https://www.phoenixcontact.com/us/products/2856317
10/21/2014Page2/5
Lightning arrester type 1-FLT 35/3+1 CTRL-0.9/I-2856317
Technical data
General
IEC 61643-1
Mounting type DIN rail: 35 mm
Type Rail-mountable module, one-piece
Surge protection fault message Optical
Direction of action 3L-N & N-PE
Protective circuit
IEC test classification I
T1
EN type T1
Nominal voltage UN230 V AC (230/400 V AC ... 240/415 V AC)
400 V AC
Maximum continuous operating voltage UC260 V
Maximum continuous operating voltage UC (L-N) 260 V AC
Maximum continuous operating voltage UC (N-PE) 260 V AC
Nominal frequency fN50 Hz
60 Hz
Residual current IPE ≤ 20 µA
Operating effective current IC at UN≤ 7.5 mA (3x L-N)
Nominal discharge current In (8/20) µs (L-N) 100 kA
Nominal discharge current In (8/20) µs (L-PE) 50 kA
Nominal discharge current In (8/20) µs (N-PE) 50 kA
Impulse discharge current (10/350)µs charge 25 As
Impulse discharge current (10/350)˽µs, specific energy 625 kJ/Ω
Impulse discharge current (10/350)˽µs, peak value limp 50 kA
Voltage protection level Up (L-N) ≤ 0.9 kV
Voltage protection level Up (N-PE) ≤ 1.5 kV
Response time (L-N) ≤ 100 ns
Response time (N-PE) ≤ 100 ns
Max. backup fuse with branch wiring 125 A (gL)
Short-circuit resistance IP with max. backup fuse (effective) 25 kA
Short-circuit current self-quenching 3 kA (260 V / L-N)
500 A (260 V / N-PE)
Follow current quenching capacity If (L-N) 3 kA
Follow current quenching capacity If (N-PE) 500 A
Connection, protective circuit
Connection method Screw connection