 2 Sep-
arate Power Supplies
Fig. 6-13: PROFIBUS-DP (Cu) and active hybrid field bus connections with 2 separate power sup-
plies
Typical application: Installation system with PROFIBUS DP (Cu) and active hybrid field bus connections with 2 separate power supplies
Power supply
Screw cap
switched
non switched
2 x 24 V cc
Slave 8
e. g. CPU 315-2 DP
2 x 24 V DC
Power supply
switched
non switched
e. g. OP 27
Hybrid field bus cable
9-pin SUB-D
IP20
IP65
IP20
IP65
Slave 5 Slave 6 Slave 7 Slave 9Slave 3 Slave 4
The power supply is not jumpered
on the hybrid field bus connection
on slave 8
=> Segment 1 supplies the OP (Slave 8)
=> Segment 2 of the hybrid field bus connection
on slave 8 is supplied by the
second power supply
with power
MMMM
M
M
+S
+S
-S
-S -NS
-NS
+NS
+NS
+S
-S-NS
-NS
+NS
+NS
+S
-S
S1S1
S1S1
3RK1911-1AE32
3RK1911-1AE22
S2
S2
ECOFAST System Manual
GWA 4NEB 950 5228-02 6-17
Commissioning
Hybrid Field Bus Connections
6.3.14 PROFIBUS-DP CU and Active Hybrid Field Bus Connections with 2 Sep-
arate Data Supplies
Fig. 6-14: PROFIBUS-DP CU and active hybrid field bus connections with 2 seperate data supplies
Typical application: Installation system with PROFIBUS DP and active hybrid field bus application with 2 separate data supplies
Slave 5 Slave 6
e. g. CPU 315-2 DP
2 x 24 V DC
Power supply
switched
non switched
Slave 3 Slave 4
9-pin SUB-D
Screw cap
Slave 3 Slave 4
Data segment 2
e. g. CPU 315-2 DP
Hybrid field bus
Data segment 1
IP20
IP65
IP20
IP65
In the active hybrid field
bus connection, data is
jumpered as a standard
=> The second hybrid field bus
segment (Data segment 2)
connection in station 2 is
MMMM MM
necessary to supply a new data
-NS
-NS
+NS
+NS
+S
-S
-NS
-NS
+NS
+NS
+S
-S
-NS
-NS
+NS
+NS
+S
-S +S
-S
+S
-S
+S
-S
S1S2
S1S2
S1S1
S2 S2
3RK1911-1AB22
3RK1911-1AB 32
3RK1911-1AB32
fiber-optic cable
Commissioning
Discriminating Module and Maintenance Switch
ECOFAST System Manual
6-18 GWA 4NEB 950 5228-02
6.4 Discriminating Module and Maintenance Switch
To commission the discriminating module/maintenance switch, and thus also the downstream
power bus (sub-)segment, carry out the following steps:
Warning
Hazardous electrical voltages! These may cause electric shock and burns. Disconnect the
system and device from the power supply before starting work.
Notice
Refer to the information in the operating instructions.
Step Activity
1 If you are using motor starters without a thermal motor model and with a motor
supply lead (installation in the vicinity of the motor), also observe the line protec-
tion guidelines in 3.5.5 on page 3-13.
2 Switch on the 400 V AC main power supply
3 Switch on the discriminating module/maintenance switch.
Table 6-7: Sequence of steps for commissioning the discriminating module/maintenance switch
ECOFAST System Manual
GWA 4NEB 950 5228-02 7-1
Technical Data 7
7.1 Power & Control Module
7.1.1 IP65 Version
Order number 4FB2111-2A...-
0AA0
4FB2121-2A...-
0AA0
4FB2111-2A...-
0AA1
4FB2112-2A...-
0AA0
Ausführung
Master/slave PROFIBUS-DP
(Master)
PROFIBUS-DP
(Master)
AS-Interface
(Master)
PROFIBUS-DP
(Slave)
PROFIBUS-DP
(Master)
AS-Interface
(Master)
Protection SIGUARD SIGUARD SIGUARD AS-I monitor
Power supply
Input voltage/range 3AC 400 V/–10% +6%
System frequency/range 50, 60 Hz ± 5%
Main power supply See table "PCM device versions", on page 2-3
Output main power circuit 3 AC 400 V
24 V switched (24 V S)
Output voltage DC 24 V (20.4 V to 28.8 V)
Output current 5 A DC when AS-Interface fitted
10 A DC when AS-Interface not fitted
Residual ripple < 5%
Backup min. 20 ms
24 V DC non switched (24 V NS)
Output voltage DC 24 V (20.4 V to 28.8 V)
Output current DC 10 A DC 10 A DC 10 A DC 10 A
Residual ripple < 5% < 5% < 5% < 5%
Backup min. 20 ms min. 20 ms min. 20 ms min. 20 ms
30 V DC non switched (AS-i)
Output voltage AS-i DC 30 V
(29.5 V to 31.6 V)
—DC 30 V
(29.5 V to 31.6 V)
Output current DC 2.4 A DC 2.4 A
Residual ripple < 300 mVss < 300 mVss
Backup —min. 20 ms—min. 20 ms
ECOFAST System Manual
GWA 4NEB 950 5228-02 7-2
Protection and monitoring
Short circuit protection
Main circuit Built-in circuit-breaker
Auxiliary circuits Built-in residual current-operated protective device
Signaling devices Green (ready for operation)
Yellow (power connected)
Red (internal fault)
Safety
Degree of protection IP65
Approvals (in preparation) CE, UL, CSA
Safety class I
EMC
Emitted interference EN 55 081-2
Noise immunity EN 61000-6-2
Temperatures
Ambient temperature 0 °C to +40 °C, +50 °C
with derating in the main circuit/auxiliary circuits
Transport-/storage temperature –25 °C to +70 °C
Relative humidity 15% to 75% at 25°C (non-condensing)
Air pressure 700 to 1060 hPa
Mechanical environmental conditions
Transport
Vibratory load 3 g
Shock 15 g with 11 ms
Operation
Vibratory load f = 10 to 58 Hz, d = 0.075 mm/58 to 100 Hz, 10 g
Shock 10 g with 6 ms/6 g with 10 ms
Order number 4FB2111-2A...-
0AA0
4FB2121-2A...-
0AA0
4FB2111-2A...-
0AA1
4FB2112-2A...-
0AA0
ECOFAST System Manual
GWA 4NEB 950 5228-02 7-3
Connections/throughfeeds
Input connections Cage – Clamp max. 2 x 16 mm2 max. current carrying capacity
(Throughfeeds 2 x M40x1.5)
Output connections
Main circuit
2 x Han Q4/2 socket (DESINA)
Output connections
Auxiliary circuits/field bus
2 x Han-Brid socket/socket (DESINA)
Output connections
AS-Interface
Cage – Clamp,
2.5 mm2
Throughfeeds
4 x ASi-seal
Cage – Clamp,
2.5 mm2
Throughfeeds
4 x ASi-seal
Output connections
EMERGENCY STOP
Cage – Clamp,
2.5 mm2
Throughfeeds via
cable throughfeed
flange
Cage – Clamp,
2.5 mm2
Throughfeeds via
cable throughfeed
flange
Cage – Clamp,
2.5 mm2
Throughfeeds via
cable throughfeed
flange
Cage – Clamp,
2.5 mm2
Throughfeeds via
cable throughfeed
flange
SIMATIC connections Cage – Clamp, 1.5 mm2
Cable throughfeed flanges 8 x 3.8 to 6.3 mm
2 x 6.1 to 8.8 mm
2 x 7.8 to 10.7 mm
Dimensions/weight
Housing dimensions (WxHxD) 550 x 850 x 255
Overall dimensions (WxHxD) 600 x 920 x 310
Fixing dimensions (WxH) 575 x 695
Fixing holes 4 x M8
Weight max. 77 kg
Fasteners Double-bit key
SIMATIC
Controller S7-300,
CPU 313C-2 DP
I/O module
S7-300,
CPU 313C-2 DP
I/O module
AS Interface master
S7-300,
CPU 313C-2 DP
I/O module
AS Interface master
ET 200M
I/O module
Data transfer rate max. 12 Mbit/s
Main memory EEPROM
MMC
IM151,
64 KByte
IM151,
64 KByte
IM151,
64 KByte
MMC Included Included Included
Unassigned SIMATIC inputs 6 6 6 6
Unassigned SIMATIC outputs 13 13 13 13
External interfaces PROFIBUS-DP PROFIBUS-DP PROFIBUS-DP PROFIBUS-DP
Order number 4FB2111-2A...-
0AA0
4FB2121-2A...-
0AA0
4FB2111-2A...-
0AA1
4FB2112-2A...-
0AA0
ECOFAST System Manual
GWA 4NEB 950 5228-02 7-4
7.1.2 IP00 Version (Control Cabinet Version)
Order number 4FB2111-2A...-
0AA2
4FB2121-2A...-
0AA1
4FB2111-2A...-
0AA3
4FB2112-2A...-
0AA1
Ausführung
Master/slave PROFIBUS-DP
(master)
PROFIBUS-DP
(master)
AS-Interface
(master)
PROFIBUS-DP
(slave)
PROFIBUS-DP
(master)
AS-Interface
(master)
Protection SIGUARD SIGUARD SIGUARD AS-I monitor
Power supply
Input voltage/range 3AC 400 V/–10% +6%
System frequency/range 50, 60 Hz ± 5%
Main power supply See table "PCM device versions", on page 2-3
Output/Main circuit 3 AC 400 V
24 V switched (24 V S)
Output voltage DC 24 V (20.4 V to 28.8 V)
Output current 5 A DC when AS-Interface fitted
10 A DC when AS-Interface not fitted
Residual ripple < 5%
Backup min. 20 ms
24 V DC non switched (24 V NS)
Output voltage DC 24 V (20.4 V bis 28.8 V)
Output current DC 10 A DC 10 A DC 10 A DC 10 A
Residual ripple < 5% < 5% < 5% < 5%
Backup min. 20 ms min. 20 ms min. 20 ms min. 20 ms
30 V DC non switched (AS-i)
Output voltage AS-i DC 30 V
(29.5 V to 31.6 V)
DC 30V
(29.5 V to 31.6 V)
Output current DC 2.4 A DC 2.4 A
Residual ripple < 300 mVss < 300 mVss
Backup min. 20 ms min. 20 ms
Protection and monitoring
Short circuit protection
Main circuit Built in circuit-breaker
Auxiliary circuit Built in residual current-operated protective device
Signaling devices Green (ready for operation)
Yellow (power connected)
Red (internal fault)
ECOFAST System Manual
GWA 4NEB 950 5228-02 7-5
Safety
Degree of protection IP65
Approvals (in preparation) CE, UL, CSA
Safety class I
EMC
Emitted interference EN 55 081-2
Noise immunity EN 61000-6-2
Temperatures
Ambient temperature 0 °C to +40 °C, +50 °C with derating in the main circuit/auxiliary circuits
Transport-/storage temperature –25 °C to +70 °C
Relative humidity 15% to 75% at 25 °C (non-condensing)
Air pressure 700 to 1060 hPa
Mechanical environmental conditions
Transport
Vibratory load 3 g
Shock 15 g with 11 ms
Operation
Vibratory load f = 10 to 58 Hz, d = 0.075 mm/58 to 100 Hz, 10 g
Shock 10 g with 6 ms/6 g with 10 ms
Connections/throughfeeds
Input connections Cage – Clamp max. 2 x 16 mm2 max. current carrying capacity
Output connections
Main circuit
Cage – Clamp,
2.5 mm2Cage – Clamp,
2.5 mm2Cage – Clamp,
2.5 mm2Cage – Clamp,
2.5 mm2
Output connections
Auxiliary circuits
Cage – Clamp,
2.5 mm2Cage – Clamp,
2.5 mm2Cage – Clamp,
2.5 mm2Cage – Clamp,
2.5 mm2
Output connections
AS-Interface
Cage – Clamp,
2.5 mm2
Throughfeeds
4 x ASi-Dichtung
Cage – Clamp,
2.5 mm2
Throughfeeds
4 x ASi-Dichtung
Output connections
EMERGENCY STOP
Cage – Clamp,
2.5 mm2Cage – Clamp,
2.5 mm2Cage – Clamp,
2.5 mm2Cage – Clamp,
2.5 mm2
SIMATIC connections Cage – Clamp, 1.5 mm2
Dimensions/weight
Dimensions (WxHxD) 520 x 830 x 240
Fixing dimensions (WxH) 350 x 809
Fixing holes 4 x M8
Weight max. 55 kg
Order number 4FB2111-2A...-
0AA2
4FB2121-2A...-
0AA1
4FB2111-2A...-
0AA3
4FB2112-2A...-
0AA1
ECOFAST System Manual
GWA 4NEB 950 5228-02 7-6
7.2 Alternative Power Supplies
7.2.1 Simple Energy Unit (SEU)
For the technical data of the circuit-breaker and the contactor, please refer to the manual enc-
losed with the device.
7.2.2 ET 200S Motor Starter
For the technical data of the motor starter ET 200S, please refer to the manual in the
6ES7151-1AA10-8AA0 documentation package.
SIMATIC
Controllers S7-300,
CPU 313C-2 DP
I/O module
S7-300,
CPU 313C-2 DP
I/O module
AS-interface master
S7-300,
CPU 313C-2 DP
I/O module
AS-interface master
ET 200M
I/O module
Data transfer rate to 12 Mbit/s
Main memoryEEPROM
MMC
IM151,
64 KByte
IM151,
64 KByte
IM151,
64 KByte
MMC Included Included Included
Unassigned SIMATIC inputs 6 6 6 6
Unassigned SIMATIC outputs 13 13 13 13
External interfaces PROFIBUS-DP PROFIBUS-DP PROFIBUS-DP PROFIBUS-DP
Order number 4FB2111-2A...-
0AA2
4FB2121-2A...-
0AA1
4FB2111-2A...-
0AA3
4FB2112-2A...-
0AA1
ECOFAST System Manual
GWA 4NEB 950 5228-02 7-7
7.3 Hybrid Field Bus Connections
General technical Data
Location On the system Mounted directly on the control cabinet
Installation position Any
Degree of protection Control cabinet
Field bus
IP20
IP65/67
Enclosure dimensions (HxWxD) 103 x 93 x 65
Weight ca. 250 g
Operating temperature –25 °C to +50 °C
Storage-/transport temperature –40 °C to +80 °C
Vibratory load 5 g
Rated insulation voltage 500 V AC
Standards, approvals DIN VDE 0627, DIN EN 61984,
DIN EN 60529, DIN VDE 0160,
DIN EN 50178, DIN EN 50170
UL 1977, CSA in preparation
Electrical Data Auxiliary Power
Rated voltage
24 V DC, non-switched (NS) 24 V DC –25%/+50% 18 V to 36 V
24 V DC, switched (S) 24 V DC –25%/+50% 18 V to 36 V
Rated current max. 10 A For each rated voltage
Voltage supply from 24 V DC non-switched (NS)
Current consumption max. 130 mA
Voltage failure bypass > 20 ms
ECOFAST System Manual
GWA 4NEB 950 5228-02 7-8
7.4 Data Tee Plug Connector
Electrical Data for Communikation
Passive Active
RS 485 version RS 485 version Fiber-optic cable version
Baud rates supported 12,000 kBd
6,000 kBd
3,000 kBd
1,500 kBd
500 kBd
187.5 kBd
93.75 kBd
45.45 kBd
19.2 kBd
9.6 kBd
12,000 kBd
6,000 kBd
3,000 kBd
1,500 kBd
500 kBd
187.5 kBd
93.75 kBd
45.45 kBd
19.2 kBd
9.6 kBd
12,000 kBd
(6,000 kBd) not permitted
(3,000 kBd) not permitted
1,500 kBd
500 kBd
187.5 kBd
93.75 kBd
45.45 kBd
19.2 kBd
9.6 kBd
Cascade depth*) 3 9 at 12,000 kBd
32 at other baud rates
Maximum permissible RS 485/
fiber-optic cable length (POF)
between 2 stations
Depending on the
baud rate
50 m
*) Maximum number of hybrid field bus connections in the RS 485/fiber-optic cable segment.
If the DP master for a fiber-optic cable system is located centrally with regard to topology, the maximum cascade depth
is permissible at each fiber-optic cable segment connected to the DP master.
General Technical Data
Location On the system Connected to motor starter
Installation position Any
Degree of protection IP65/67 Watertight acc. to IEC 529 (DIN 40050)
Cooling Convection No additional cooling required
Weight 105 g
100 g
Copper variante
Fibe-optic cable variant
Operating temperature –20 °C to + 40 °C Non condensing
Max. 55 °C with reduktion of IDC24V-NS and
IDC24V-S each with je 0.3 A per K
Storage/transport temperature –40 °C to +80 °C
Relative humidity 5% to 95% Non condensing
Site altitude 2000 m No restrictions
Vibratory load f = 5 to 26 Hz; d = 0.75 mm 10 Zyklen/f = 26 to 150 Hz; a = 2 g
Shock a = 150 m/s2 (15 g) with 11 ms each with 3 shocks in all axes (=18)
ESD 8 kV air discharge
6 kV contact discharge
IEC 1000-4-2 Severity 3
Electromagnetic fields 10 V/m IEC 1000-4-3 Severity 3
ECOFAST System Manual
GWA 4NEB 950 5228-02 7-9
BURST 2 kV/5 kHz supply voltage
1 kV/5 kHz data cables
2 kV/5 kHz process cables
IEC 1000-4-4 Severity 3
Emitted interference Limit value class A EN 55011
General Technical Data
Electrical Data Auxiliary Power
Non switched Voltage, DC24V-NS Switched Voltage DC24V-S
Voltage range 20.4 V DC to 28.8V DC standard power supply acc. to DIN 19240
Maximum current-carrying capa-
city from Han-brid to Han-brid
10 A 10 A
Polarity protection no no
Short circuit protection/
overload protection
no no
Insulation voltage 500 V DC between auxiliary voltages and PE
Electrical Data for Communication
Copper Variant Fiber-optic Cable Variante
Baud rates supported 12,000 kBd
6,000 kBd
3,000 kBd
1,500 kBd
500 kBd
187.5 kBd
93.75 kBd
45.45 kBd
19.2 kBd
9.6 kBd
12,000 kBd
(6,000 kBd) not permitted
(3,000 kBd) not permitted
1,500 kBd
500 kBd
187.5 kBd
93.75 kBd
45.45 kBd
19.2 kBd
9.6 kBd
Cascade depth*) 9 at 12,000 kBd
32 at other baud rates
Maximum permissible fiber-optic
cable length (POF) between
2 stations
50 m
*) Maximum number of data tee connectors in the fiber-optic cable segment.
If the DP master for a fiber-optic cable system is located centrally with regard to topology, the maximum cascade depth
is permissible at each fiber-optic cable segment connected to the DP master.
ECOFAST System Manual
GWA 4NEB 950 5228-02 7-10
7.5 Discriminating Module
General Technical Data
Location On the system Wall mounting
Mounted directly on the
ECOFAST consumer *)
Installation position Any
Degree of protection IP65/67 Watertight acc. to IEC 529 (DIN 40050)
Enclosure dimensions (HxWxD) 205 x 105 x 140
Weight 1.5 kg
Operating temperature –20 °C to +40 °C
Storage-/transport temperature –40 °C to +80 °C
Vibratory load 5 g
Rated insulation voltage 500 V AC
Locking device 3 padlocks acc. to IEC 60 204-1
Standards, approvals IEC 69 947,
IEC 60 204-1,
DIN VDE 0627
UL 1977, CSA
*) Not possible if ECOFAST motor starters are operated with PROFIBUS-DP
ECOFAST System Manual
GWA 4NEB 950 5228-02 8-1
Dimension Drawings 8
8.1 Power & Control Module
8.1.1 IP65 Version
Fig. 8-1: Power & Control Module, IP65 version
600 ± 2
576
850 ± 2
50 ± 0.2
695 ± 1
Ø 9
Ø 15
4 x
255 max.
310 max.
920 max.
695
576
8
4 x
Drilling dimensions:
Clearance (hatched):
400
PCM
400
100* 100
150*
* Allow clearance for plug if necessary!
Dimension Drawings
Power & Control Module
ECOFAST System Manual
8-2 GWA 4NEB 950 5228-02
8.1.2 IP00 Version (Control Cabinet Version)
Fig. 8-2: Power & Control Module, IP00 version (control cabinet version)
520
350
830
809
Ø 9
2 x
224
2 x
Ø 9
809
350
8
4 x
Drilling dimensions:
ECOFAST System Manual
GWA 4NEB 950 5228-02 8-3
Dimension Drawings
Alternative Power Supplies
8.2 Alternative Power Supplies
8.2.1 Simple Energy Unit (SEU)
Circuit-breaker
Fig. 8-3: 3RV10.. circuit-breaker
S00
S0
S2
45
90
70
76
918
62
5
4512
45
3,5
18
25
5
105
45
14
12
90
97
45 556
80
91
45
69
18 18
72
9
5
25
106
20
5518 18
45
85
109
121
127
5
8
132
144
140
89
125
9
5
30
130
Dimension Drawings
Alternative Power Supplies
ECOFAST System Manual
8-4 GWA 4NEB 950 5228-02
Contactors
Fig. 8-4: Contactors 3RT10..
20
75
171 a
112
5
15 64 110
159
107 5
18
35
55
10
95
45
72
5
Test
01
AH
STOP RESET
14
S00
S0
S2
4 5
a
2 )
1 4 3
6 3
8 6
10 135
7 2
1 5 , 5
1 0
8 6
5
5
3 5
6 0
5
Drill pattern
5
50
35
5 9
45
37
60
47
44
25
68 109
5
36
ECOFAST System Manual
GWA 4NEB 950 5228-02 8-5
Dimension Drawings
Alternative Power Supplies
8.2.2 ET 200S Motor Starter
Fig. 8-5: ET 200S motor starter
66
7
138
149
48
43
99
126
100
290
333
23
DS=65
RS=130
135
Connection area
Sectional rail
35 x 7,5 mm
min. 35 mm
Clearance for
heat dissipation
min. 35 mm
Clearance for
heat dissipation
Sectional rail
35 x 7,5 mm
Dimension Drawings
Power Tee Clamp Connector
ECOFAST System Manual
8-6 GWA 4NEB 950 5228-02
8.3 Power Tee Clamp Connector
Fig. 8-6: Power tee/tee-tee clamp connector
112.6
158
130 55
142.5
78.5
Ø5.5
Ø5.5
Power tee clamp connector
112.6
158
130 55
142.5
78.5
Ø5.5
Ø5.5
Power tee-tee clamp connector
Seals for power tee/tee-tee clamp connector
D: Depends on the cable cross section
34
34
D
ECOFAST System Manual
GWA 4NEB 950 5228-02 8-7
Dimension Drawings
Hybrid Field Bus Connections
8.4 Hybrid Field Bus Connections
Fig. 8-7: Dimension drawing of the hybrid field bus connection
93
103
5 max.
65
IP20 IP65
80
90
Cut out section on control cabinet:
Dimension Drawings
Data Tee Plug Connector
ECOFAST System Manual
8-8 GWA 4NEB 950 5228-02
8.5 Data Tee Plug Connector
Fig. 8-8: Dimension drawing of the data tee plug connector
ECOFAST System Manual
GWA 4NEB 950 5228-02 8-9
Dimension Drawings
Discriminating Module and Maintenance switch
8.6 Discriminating Module and Maintenance switch
Fig. 8-9: Discriminating module with M12 connector
Fig. 8-10: Maintenance switch
105
230
135
155
C
F
A
KHM
G
d
A1
A1
A= 94 B= 125 A1 = 110
B1 = 80 C= 36 d= 4.5
D = 4 x PG16 E= 21 F= n/a
G= n/a H= 82 K= 67
M= 36
Dimension Drawings
Discriminating Module and Maintenance switch
ECOFAST System Manual
8-10 GWA 4NEB 950 5228-02
ECOFAST System Manual
GWA 4NEB 950 5228-02 9-1
Order Numbers 9
9.1 Motor Starters (Reversing Starters)
Setting Range*Motor Protection/
Switching
Technology
Brake Field Bus Order Number
ECOFAST Motor Starters
0.3 A - 9 A (4 kW) Temperature
sensor/
Mechanical
AS-Interface 3RK1323-2AS54-1AA0
400 V AC AS-Interface 3RK1323-2AS54-1AA3
0.3 A - 9 A (4 kW) Temperature
sensor/
Mechanical
PROFIBUS-DP 3RK1303-2AS54-1AA0
400 V AC PROFIBUS-DP 3RK1303-2AS54-1AA3
ECOFAST Motor Starter High Feature
0.3 A - 3 A (1.1 kW) Thermal
Motor Model/
Mechanical
PROFIBUS-DP 3RK1303-5BS44-3AA0
2.4 A - 9 A (4 kW) PROFIBUS-DP 3RK1303-5CS44-3AA0
0.3 A - 3 A (1.1 kW) 400 V AC PROFIBUS-DP 3RK1303-5BS44-3AA3
2.4 A - 9 A (4 kW) 400 V AC PROFIBUS-DP 3RK1303-5CS44-3AA3
0.3 A - 3 A (1.1 kW) Thermal
Motor Model/
Mechanical
AS-Interface 3RK1323-5BS44-3AA0
2.4 A - 9 A (4 kW) AS-Interface 3RK1323-5CS44-3AA0
0.3 A - 3 A (1.1 kW) 400 V AC AS-Interface 3RK1323-5BS44-3AA3
2.4 A - 9 A (4 kW) 400 V AC AS-Interface 3RK1323-5CS44-3AA3
0.3 A - 3 A (1.1 kW) Full Motor
Protection/
Electronic-Soft
PROFIBUS-DP 3RK1303-6BS74-3AA0
2.4 A - 12 A (5.5 kW) PROFIBUS-DP 3RK1303-6DS74-3AA0
0.3 A - 3 A (1.1 kW) 400 V AC PROFIBUS-DP 3RK1303-6BS74-3AA3
2.4 A - 12 A (5.5 kW) 400 V AC PROFIBUS-DP 3RK1303-6DS74-3AA3
0.3 A - 3 A (1.1 kW) Full Motor
Protection/
Electronic-Soft
AS-Interface 3RK1323-6BS74-3AA0
2.4 A - 12 A (5.5 kW) AS-Interface 3RK1323-6DS74-3AA0
0.3 A - 3 A (1.1 kW) 400 V AC AS-Interface 3RK1323-6BS74-3AA3
2.4 A - 12 A (5.5 kW) 400 V AC AS-Interface 3RK1323-6DS74-3AA3
0.6 A - 4 A (1.5 kW) Full Motor
Protection/
Electronic-Soft
(Duo-Reversing
Soft)
400 V AC AS-Interface 3RK1323-6ES84-3AA3
0.6 A - 4 A (1.5 kW) 400 V AC PROFIBUS-DP 3RK1303-6ES84-3AA3
*) Power descriptions are valid for 400 V AC
Order Numbers
Motor Connection Cables
ECOFAST System Manual
9-2 GWA 4NEB 950 5228-02
9.2 Motor Connection Cables
Description Order No.
Motor Connection Cables (not shielded)
Han 10 E pin on one side to connect the motor starter with the motor
(for mounting in the vicinity of the motor)
- 7 x 1.5 mm2 1.5 m
- 7 x 1.5 mm2 < 3 m, any length
- 7 x 1.5 mm2 3.0 m
- 7 x 1.5 mm2 > 3 m to < 5 m, any length
- 7 x 1.5 mm2 5.0 m
3RK1911-0BG10
3RK1911-0CG20
3RK1911-0BG20
3RK1911-0CG30
3RK1911-0BG30
Han 10 E pin on one side to connect the motor starter with the motor
(for mounting in the vicinity of the motor)
- 11 x 1.5 mm2 1.5 m
- 11 x 1.5 mm2 < 3 m, any length
- 11 x 1.5 mm2 3.0 m
- 11 x 1.5 mm2 > 3 m to < 5 m, any length
- 11 x 1.5 mm2 5.0 m
3RK1911-0BJ10
3RK1911-0CJ20
3RK1911-0BJ20
3RK1911-0CJ30
3RK1911-0BJ30
Han 10 E on both sides to connect the motor starter with the motor
(for mounting in the vicinity of the motor)
- 7 x 1.5 mm2 1.5 m
- 7 x 1.5 mm2 < 3 m, any length
- 7 x 1.5 mm2 3.0 m
- 7 x 1.5 mm2 > 3 m to < 5 m, any length
- 7 x 1.5 mm2 5.0 m
3RK1911-0BH10
3RK1911-0CH20
3RK1911-0BH20
3RK1911-0CH30
3RK1911-0BH30
Han 10 E on both sides to connect the motor starter with the motor
(for mounting in the vicinity of the motor)
- 11 x 1.5 mm2 1.5 m
- 11 x 1.5 mm2 < 3 m, any length
- 11 x 1.5 mm2 3.0 m
- 11 x 1.5 mm2 > 3 m to < 5 m, any length
- 11 x 1.5 mm2 5.0 m
3RK1911-0BK10
3RK1911-0CK20
3RK1911-0BK20
3RK1911-0CK30
3RK1911-0BK30
Motor Connection Cables (shielded)
Han 10 E pin on one side to connect the motor starter with the motor
(for mounting in the vicinity of the motor)
- 8 x 1.5 mm2 < 1.5 m
- 8 x 1.5 mm2 1.5 m
- 8 x 1.5 mm2 < 3 m, any length
- 8 x 1.5 mm2 3.0 m
- 8 x 1.5 mm2 > 3 m to < 5 m, any length
- 8 x 1.5 mm2 5.0 m
3RK1911-0CV10
3RK1911-0BV10
3RK1911-0CV20
3RK1911-0BV20
3RK1911-0CV30
3RK1911-0BV30
ECOFAST System Manual
GWA 4NEB 950 5228-02 9-3
Order Numbers
Power Cables
9.3 Power Cables
Motor Connection Cables (shielded)
Han 10 E on both sides to connect the motor starter with the motor
(for mounting in the vicinity of the motor)
- 8 x 1.5 mm2 < 1.5 m
- 8 x 1.5 mm2 1.5 m
- 8 x 1.5 mm2 < 3 m, any length
- 8 x 1.5 mm2 3.0 m
- 8 x 1.5 mm2 > 3 m to < 5 m, any length
- 8 x 1.5 mm2 5.0 m
3RK1911-0CU10
3RK1911-0BU10
3RK1911-0CU20
3RK1911-0BU20
3RK1911-0CU30
3RK1911-0BU30
Unassembled
- 8 x 1.5 mm2 20 m
- 8 x 1.5 mm2 50 m
- 8 x 1.5 mm2 100 m
3RK1911-0BW60
3RK1911-0BW70
3RK1911-0BW80
Description Order No.
Description Order No.
Spur cables
Han Q4/2 pin/Han Q4/2 socket
- 5 x 4.0 mm2 < 3 m. any length
- 5 x 4.0 mm2 > 3 m to < 5 m, any length
- 5 x 4.0 mm2 > 5 m to < 10, any length
- 5 x 4.0 mm2 > 10 m to < 15 m, any length
- 5 x 6 mm2 < 3 m, any length
- 5 x 6 mm2 > 3 m to < 5 m, any length
- 5 x 6 mm2 > 5 m to < 10 m, any length
- 5 x 6 mm2 > 10 m to < 15m, any length
3RK1911-0CP21
3RK1911-0CP31
3RK1911-0CP41
3RK1911-OCP51
3RK1911-0CP22
3RK1911-0CP32
3RK1911-0CP42
3RK1911-0CP52
ET200X sub-segment lines
Han Q4/2 pin/Han Q8/0 socket
- 5 x 4.0 mm2 < 3 m, any length
- 5 x 4.0 mm2 > 3 m to < 5 m, any length
- 5 x 4.0 mm2 > 5 m to < 10, any length
- 5 x 4.0 mm2 > 1 0 m to < 15 m, any length
3RK1911-0CR21
3RK1911-0CR31
3RK1911-0CR41
3RK1911-OCR51
Cut-to-length
- 5 x 4.0 mm2 20 m
- 5 x 4.0 mm2 50 m
- 5 x 4.0 mm2 100 m
- 5 x 6.0 mm2 20 m
- 5 x 6.0 mm2 50 m
- 5 x 6.0 mm2 100 m
3RK1911-0AG60
3RK1911-0AG70
3RK1911-0AG80
3RK1911-0AH60
3RK1911-0AH70
3RK1911-0AH80
Order Numbers
Power & Control Modules (Infeed Modules)
ECOFAST System Manual
9-4 GWA 4NEB 950 5228-02
9.4 Power & Control Modules (Infeed Modules)
9.5 Simple Energy Unit (SEU)
Description Order No.
PROFIBUS S7-300 (Master)
Main power supply 3 AC 400 V, 40 A
Auxiliary power supply 2x DC 24 V
Rotary actuator with main switch functions
SIGUARD contactor safety combination Autostart
Dimensions (W x H x D) in mm: 400 x 650 x 248
4FB2111-2AE01-0AA0
PROFIBUS S7-300 (Master) and AS-i-Bus (Master)
Main power supply 3 AC 400 V, 40 A
Auxiliary power supply 2 x DC 24 V, 1x AS-i
Rotary actuator with main switch functions
SIGUARD contactor safety combination Autostart
Dimensions (W x H x D) in mm: 400 x 650 x 248
4FB2121-2AE01-0AA0
PROFIBUS S7-300 (Master) und AS-i-Bus (Master)
Main power supply 3 AC 400 V, 25 A
Auxiliary power supply 2x DC 24 V, 1x AS-i
Rotary actuator with EMERGENCY STOP functions
AS-i monitor for SAFETY AT WORK
Dimensions (W x H x D) in mm: 400 x 650 x 248
4FB2112-2AC01-0AA0
PROFIBUS ET 200B (Slave)
Main power supply 3 AC 400 V, 40 A
Auxiliary power supply 2x DC 24 V
Rotary actuator with main switch functions
SIGUARD contactor safety combination Autostart
Dimensions (W x H x D) in mm: 400 x 650 x 248
4FB2111-2AE01-0AA1
Description Circuit-Breaker Contactor with Aux. Switch
S00 8.00 A 3RV10 11-1HA10 3RT1015-1BB44-3MA
S0 8.00 A 3RV10 21-1HA10 3RT1024-1BB44-3MA
S2 16.00 A 3RV10 31-4AA10 3RT1026-1BB44-3MA0
S2 20.00 A 3RV10 31-4BA10 3RT1026-1BB44-3MA0
S2 25.00 A 3RV10 31-4DA10 3RT1034-1BB44
S2 32.00 A 3RV10 31-4EA10 3RT1034-1BB44
S2 40.00 A 3RV10 31-4FA10 3RT1035-1BB44
S2 50.00 A 3RV1031-4HA10 3RT1036-1BB44
ECOFAST System Manual
GWA 4NEB 950 5228-02 9-5
Order Numbers
Discriminating Modules
9.6 Discriminating Modules
9.7 Maintenance Switch
9.8 Hybrid Field Bus Cables
Description Order No.
Discriminating Module
Used to selectively disconnect feeders with a repair switch function in order
to protect the line in case of a change in cross-section and to increase the
size of the segments. Connected to AS-Interface.
for 400 V AC, 8 A
for 400 V AC, 16 A
for 400 V AC, 25 A
3RK1911-4AB08
3RK1911-4AB16
3RK1911-4AB25
Description Order No.
Maintenance switch with M12 connector
25 A rated current 6AG1264-1GP51-6AA0
Description Order No.
PROFIBUS ECOFAST Hybrid field bus fiber-optic cable
Trailing cable (PUR casing) with two plastic FO conductors for PROFIBUS-DP
and four copper cores with 1.5 mm2 (DESINA-compatible)
Pre-assembled with two ECOFAST connectors
1.5 m 6XV1 830-7DH15
3 m 6XV1 830-7DH30
5 m 6XV1830-7DH50
10 m 6XV1830-7DN10
15 m 6XV1830-7DN15
Unassembled cable
20 m 6XV1830-7CN20
50 m 6XV1830-7CN50
100 m 6XV1830-7CT10
Order Numbers
AS-Interface Shaped Cable
ECOFAST System Manual
9-6 GWA 4NEB 950 5228-02
9.9 AS-Interface Shaped Cable
PROFIBUS ECOFAST Hybrid Cable – Copper
Trailing cable (PUR casing) with two shielded copper conductors for
PROFIBUS-DP and four copper cores with 1.5 mm2
Pre-assembled with two ECOFAST connectors
1. 5 m 6XV1830-7BH15
3 m 6XV1830-7BH30
5 m 6XV1830-7BH50
10 m 6XV1830-7BN10
15 m 6XV1830-7BN15
20 m 6XV1830-7BN20
25 m 6XV1830-7BN25
30 m 6XV1830-7BN30
35 m 6XV1830-7BN35
40 m 6XV1830-7BN40
45 m 6XV1830-7BN45
50 m 6XV1830-7BN50
Unassembled cable
Cut-to-length 6XV1830-7AH10
20 m 6XV1830-7AN20
50 m 6XV1830-7AN50
100 m 6XV1830-7AT10
Description Order No.
Description Order No.
Material Color Quantity
Rubber Yellow (AS-Interface) 100 m roller 3RX9010-0AA00
1 km drum 3RX9012-0AA00
Black (DC 24 V) 100 m roller 3RX9020-0AA00
1 km drum 3RX9022-0AA00
TPE Yellow (AS-Interface) 100 m roller 3RX9013-0AA00
1 km drum 3RX9014-0AA00
Black (DC 24 V) 100 m roller 3RX9023-0AA00
1 km drum 3RX9024-0AA00
TPE
Special design acc. to UL Class2
Yellow (AS-Interface) 100 m roller 3RX9017-0AA00
Black (DC 24 V) 100 m roller 3RX9027-0AA00
PUR Yellow (AS-Interface) 100 m roller 3RX9015-0AA00
1 km drum 3RX9016-0AA00
Black (DC 24 V) 100 m roller 3RX9025-0AA00
1 km drum 3RX9026-0AA00
ECOFAST System Manual
GWA 4NEB 950 5228-02 9-7
Order Numbers
Hybrid Field Bus Connections
9.10 Hybrid Field Bus Connections
9.11 Connectors
Description Order No.
Hybrid field bus connection
Interface between control cabinet/infeed module (IP20)
and the field IP67
Data via 2 x copper shielded/FO
2 x 24 V DC for switched/non-switched voltage
Infeeding of data and 2 x 24 V into the hybrid fieldbus cable, 2 channels
Hybrid field bus connection Cu/Cu, socket/socket for supply
Hybrid field bus connection Cu/Cu, pin/socket conducting
Hybrid field bus connection Cu//FO, socket/socket for supply (active)
Hybrid field bus connection Cu/FO, pin/socket conducting (active)
Hybrid field bus connection Cu/Cu, socket/socket for supply (active)
Hybrid field bus connection Cu/Cu, pin/socket conducting (active)
Hybrid field bus connection Cu/Cu, Fast Connect, for supply
Hybrid field bus connection Cu/Cu, Fast Connect, conducting
3RK1911-1AA22
3RK1911-1AA32
3RK1911-1AB22
3RK1911-1AB32
3RK1911-1AE22
3RK1911-1AE32
3RK1911-1AF22
3RK1911-1AF32
Description Order No.
Data + 24 V
Data tee Connector Cu
Data tee Connector FO
Bus terminating connector for PROFIBUS-DP, 1 piece
Bus terminating connector for PROFIBUS-DP, 5 pieces
3RK1911-2AG00
3RK1911-2AH00
6GK1905-0DA10
6GK1905-0DA00
PROFIBUS FO plug connector FO, 5 pieces
with 2x plastic FO and 4x copper conductors 1.5 mm2
with pin insert
with socket insert
6GK1905-0BA00
6GK1905-0BB00
PROFIBUS copper-cable plug connector, 5 pieces
with 2x shielded copper and 4x copper conductors 1.5 mm2
with pin insert
with socket insert
6GK1905-0CA00
6GK1905-0CN00
Order Numbers
Connectors
ECOFAST System Manual
9-8 GWA 4NEB 950 5228-02
Power
Power tee clamp connector (round cable adapter) for 400 V AC
Used to connect feeders to any point on the power bus by means of standard
round cables (insulation displacement method).
Power tee clamp connector up to 4 mm2
Power tee clamp connector up to 6 mm2
Power tee-tee clamp connector up to 6 mm2
Seals for power tee clamp connector
For power cable with Ø 10 to 13 mm
For power cable with Ø 13 to 16 mm
For power cable with Ø 16 to 19 mm
For power cable with Ø 19 to 22 mm
Filler plug
3RK1911-2BF01
3RK1911-2BF02
3RK1911-2BG02
3RK1911-5BA00
3RK1911-5BA10
3RK1911-5BA20
3RK1911-5BA30
3RK1911-5BA50
Connector set Han 10E pin in thin coupling enclosure PG 16
Connector set Han 10E pin in thick coupling enclosure PG 21
Connector set Han 10E socket in thin funnel enclosure PG 16
Connector set Han 10E socket in thick funnel enclosure PG 21
Connector set Han 10E pin EMC
Connector set Han 10E socket EMC
3RK1911-2BK00
3RK1911-2BL00
3RK1911-2BM00
3RK1911-2BN00
3RK1911-2BL10
3RK1911-2BN10
Description Order No.
ECOFAST System Manual
GWA 4NEB 950 5228-02 9-9
Order Numbers
Project Engineering Software and Documentation
9.12 Project Engineering Software and Documentation
Description Order No.
Project Engineering Software
ECOFAST ES
Graphical power bus configuration
Power bus dimensioning
Operator prompting for selection of Siemens A&D products
Norm-compliant power system design
Documentation
3ZS1200-0CC13-0YA0
Switch ES
Switch ES Motor Starter 2004
for parameterizing, visualizing, diagnosing and testing the
ECOFAST motor starters via PROFIBUS-DP
with online help
German/English selectable
tested for execution under Windows 95/98/2000/NT system
System requirements:
PROFIBUS-DP interface: CP5411 (ISA), CP5412 (ISA), CP5511
(PCMCIA)
P5611 (PCI), Smart Cable for serial communication via a serial
interface and
Teleservice, CP5613 and CP5614 (new CP card) and MPI inter-
face on PG7xx
and its driver software (view interactive catalog CA01)
CD-ROM drive
STEP7 object manager
for integrating the ECOFAST starter as an S7 slave in
SIMATIC S7
for calling Switch ES from STEP7
System requirements:
SIMATIC: S7, M7, C7, PCS7
STEP7: Version 5.0 or higher
CD-ROM drive
3ZS1310-0CC20-0YA0
Upgrade Switch ES Motorstarter from Version 1.0 up to 2.0 3ZS1 310-0CC20-0YE0
Documentation
ECOFAST Manual (German)
ECOFAST Manual (English)
ECOFAST Motor Starters Manual (German/English)
ECOFAST Motor Starters High Feature Manual (German)
ECOFAST Motor Starters High Feature Manual (English)
3RK1703-0AB18-0AA1
3RK1703-0BB18-0AA1
3RK1702-2GB18-0AA0
3RK1702-3AB18-1AA0
3RK1702-3BB18-1AA0
Order Numbers
Tools, Connector Sets, Configuration
ECOFAST System Manual
9-10 GWA 4NEB 950 5228-02
9.13 Tools, Connector Sets, Configuration
Description Pieces per
Package
Order No.
Crimping tool
for contact pins and sockets 1.5 to 2.5 mm2
for contact pins and sockets 2.5 to 4.0 mm2
1
1
3RK1902-0AH00
3RK1902-0CT00
Disassembling tool for contact pins and sockets 1 3RK1902-0AJ00
Cover for power sockets Han Q8/0 1
10
3RK1902-0CK00
3RK1902-0CJ00
Connector set for power infeed Han Q8/0 2.5 mm2:
1 connector enclosure with PG 16,
1 socket insert and 9 contact sockets 2.5 mm2
1 3RK1902-0CA00
Connector set for power infeed Han Q8/0 4.0 mm2:
1 connector enclosure with PG 16,
1 socket insert and 9 contact sockets 4.0 mm2
1 3RK1902-0CB00
Connector set for looping through power Han Q8/0 2.5 mm2:
1 connector enclosure with PG 16,
1 pin insert and 9 contact pins 2.5 mm2
1 3RK1902-0CC00
Connector set for looping through power Han Q8/0 4.0 mm2:
1 connector enclosure with PG 16, 1
1 pin insert and 9 contact pins 4.0 mm2
1 3RK1902-0CD00
Mounting plate (for motor plugged in) 1 3RK1911-3AA00
Identification Plug 1 6ES7194-1KB00-
0XA0
PC cable with memory submodule 1 3RK1911-0BN20
Test connector set 1 3RK1911-2AM00
Cable end covers for AS-Interface shaped cable 1 3RK1901-1MN00
Addressing and diagnostic unit for AS-i 1 3RK1904-2AB01
ECOFAST System Manual
GWA 4NEB 950 5228-02 A-1
Questions and Answers A
A.1 Frequently Asked Questions
No. Question Answer
1 Is ECOFAST the
DESINA system from
Siemens?
No.
ECOFAST is based on interfaces standardized by DESINA.
ECOFAST goes beyond the DESINA specification, e.g. ECOFAST
also includes transmission technology for the AS-Interface. In addi-
tion, ECOFAST can optionally be supplied with special configuring
software.
2 Can components from
other manufacturers
also be integrated in
ECOFAST?
Yes.
ECOFAST is designed as an open system.
ECOFAST is based on open bus systems (Profibus-DP, AS-Inter-
face), and its interfaces (connections) are both standardized and
open (in accordance with DESINA). Any manufacturer offering
devices that comply with these specifications can thus easily be inte-
grated in an ECOFAST system.
3 Can connectors from
other manufacturers
be used as well?
Yes.
ECOFAST is an open system with standardized interfaces.
Siemens currently cooperates with Harting as a connector manufac-
turer and supplier regarding connection techniques. Other connectors
and cables from other manufacturers can, however, also be used at
any time, providing their design and their pin assignment can be
adapted to the specification (DESINA). Non-Siemens products can
also be integrated in ECOFAST ES.
4 Can SIMOCODE be
integrated?
Yes.
SIMOCODE must be installed in a local switchbox. It is integrated in
ECOFAST by means of the switch cabinet throughfeeds (hybrid field
bus connections).
If the maximum permissible current of the power bus (40 A) is excee-
ded, this feeder must be started separately on the power side.
5 Is ECOFAST suitable
for sub-zero tempera-
tures (outdoor applica-
tions, cold stores)?
No.
ECOFAST is designed for ambient temperatures between 0 and 60
degrees Celsius.
6 Can ECOFAST be
used in potentially
explosive areas?
No.
ECOFAST is not designed for use in potentially explosive areas.
7 How is the PLC inte-
grated in ECOFAST?
The power & control module can optionally be supplied with an inte-
grated PLC for ECOFAST. The S7 315-2 DP is planned in the first
stage. The PLC can, of course, also be accommodated in a conventi-
onal control cabinet. In this case it is integrated into the system by
means of control cabinet throughfeeds (hybrid field bus connections).
Questions and Answers
Frequently Asked Questions
ECOFAST System Manual
A-2 GWA 4NEB 950 5228-02
8 Are frequency conver-
ters available for ECO-
FAST?
Yes.
A frequency converter up to 1.5 kW is available for the ET 200X
which can also be operated as stand-alone. Furthermore, the
Combi 411 and R28S are also available.
9 If ECOFAST is based
on DESINA, how can it
be connected to a
SINUMERIK?
It is connected by means of the control cabinet throughfeeds (hybrid
field bus connections), i.e. the control cabinet can be factory-wired
(interface to SINUMERIK) and the peripheral devices (I/Os and star-
ter) are then connected externally.
10 If ECOFAST is based
on DESINA, does this
mean that it is only
designed for machine
tools?
No.
Machine tools are only one target industry. Since DESINA pursues
the same objective of cutting overall costs and already has standardi-
zed interfaces, we decided to use it as a basis for ECOFAST. ECO-
FAST is more versatile than DESINA, however, being designed for
use across industry boundaries. Conveyor systems and production
machines are among our other target markets.
11 What about the safety
technology interface
via bus systems (Profi-
safe, Safety at work)?
EMERGENCY STOP circuits can be connected to the power & cont-
rol module. The AS-I motor for Safety at Work can also be installed in
this module. Safety-oriented (two-channel) modules are required to
transmit safety-oriented signals via Profibus-DP. They will be integra-
ted depending on availability (e.g. in the ET 200X). We are unable to
provide a definite date at the present time. Compatible with Safety/
Profisafe.
12 Can components with
the IP20 degree of
protection (e.g. SIMO-
CODE or ET 200S)
also be integrated into
ECOFAST?
Yes.
These components can also be connected to ECOFAST. The switch-
box can be factory-wired with plug-in control cabinet throughfeeds
(hybrid field bus connections). The switchbox can be factory-wired on
the inside; the plug-in connections are located on the outside. Integra-
tion into the complete system is thus very straightforward.
13 How can the bus and
the power supplies
(24 V auxiliary volta-
ges) be combined in
the hybrid cable?
The bus (PROFIBUS-DP) and the 24 V power supplies are combined
by means of the hybrid field bus connections (control cabinet through-
feeds). These are available in several different versions (for copper,
fiber-optic, active and passive). In other words, no additional terminal
blocks are required in the control cabinet or the switchbox.
14 How can an OP be
integrated for visuali-
zation purposes?
OPs are normally designed with the IP20 degree of protection and
are therefore installed either in a control cabinet or in a local box.
They can be integrated in an ECOFAST system by means of the con-
trol cabinet throughfeeds (hybrid field bus connections).
15 How many feeders fit
into one segment?
Very easily.
The communication and power components are simply hooked onto
the PROFIBUS or the power bus. The communication components
must, of course, be configured with STEP7 or COM PROFIBUS (soft-
ware integration).
The power components can be integrated and tested with ECOFAST
ES. The wiring can be reoptimized, or the existing wiring tested and
documented, taking account of the newly connected consumer.
16 How can switching
devices with a higher
power than ECOFAST
starters (4 kW) be inte-
grated?
Switching devices of this kind can be integrated in local boxes as
IP20 components by means of the control cabinet throughfeeds (hyb-
rid field bus connections).
If the maximum permissible current of the “power bus” (40 A) is
exceeded, this feeder must be started separately on the power side.
No. Question Answer
ECOFAST System Manual
GWA 4NEB 950 5228-02 A-3
Questions and Answers
Frequently Asked Questions
17 Is a repair switch pro-
vided? Do the starters
have a repair switch?
There is a lockable repair switch on the power & control module, in
other words the connected segment is disconnected. The starters
themselves are not fitted with a repair switch. There is also a lockable
version for the connector on the motor.
The discriminating module can be used as a repair switch.
A maintenance switch will be available in Autumn 2004.
18 How can a system
built with ECOFAST be
extended?
Very easily.
The communication and power components are simply hooked onto
the PROFIBUS or the power bus. The communication components
must, of course, be configured with STEP7 or COM PROFIBUS (soft-
ware integration).
The power components can be integrated and tested with ECOFAST
ES. The wiring can be reoptimized, or the existing wiring tested and
documented, taking account of the newly connected consumer.
19 What is the maximum
power allowed for the
electronic starter (soft
starter)?
Soft starters in output classes of up to 1.1 kW and of up to 5.5 kW can
be supplied.
20 Is ECOFAST
UL-listed?
The individual components (devices) of ECOFAST are UL-listed. As
far as ECOFAST's UL listing as a complete system is concerned, we
are still negotiating with the responsible bodies, because the handling
of acceptances and certifications for complete systems varies consi-
derably from one system to another. Importance is attached, for
instance, to the definition of a self-contained unit (complete machine
or system?). The same applies to the cable laying types (the cables
do not necessarily have to be “piped” in self-contained units), for
example in concatenated units.
21 Is a metal version of
the connectors also
available?
Only molded-plastic versions of the bus and power connectors are
available at present. Metal versions of motor feeder connectors are
also available (for FUs, due to shielded motor line).
Metal versions of the plug cases can be requested from Harting.
22 What is the situation
regarding Ethernet
communication?
The ECOFAST communication philosophy is based on Profibus-DP
and AS-Interface. With regard to Ethernet, a considerable amount of
work still needs to be invested in industry-standard connection
methods.
The ECOFAST devices, such as ECOFAST starters, have a modular
internal set-up, so that additional bus interfaces can be implemented
easily as and when necessary (which is not the case with Ethernet).
23 Is it true that
ECOFAST starters
compete with the star-
ters of the ET 200X?
No.
Different ECOFAST solutions are offered intentionally to facilitate
maximum adaptability to each particular application.
The following solutions are possible:
Standalone starters (1 starter = 1 bus station) for branch drives
Isolated solutions (ET 200X) for drives that are physically close
together
Installation near the motor
Integration in the motor (starter on motor)
24 Is ECOFAST very
expensive?
Although the connector technique is slightly more expensive than
simple terminals, it is important to consider the overall costs of ECO-
FAST, namely both material and installation costs. The potential
savings concern the costs of installation and servicing.
No. Question Answer
Questions and Answers
Frequently Asked Questions
ECOFAST System Manual
A-4 GWA 4NEB 950 5228-02
ECOFAST System Manual
GWA 4NEB 950 5228-02 B-1
ECOFAST Pilot Projects B
B.1 Production Line for SIRIUS 2 - Siemens Cham
Production planning
Location: Siemens Cham
Application: Production line for SIRIUS 3RT contactors
Task: Conveyor system with 5 autonomous cells for screwing, testing, inscribing
and repairing
Set-up: Power & control module with S7-300 PLC, PROFIBUS-DP and AS-i.
Total of 21 motor starters for 0.18 and 0.3 kW motors
Objective: To replace central drive systems with distributed peripheral devices in an
installation system with diagnostics-capable motor starters and preassemb-
led connections.
Fig. B-1: SIRIUS 2 pilot system - production
Power & Control Modul
PROFIBUS-DP ECOFAST Hybrid Kabel
Energieleitung
Bandstrecke 2 Bandstrecke 3 Bandstrecke 4
Power & Control Module
PROFIBUS-DP ECOFAST Hybrid Cable
Power cable
Conveyor section 1 Conveyor section 2 Conveyor section 3 Conveyor section 4
ECOFAST System Manual
GWA 4NEB 950 5228-02 B-2
Configuration with ECOFAST ES
Fig. B-2: SIRIUS 2 pilot system - configuration with ECOFAST ES
ECOFAST System Manual
GWA 4NEB 950 5228-02 B-3
Production
Fig. B-3: SIRIUS 2 pilot system - production
ECOFAST System Manual
GWA 4NEB 950 5228-02 B-4
B.2 Configuration in the Automotive Industry - Production Plan-
ning
Production planning
Application: Production of wheel hubs
Task: Conveyor system with 4 cells
Set-up: Power & control module with S7-300 PLC, PROFIBUS-DP, AS-interface and
AS-interface monitor (Safety at Work)
Total of 6 motor starters for motors with 0.55 KW
Objective: To replace centrally controlled drive technology with a distributed installation
system.
To integrate pneumatics and EMERGENCY STOP functionality in a single
system technology.
ECOFAST System Manual
GWA 4NEB 950 5228-02 B-5
Configuration with ECOFAST ES
Fig. B-4: Configuration with ECOFAST ES
ECOFAST System Manual
GWA 4NEB 950 5228-02 B-6
ECOFAST System Manual
GWA 4NEB 950 5228-02 1
Glossary
3-phase AC current for
contactor
The 3-phase AC current for the contactor is the rated operational current for switch off during
the operation of the squirrel-cage motors.
Baud rate The baud rate is the rate of data transmission and indicates the number of bits transmitted
per second (baud rate = bit rate).
Baud rates of 9.6 kilobaud to 12 megabaud are possible with PROFIBUS-DP
Bus Common transmission path via which all stations are connected. It has two defined ends.
With PROFIBUS, the bus is a two-wire line (copper wire) or a fiber-optic cable.
Bus segment See Segment
Bus system The bus system comprises all the stations that are physically connected via a bus cable.
Current limit You can set an upper and/or a lower current limit.
Example:
“Substance for mixing too thick”, that is, the upper current limit has been exceeded.
“No-load operation because drive belt is torn”, that is, the lower current limit has been
undershot.
The current limits and the block protection are not activated in order to bypass start-up until
the class time has elapsed (e.g. after 10 seconds for class 10). If the current limits are viola-
ted, the motor starter responds with either a shutdown or warning.
Setting range for lower current limit:
20%..0.100% of the rated operational current.
Setting range for upper current limit:
50%...150% of the rated operational current.
Data tee connectors Data tee connectors connect the components of an automation system with PROFIBUS-DP.
Two data tee connectors are available in the ECOFAST system:
With copper cable (PROFIBUS-DP Cu)
With fiber-optic cable (PROFIBUS-DP fiber-optic cable)
DESINA Decentralized and standardized installation system for machine tools:
Developed by the Association of Machine Tool Manufacturers with the aim of defining a stan-
dard for the design and installation of machine tool components.
DMD Device master data (DMD) contains DP slave descriptions in a standardized format. The use
of DMD makes configuring the master and the DP slave easier.
DP master The DP master is a master that functions in accordance with EN 50 170, Volume 2, PROFI-
BUS, and uses the DP protocol.
DP slave The DP slave is a slave that is operated on the PROFIBUS bus with the PROFIBUS-DP pro-
tocol and functions in accordance with EN 50 170 standard, Volume 2, PROFIBUS.
DP standard The DP standard is the bus protocol of the ET 200 distributed I/O system based on the EN
50 170 standard, Volume 2, PROFIBUS.
ECOFAST Energy and Communication Field Installation System:
A system that decentralizes and modularizes installation to a large extent and permits exten-
sive diagnostics on the component level.
ECOFAST System Manual
2GWA 4NEB 950 5228-02
ECOFAST certified Confirms that devices from different manufacturers are compatible with ECOFAST specifica-
tions.
ECOFAST ES The ECOFAST ES configuration tool supports power-engineering system design.
ECOFAST integrated In addition to Siemens components, devices from other manufacturers can be integrated in
this configuration tool. Their integration and conformity is confirmed by the “ECOFAST inte-
grated” certificate.
Host A host is a system or unit that contains at least one DP Master. For example, the program-
mable controller with the CPU is the host, and the IM 308-C is the DP master.
Hybrid field bus
connector
The hybrid field bus connector is the physical connection between the station and the bus
cable.
IM 308-C The IM 308-C is a DP master for the ET 200 distributed I/O system. The IM 308-C can be
used together with COM PROFIBUS and plugged into the S5-115U, S5-135U and S5-155U
programmable controllers.
IrDA Infrared Data Association: standard for an infrared interface driver.
Load feeder A load feeder is a branch from the main circuit to the load with “Switching” and “Protection”
functions. The “Protection” function comprises:
Protection of the line from the load feeder to the load (line protection),
Protection of the load against overloading (load protection).
Master When they are in possession of the token, masters can send data to other stations and
request data from these stations (= active station).
Master interface Module for a distributed configuration. The distributed inputs and outputs are “connected” to
the programmable controller via the master interface C.
Master system All slaves that are assigned to a master with a reading and writing function form a master
system together with the master.
Master-slave method A bus access method whereby only one station at a time is the master and all other stations
are slaves.
Power bus Linear, primary power distribution bus.
Power tee clamp
connnector
Power tee clamp connectors connect ECOFAST components to the power bus. The power
bus is not interrupted when the ECOFAST component is unplugged.
Process image An “image” of the states of all inputs (= PII) or all outputs (= PIO) at a particular instant in
time. You can access the process image in the controller program.
PROFIBUS PROcess FIeld BUS, European process and fieldbus standard which is defined in the
PROFIBUS standard (EN 50 170, Volume 2, PROFIBUS). It specifies functional, electrical
and mechanical properties for a one-bit, serial fieldbus system.
PROFIBUS is a bus system which networks PROFIBUS-compatible automation systems and
field devices at the cell and field levels.
PROFIBUS is available with the following protocols: DP (= Distributed Input/Output), FMS (=
Fieldbus Message Specification), PA (Process Automation) and TF (= Technological Func-
tions).
PROFIBUS address Each station must be assigned a PROFIBUS address for the purpose of unique identifica-
tion. The PC/PU or the ET 200 hand-held unit have the PROFIBUS address “0”. The master
and slaves have a PROFIBUS address within the range from 1 to 125.
ECOFAST System Manual
GWA 4NEB 950 5228-02 3
PROFIBUS-DP PROFIBUS bus system with the DP protocol. DP stands for distributed I/O system.
The primary task of PROFIBUS-DP is fast cyclical exchange of data between the central DP
Master and the peripheral devices.
Segment The bus line between two terminating resistors forms a segment. A segment contains 0 to 32
stations. Segments can be coupled via RS 485 repeaters.
Slave A slave can only exchange data with a master after being requested to do so by the master.
Slaves include, for example, all DP slaves, such as motor starters, frequency converters, etc.
Station A station is a device that can send, receive, or amplify data via the bus (e.g. a master, a
slave, an RS 485 repeater, or an active star coupler).
Station number See PROFIBUS address.
Terminating resistor Each bus line connecting the individual motor starters to each other must be terminated with
a resistor at the beginning and end. This prevents line reflections.
ECOFAST System Manual
4GWA 4NEB 950 5228-02
ECOFAST System Manual
GWA 4NEB 950 5228-02
ECOFAST System Manual
Have you found any typographical errors while reading this manual?
Please use this form to tell us about them.
We would also welcome any ideas and suggestions you may have.
To: Sender (please fill out)
SIEMENS AG Name
A&D CD MM3
P.O. Box 1954 Company/Department
92220 Amberg Address
Fax: **49-9621-80-3337 Telephone
ECOFAST System Manual
GWA 4NEB 950 5228-02
Siemens Aktiengesellschaft
Automation and Drives
Low Voltage Controls and Distribution
Postfach 48 48
D-90327 rnberg
w w w . s i e m e n s . d e / e c o f a s t Order No. 3RK1703-0BB18-0AA1