Model 18TBP/TB
•Description:Variable-Voltage
Power Control
•Product Range:120-240 VAC,
5-25 amps.
•Application:Resistance Loads
FEATURES
•All Solid-State Construction
•Short Circuit Protection
•Integral Heatsink Chassis
•No Thermal Derating
TYPICAL APPLICATIONS
•Replace Variable Transformers
•Electric Heater Control
•Light Dimming
•Hot-Wire Cutting
•Heat Sealing and Packaging
•Plastic Molding and Extruding
•Food Preparation Equipment
Model 18TBP/TB controls provide infi-
nitely variable control of single-phase
a.c. voltage to resistive heating ele-
ments. These controls are solid-state
replacementsforvariabletransformers,
mercury relays, saturable core reac-
tors,andelectromechanicalcontactors.
Power Triacs replace contacts and
brushes to control electric power with-
out moving parts, and, when operated
within their stated ratings for current,
voltage, and temperature, have no
knownMTBForlifeexpectancyrating.
PANEL- OR CHASSIS-MOUNT
Model 18TBP controls are compact,
lightweight packages that employ
single hole mounting to panels and
enclosure doors. Model 18TB con-
trols are designed for rear or rack
mounting.Both utilizean electrically
isolated heatsink chassis.
EXCLUSIVE ADVANCED
TECHNOLOGY:
Three Pillars Of Protection
Model 18TBP/TB controls incorpo-
rate exclusive design features to
protect power semiconductor com-
ponents against damage. “2 milli-
second” fuses protect against
short-circuit damage; an R-C snub-
ber network protects against dv/dt
failure; an integral heatsink chassis
allows continuous operation in
ambients to 50oC with no derating.
SPECIFICATIONS
Power Circuit:power Triac with par-
allel R-C circuit for dv/dt protection
and current-clamping 2 millisecond
fuse for short-circuit protection.
Control Circuit:R-C network with
variable-resistance potentiometer
adjusts firing capacitor into bilateral
diodeconnectedtopowerTriacgate
for stable, full-range control.
Mains Frequency:50/60 Hz.
Output Voltage:0-95% of input.
Overall Efficiency:99%.
Power Loss: approximately 1.5
watts/amp.
Voltage Drop Across Power Circuit
at 100% Output: 1-2 volts maxi-
mum/phase.
Control Input:manual control via
variable potentiometer.
Control Power:1 watt.
Fuse Protection:2 millisecond I2t
fuses are factory tested and coordi-
nated with all power semiconduc-
tors, considering:
a. fuse element melt time tmelt;
b. peak melt current Imelt;
c. arc quench time tarc;
d. peak arc current Iarc.
AmbientTemperatureRange:-10to
+50oC.
Terminal Connections:Bakelite or
thermoplastic blocks.
SIZING CONSIDERATIONS
Model 18TBP/TB controls are rated
for use with constant resistance
loads. Size units by actual load cur-
rent, not kW.
1> Always use maximum possible
load current for sizing purposes.
2> The amp rating is determined by
the fuse. Current draw must not ex-
ceed the fuse rating at any time.
3> Rated voltage of connected load
shouldmatchcontrolinputvoltage.
SIZING EXAMPLE
Application:single-phase, 800 watt
nichrome heating element; input
voltage 120 VAC, 60 Hz.
Model Number Selection:
a.Triac-basedvariable-voltage:SC
b. Panel-mount: E
c. 120 VAC input: 12
d.Amprating,calculatedasfollows:
800 = 6.66 amps
120
Since 6.66<10, amp rating: -10
Model Number:SCE12-10.
WHEN ORDERING, SPECIFY:
•Model Number
•Input Voltage
•Load Specifications
PERFORMANCE NOTE: Triac
power circuits may “slave” when
multiple units are used on 240 VAC
lines derived from three phase
mains. For optimum performance,
use on single phase, 240 VAC de-
rived from 3-wire, 120/240 VAC
mains.
Model 18TBP/TB
SCR Power Controls
Rt. 29 Scott Depot WV 25560-0070 APPLICATION ASSISTANCE - 304/757-7354