Dimensions
MAIN CHARACTERISTICS
Size
36x400
Current
rating
IN( A )
0.8
1
1.5
2
3.15
4
5
6
8
10
12
16
20
Catalog Number
CC 4000 CP gRC 36x400/0.8
CC 4000 CP gRC 36x400/1
CC 4000 CP gRC 36x400/1.5
CC 4000 CP gRC 36x400/2
CC 4000 CP gRC 36x400/3.15
CC 4000 CP gRC 36x400/4
CC 4000 CP gRC 36x400/5
CC 4000 CP gRC 36x400/6
CC 4000 CP gRC 36x400/8
CC 4000 CP gRC 36x400/10
CC 4000 CP gRC 36x400/12
CC 4000 CP gRC 36x400/16
CC 4000 CP gRC 36x400/20
Interrupting rating
@ 4000 V DC
30 kA
L/R = 20 ms
Ref Number
Z 220293
R 221137
S 221138
Z 089423
T 221139
A 089424
Y 098461
E 099847
V 221140
G 098469
C 098396
Z 083052
F 099848
Pack.
3
pieces
Watts loss
0.8 ININ
1.5
1.6
2.4
3.0
3.9
6.0
9.6
11
12
13
15
15
18.6
2.5
2.7
4.1
5.0
6.4
10
16
19
22
23
26
27
33
400
Weight: 785 g
ø 36
4000 V DC
gRC from 0.8 to 20 A
Size 36 x 400
Semiconductor Fuses
DC Fuses
Ferrule Fuses 4000V DC
385
See Fuse Blocks and Fuse Holders, and Medium Voltage fuse clips
386
Semiconductor Fuses
DC Fuses
Ferrule Fuses 4000V DC
Time vs. current characteristics
t (s)
L/R (ms)
I (A)
I (A)
U (V)
DC application data
1 10 10 2 10 310 10 2 10 3 10 4
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
90
80
70
60
50
40
30
20
10
0
10 4
10 3
10 2
10
1
10 -1
10 -2
10 -3
10 -4
10 4
10 3
10 2
10
1
10 -1
10 -2
10 -3
10 -4
0.8 1
1.5 2
3.154
5
Above: Curve indicates maximum permissible
value of time constant L/R as a function of DC
working voltage
1 : L/R = 45 ms
2 : L/R = 15 ms
Max. AC voltage (50/60 Hz): 4,000 V with interrupting
rating of 50 kA
Um(V)
U (V)
Peak arc voltage
vs. working voltage
0
1000
2000
3000
4000
6000
4000
2000
0
1
2
ELECTRICAL CHARACTERISTICS
68
10 12
16
20
Above: Curves indicate for various time constants L/R
the peak arc voltage, which may appear across fuse
terminals, vs. DC working voltage
a= 130
A2=0.6
B1= 1.25
B2= 0.6
Cf3= 0.8
a= 130
A2=0.6
B1= 1.25
B2= 0.6
Cf3= 0.8
± 10% tolerance for mean
pre-arcing current
Above, left and right: Curves indicate, for each rated current,
pre-arcing time vs. R.M.S. pre-arcing current