TIME CUBE
84 B1201 www.turck.us • 1-800-544-7769 Fax: (763) 553-0708 TURCK Inc. Minneapolis, MN 55441
The modules CT 2 and CT 3 are electronic
timers that are designed to be inserted
beween a standard plug-in relay and its
socket, enabling the relay to be operated
as a timer relay.
The CT modules are able to accept any
standard 8 or 11-Pin RELECO series C2
or C3 as well as those from any other
supplier.
The relay coil voltage must be in the range
shown for each model.
8 and 11-Pin, Time Cube
CT 2A CT 3A
Off delay
The timing starts when S is switched off.
The relay drops out at time (t).
R
S
S
+
~
R
S
2
10
(7)
t
Function A
CT 2B CT 3B
Blinker
The relay blinks ON/OFF at time (t) when
switch S is closed. First pulse, ON.
(7)
10 S
R
~+
S
R
t t t
Function B
CT 2E CT 3E
On delay
The timing starts when the switch S is
closed. The relay pulls in at the time (t).
R
S
+
~
R
S
2
10
(7) t
Function E
CT 2-A30/S* .......9.5-18 V
CT 2-A30/L .......... 20-65 V
CT 2-A30/M .......90-150 V
CT 2-A30/U .....180-265 V
CT 3-A30/S* .......9.5-18 V
CT 3-A30/L .......... 20-65 V
CT 3-A30/M .......90-150 V
CT 3-A30/U .....180-265 V
CT 2-B30/S* ........9.5-18 V
CT 2-B30/L ........... 20-65 V
CT 2-B30/H ........90-265 V
CT 3-B30/S* ........9.5-18 V
CT 3-B30/L ........... 20-65 V
CT 3-B30/H ........90-265 V
CT 2-E30/S* ........9.5-18 V
CT 2-E30/L ...........20-65 V
CT 2-E30/H ........90-265 V
CT 3-E30/S* ........9.5-18 V
CT 3-E30/L ...........20-65 V
CT 3-E30/H ........90-265 V
CT2... (8-Pin) and CT3... (11-Pin) types with time range from 0.2 seconds to 30 minutes (range 30)
*All types are for AC/DC except “S” voltage range (only DC)
Specifications
Time accuracy
Repetition +0.5%/20 ms
Supply voltage 1 ms / volt.
Ambient temperature -0.25% / K
Reset time (types E, W, B) <150 ms
Reset time (types A, K) <200 ms
Triggering time: AC, 80 ms; DC, 50 ms
Ambient temperature -10°C to +60°C
Transient protection IEC 255.4
Housing material Noryl SE1 (UL94 V-1)
Protection class (DIN 40050) IP 40
Weight avg. 35 g
35
50
12.5 24.5
10
9
8
7
6
1
2
3
4
5
1
9
3
2
1
8
7
6
5
4
10
1
Time Range Setting Dimensions
0.2-3 s
2-30 s
0.2-3 min
2-30 min
Range 30 Dip - Sw