https://www.phoenixcontact.com/us/products/2904901
05/18/2015Page2/5
Temperature measuring transducer-MACX PL-T-UIREL-UP-2904901
Technical data
Ambient conditions
Noise immunity EN 61000-6-2 When being exposed to interference, there may be minimal
deviations.
Input data
Sensor types (RTD) that can be used Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC) B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range -200 °C ... 850 °C
Input signal range 0 Ω ... 50 kΩ
Potentiometer resistance range 0 Ω ... 50 kΩ
Input signal range -1000 mV ... 1000 mV
Output data
Current output signal 4 mA ... 20 mA
Max. current output signal 22 mA
Load/output load current output ≤ 600 Ω (at 20 mA)
Behavior in the event of a sensor error according to NE 43 or freely configurable
Output name Relay output
Output description 1 SIL/PL
Contact type 2 PDT
Contact material AgSnO2, hard gold-plated
Maximum switching voltage 250 V AC (250 V DC)
Maximum inrush current 2 A (250 V AC)
2 A (28 V DC)
0.2 A (120 V DC)
Power supply
Supply voltage range 24 V ... 230 V AC/DC (-20 %/+10 %, 50/60 Hz)
Power consumption < 2.4 W
Connection data
Conductor cross section solid min. 0.2 mm²
Conductor cross section solid max. 2.5 mm²
Conductor cross section flexible min. 0.2 mm²
Conductor cross section flexible max. 2.5 mm²
Conductor cross section AWG min. 24
Conductor cross section AWG max. 14
Screw thread M3
Connection method Screw connection
General