1
Inductive sensor NJ5-18GM-N-V1
Release date: 2015-04-25 23:23 Date of issue: 2015-04-26 106453_eng.xml
Germany: +49 621 776 4411Pepperl+Fuchs Group
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
USA: +1 330 486 0001 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com
0102
Model Number
NJ5-18GM-N-V1
Features
•5 mm flush
Usable up to SIL2 acc. to IEC 61508
Accessories
V1-G
Female connector, M12, 4-pin, field attachable
V1-W
Female connector, M12, 4-pin, field attachable
V1-G-N-2M-PUR
Female cordset, M12, 2-pin, NAMUR, PUR cable
V1-W-N-2M-PUR
Female cordset, M12, 2-pin, NAMUR, PUR cable
BF 18
Mounting flange, 18 mm
EXG-18
Quick mounting bracket with dead stop
Technical Data
General specifications
Switching element function NAMUR, NC
Rated operating distance sn5 mm
Installation flush
Output polarity NAMUR
Assured operating distance sa0 ... 4.05 mm
Reduction factor rAl 0.21
Reduction factor rCu 0.18
Reduction factor r304 0.63
Nominal ratings
Nominal voltage Uo8.2 V (Ri approx. 1 k)
Operating voltage UB5 ... 25 V
Switching frequency f 0 ... 500 Hz
Hysteresis H 3 %
Current consumption
Measuring plate not detected 3 mA
Measuring plate detected 1 mA
Ambient conditions
Ambient temperature -25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection type Connector M12 x 1 , 4-pin
Housing material Stainless steel 1.4305 / AISI 303
Sensing face PBT
Degree of protection IP67
General information
Use in the hazardous area see instruction manuals
Category 1G; 2G
Compliance with standards and directives
Standard conformity
NAMUR EN 60947-5-6:2000
IEC 60947-5-6:1999
Standards EN 60947-5-2:2007
IEC 60947-5-2:2007
Approvals and certificates
FM approval
Control drawing 116-0165F
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated 36 V
Dimensions
Electrical Connection
50
4
40
M12x1
M18x1
24
1L+
L-
2
Germany: +49 621 776 4411Pepperl+Fuchs Group
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
USA: +1 330 486 0001 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com
Inductive sensor NJ5-18GM-N-V1
2
Release date: 2015-04-25 23:23 Date of issue: 2015-04-26 106453_eng.xml
Pinout
1
3
4
2
1 BN
2 BU
Wire colors in accordance with EN 60947-5-6
(brown)
(blue)
Germany: +49 621 776 4411Pepperl+Fuchs Group
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
USA: +1 330 486 0001 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com
Inductive sensor NJ5-18GM-N-V1
3
Release date: 2015-04-25 23:23 Date of issue: 2015-04-26 106453_eng.xml
ATEX 1G
Instruction Manual electrical apparatus for hazardous areas
Device category 1G
for use in hazardous areas with gas, vapour and mist
EC-Type Examination Certificate PTB 00 ATEX 2048 X
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga
Directive conformity 94/9/EG
Standards EN 60079-0:2012, EN 60079-11:2012, EN 60079-26:2007
Ignition protection "Intrinsic safety"
Use is restricted to the following stated conditions
Appropriate type NJ 5-18GM-N...
Effective internal capacitance Ci 70 nF ; a cable length of 10 m is considered.
Effective internal inductance Li 50 µH ; a cable length of 10 m is considered.
Ge n e r a l The apparatus has to be operated according to the appropriate data in the data sheet
and in this instruction manual.
The EC-Type Examination Certificate has to be observed. The special conditions
must be adhered to!
Directive 94/9/EG and hence also EC-Type Examination Certificates apply in general
only to the use of electrical apparatus under atmospheric conditions.
The use in ambient temperatures of > 60 °C was tested with regard to hot surfaces
by the mentioned certification authority.
If the equipment is not used under atmospheric conditions, a reduction of the permis-
sible minimum ignition energies may have to be taken into consideration.
Ambient temperature The temperature ranges, according to temperature class, are given in the EC-Type
Examination Certificate. Note: Use the temperature table for category 1 !!! The 20 %
reduction in accordance with EN 1127-1:2007 has already been accounted for in the
temperature table for category 1.
Installation, commissioning Laws and/or regulations and standards governing the use or intended usage goal
must be observed. The intrinsic safety is only assured in connection with an appro-
priate related apparatus and according to the proof of intrinsic safety. The associated
apparatus must satisfy the requirements of category "ia" and have electrical isolation
between the power supply and signal circuits.
The sensor must be protected from strong electromagnetic fields.
Maintenance No changes can be made to apparatus, which are operated in hazardous areas.
Repairs to these apparatus are not possible.
Special conditions
Protection from mechanical danger When used in the temperature range below -20 °C the sensor should be protected
from knocks by the provision of an additional housing.
Electrostatic charge Electrostatic charges must be avoided on the mechanical housing components.
Dangerous electrostatic charges on the mechanical housing components can be
avoided by incorporating these in the equipotential bonding.
Germany: +49 621 776 4411Pepperl+Fuchs Group
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
USA: +1 330 486 0001 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com
Inductive sensor NJ5-18GM-N-V1
4
Release date: 2015-04-25 23:23 Date of issue: 2015-04-26 106453_eng.xml
ATEX 2G
Instruction Manual electrical apparatus for hazardous areas
Device category 2G for use in hazardous areas with gas, vapour and mist
EC-Type Examination Certificate PTB 00 ATEX 2048 X
CE marking 0102
ATEX marking ¬ II 1G Ex ia IIC T6T1 Ga
Directive conformity 94/9/EG
Standards EN 60079-0:2012, EN 60079-11:2012
Ignition protection "Intrinsic safety"
Use is restricted to the following stated conditions
Appropriate type NJ 5-18GM-N...
Effective internal capacitance Ci 70 nF ; a cable length of 10 m is considered.
Effective internal inductance Li 50 µH ; a cable length of 10 m is considered.
Ge n e r a l The apparatus has to be operated according to the appropriate data in the data sheet
and in this instruction manual. The EC-Type Examination Certificate has to be
observed. The special conditions must be adhered to!
Directive 94/9/EG and hence also EC-Type Examination Certificates apply in general
only to the use of electrical apparatus under atmospheric conditions.
The use in ambient temperatures of > 60 °C was tested with regard to hot surfaces
by the mentioned certification authority.
If the equipment is not used under atmospheric conditions, a reduction of the permis-
sible minimum ignition energies may have to be taken into consideration.
Ambient temperature The temperature ranges, according to temperature class, are given in the EC-Type
Examination Certificate.
Installation, commissioning Laws and/or regulations and standards governing the use or intended usage goal
must be observed. The intrinsic safety is only assured in connection with an appro-
priate related apparatus and according to the proof of intrinsic safety. The sensor
must be protected from strong electromagnetic fields.
Maintenance No changes can be made to apparatus, which are operated in hazardous areas.
Repairs to these apparatus are not possible.
Special conditions
Protection from mechanical danger When used in the temperature range below -20 °C the sensor should be protected
from knocks by the provision of an additional housing.
Electrostatic charge Electrostatic charges must be avoided on the mechanical housing components.
Dangerous electrostatic charges on the mechanical housing components can be
avoided by incorporating these in the equipotential bonding.