Specifications are subject to change without notice (27.02.00) 1
Plug Output Time range Supply:
24 to 230 VAC/DC
Circular SPDT 0.1 s - 10 m S 105 156 924
Circular DPDT 0.1 s - 10 m S 105 166 924
Timers
Time ranges: 0.1 s to 10 m
Easy-to-use (true) delay on release time function
Easy time setting
Knob-adjustable time setting
Automatic start after drop-out of power supply
Repeatability: 0.2%
Output: 5 A SPDT or DPDT relay
Plug-in module, S-housing
LED-indication for power supply ON
24 to 230 VAC/DC power supply
Cadminum-free contacts
Timer in accordance with IEC 61812-1
Product Description
Mono-function, multi-voltage
(true) delay on release timer
with 4 selectable time ranges
from 0.1 s up to 10 m for
standard 11-pin circular sock-
ets. Often used in applica-
tions where a cooling fan has
to remain turned on for at cer-
tain period of time after a
motor has been turned off.
Ordering Key
Housing
Type/function
Output
Power supply
Type Selection
Time Specifications
Time ranges
Selectable by DIP-switch 0.1 - 1 s
1 - 10 s
0.1 - 1 m
1 - 10 m
Setting accuracy < ±10%
Repeatability 0.2%
Time variation
Within rated power supply 0.05%/V
and ambient temperature 0.2%/°C
Minimum control pulse Power supply applied for
min. 200 ms
Output Specifications
Output S 105 156 924 SPDT relay
S 105 166 924 DPDT relay
Rated insulation voltage
250 VAC (rms) (cont./elect.)
Contact ratings (AgNi) µ (micro gap)
(IEC 60947-5-1/IEC 60337)
Resistive loads
AC 1
5 A/250 VAC
DC 1
5 A/24 VDC
Small inductive loads
AC 15
2 A/250 VAC
DC 13
3 A/24 VDC
Mechanical life 2 x 106operations
Electrical life AC 1 105operations
(at max. load)
Operating frequency 3600 operations/h
Insulation voltage
Rated insulation voltage 2.0 kVAC (rms) (cont./elect.)
Rated impulse withstand volt. 4 kV (1.2/50 µs) (cont./elect.)
(IEC 60664)
Delay on Release
Type S 105
S 105 166 924
Supply Specifications
Power supply
Overvoltage cat. III (IEC 60664)
Rated operational voltage
through pins 2 & 10 24 to 230 VAC/DC ±15%
45 to 65 Hz
(pin 2 positive)
Voltage interruption 40 ms
Rated insulation voltage None
Rated impulse withstand volt. 4 kV (1.2/50 µs)
Rated operational current
AC supply 9 mA @ 230 VAC
5 mA @ 115 VAC
3 mA @ 24 VAC
DC supply 1.5 mA @ 24 VDC
Inrush current 0.5 AAC for < 100 ms
2Specifications are subject to change without notice (27.02.00)
Relay ON
Power supply
S 105
Mode of Operation
When power supply is applied
the relay operates.
When power supply is inter-
rupted, the time period starts
and at the end of the set time
period, the relay releases.
If power supply is reapplied
before the relay releases, the
time is reset and the relay
remains on.
Note:
The S 105 should not be oper-
ated by pulses shorter than
200 ms.
For this purpose the relay
S 103, operated by means of
an external contact function,
should be used.
Wiring Diagrams
Accessories
SocketS 411
Hold down springHF
Mounting rack SM 13
Socket cover BB 4
General Specifications
Power ON delay 200 ms
Power OFF delay 100 ms
Indication for
Power supply ON LED, green
Environment
Degree of protection IP 20
Pollution degree 2 (IEC 60664)
Operating temperature -20° to +50°C (-4° to +122°F)
Storage temperature -50° to +85°C (-58° to +185°F)
Weight 125 g
Approvals UL, CSA
CE-marking Yes
EMC Electromagnetic
Compatibility
Immunity Acc. to EN 50082-2
Emission Acc. to EN 50081-1
Timer specifications Acc. to IEC 61812-1 Time Setting
DIP-switch selector
x 1
sec.
min.
hrs.
x 0.1
Shown example:
min. x 0.1
ON OFF
S 105 156 924 S 105 166 924