Description
The Ultra SlimPak G108 is a DIN rail mount, DC voltage or current
input limit alarm with dual setpoints and two contact closure
outputs. The field configurable input and alarm functions offer
flexible setpoint capability. Input voltage spans from 10mV to
200V and input current spans from 1mA to 100mA can be field
configured. Bipolar inputs are also accepted.
The G108 is configurable as a single or dual setpoint alarm, with
HI or LO trips and failsafe or non-failsafe operation. Also included
are adjustable deadbands (0.25 to 5% of full scale input) for each
setpoint, a 24VDC voltage source (isolated from line power) for
transducer excitation, and a flexible DC power supply which
accepts any voltage between 9 and 30VDC.
Diagnostic LEDS
The G108 is equipped with three front panel LEDs. The dual
function green LED is labeled INPUT and indicates line power and
input signal status. Active DC power is indicated by an illuminated
LED. If this LED is off, check DC power and the wiring connection.
If the input signal is more than 110% of the full scale range, the LED
will flash at 8 Hz. Below 0%, it flashes at 4 Hz. Two red LEDs indicate
the relay state for each setpoint. An illuminated red LED indicates
the tripped condition.
Output
The G108 is equipped with two SPDT (form C) relays, rated at
120VAC or 28VDC at 5 Amperes. Each of these relays is indepen-
dently controlled by the field configurable setpoint and deadband.
Operation
The field configurable G108 limit alarm setpoints can be config-
ured for HI or LO, failsafe or non-failsafe operation. Each of the
setpoints has a respective HI or LO deadband. In a tripped
condition, the setpoint is exceeded and the appropriate red LED
will illuminate. The trip will reset only when the process falls below
the HI deadband or rises above the low deadband (see Figure 1).
For proper deadband operation, the HI setpoint must always be
set above the LO setpoint. In failsafe operation, the relay is
energized when the process is below the HI setpoint or above the
LO setpoint (opposite for non-failsafe). In the failsafe mode, a
power failure results in an alarm state output.
ULTRA SLIMPAK®
G108-0001
DC Powered DC Input Limit Alarm
Provides Relay Contact Closures
at a Preset DC Input Level
Programmable HI or LO, Failsafe or Non-failsafe
Field Configurable Input Ranges
24VDC Transducer Excitation
LED Trip and Input Indicators
G108-0001
Flexible Power Supply Accepts 9 to 30 VDC
ASIC Technology for Enhanced Reliability
RoHS Compliant
Dynamic Deadband
Circuitry in the G108 prevents false trips by repeatedly sampling
the input. The input must remain beyond the setpoint for 100
milliseconds, uninterrupted, to qualify as a valid trip condition.
Likewise, the input must fall outside the deadband and remain
there for 100 milliseconds to return the alarm to an untripped
condition. This results in a “dynamic deadband” (based on time)
in addition to the normal deadband.
Configuration
Unless otherwise specified, the factory presets the Model G108 as
follows:
Input: Current
Range: 0-20mA
Output: Dual, SPDT
Trip: A:HI, B:LO
Failsafe: No
Deadband: A, B: 0.25%
The DC power input accepts any DC source between 9 and 30V.
Typically a 12V or 24VDC source is used (see Accessories).
For other I/O ranges, refer to Table 1. Reconfigure switch SW1 for
the desired input type, range and function.
1. With DC power off, set position 9 and 10 of SW1 for current or
voltage (see Figure 4).
2. Set position 1 through position 4 of input range switch “SW1”
for the desired input range (see Table 1).
3. Set position 5 of input range switch “SW1” to ON for unipolar
(e.g. zero based, 0-20mA) range or OFF for bipolar (e.g. -100%
offset, -20 to 20mA) range.
4. Set position 6 and 7 of input range switch “SW1” to ON for a HI
trip setpoint or OFF for a LO trip setpoint.
5. Set position 8 of input range switch “SW1” to ON for non-failsafe
operation or OFF for failsafe operation (e.g. alarm trips upon
power failure).