CTM 1X2-110AC Order No.: 2838539
http://eshop.phoenixcontact.de/phoenix/treeViewClick.do?UID=2838539
PHOENIX CONTACT Deutschland GmbH Page 3 / 7
http://www.phoenixcontact.de Feb 2, 2011
Nominal discharge surge current In (8/20) µs
(Core-Core)
5 kA
Nominal discharge surge current In (8/20) µs
(Core-Earth)
5 kA
Total surge current (8/20) µs 10 kA
Max. discharge surge current Imax (8/20) µs
maximum (Core-Earth)
10 kA (in total)
Nominal pulse current Ian (10/1000) µs (Core-
Core)
100 A
Nominal pulse current Ian (10/1000) µs (Core-
Earth)
100 A
Lightning test current (10/350) µs, peak value limp 1 kA
Output voltage limitation at 1 kV/µs (Core-Core)
spike
≤ 260 V
Output voltage limitation at 1 kV/µs (Core-Earth)
spike
≤ 800 V
Output voltage limitation at 1 kV/µs (Core-Core)
static
≤ 260 V
Output voltage limitation at 1 kV/µs (Core-Earth)
static
≤ 800 V
Residual voltage at In, (conductor-conductor) ≤ 10 V
Residual voltage at In, (conductor-ground) ≤ 55 V
Residual voltage with Ian (10/1000)µs (conductor-
conductor)
≤ 10 V
Residual voltage with Ian (10/1000)µs (conductor-
ground)
≤ 12 V
Protection level UP (Core-Core) ≤ 260 V (C2, 10 kV/5 kA, spike)
≤ 10 V (C2, 10 kV/5 kA, static)
≤ 260 V (C3, 7.5 kV/100 A, spike)
≤ 10 V (C3, 7.5 kV/100 A, static)
Protection level UP (Core-Earth) ≤ 800 V (C2, 10 kV/5 kA, spike)
≤ 60 V (C2, 10 kV/5 kA, static)
≤ 800 V (C3, 7.5 kV/100 A, spike)
≤ 12 V (C3, 7.5 kV/100 A, static)
Response time tA (Core-Core) ≤ 1 ns
Response time tA (Core-Earth) ≤ 100 ns
Input attenuation aE, sym. 0.3 dB (≤ 1.8 MHz)
Cut-off frequency fg (3 dB), sym. in 100 Ohm
system
20 MHz
Capacity (Core-Core) 100 pF (f=1 MHz / VR= 0 V)