Semiconductor fuses
Semiconductor (AC) fuses
SCAC166
Other Protistor®Fuses
Ferrule Fuses
10x38 gRB - 690VAC
12/04
690V AC
gRB - from 1 up to 30 A
Size: 10x38
The fuse preselection table below indicates:
- rated current (or rating) IN
- pre-arcing I2t (I2tp) at 1 ms
- total operating I2t (I2tt) at 690V, cos ϕ=0.15, and for a total operating time from 8 to 10 ms
- dissipated power PNat the rated current IN, and at 0.8 IN, in steady state
- Nominal breaking capacity, checked by tests made in accordance with IEC standard.
at In
(W)
at 0.8 In
(W)
Voltage
Rating Rated current Pre-arcing I2t Total I2t at 660VAC Dissipated power Peak arc voltage Breaking capacity
(VAC) In (A) I2tp (A2s) I2tt (A2s) (V) I (kA)
1 0,075 0,28 0,9 0,52
1,25 0,115 0,36 1,25 0,7
1,5 0,185 0,57 1,5 0,81
2 0,42 1,3 2 1,1 2500
2,5 0,88 2,7 2,1 1,15
3 1,55 4,6 2,3 1,25
4 4 12 2,6 1,35 160 kA
690 5 8,6 25 2,7 1,4 690 V
6 15 44 2,9 1,5 (IEC)
8 3,3 33 2,4 1,35
10 5,4 55 3,4 1,85
12,5 8,5 82 3,4 1,9 1450
16 16 145 4,1 2,3
20 230 250 4,3 2,4
25 58 470 4,7 2,7
30 (32*) 96 740 5 2,9
* Non approval rating
SCAC167
Semiconductor fuses
Semiconductor (AC) fuses
Other Protistor®Fuses
French Ferrule
10x38 gRB - 690VAC
12/04
Maximum values of total operating I2t and total operating times
Arc voltage
Multiplier coefficient
- 32- 32
Semiconductor fuses
Semiconductor (AC) fuses
SCAC168
Other Protistor®Fuses
Ferrule Fuses
10x38 gRB - 690VAC
12/04
Time-current characteristics (1 to 6 A)
Cut-off characteristics
Time-current characteristics (8 to 30 A)
Cut-off characteristics
-32
SCAC169
Semiconductor fuses
Semiconductor (AC) fuses
Other Protistor®Fuses
Ferrule Fuses
10x38 gRB - 690VAC
12/04
DC working voltage possibilities
Dimensions / Reference / Ref. No.
Without trip-indicator
Max. weight 10g
Packaging: per 10 pieces
Above: Curve indicating the maximum time constant
L/R of the fault path as a function of the DC voltage U,
for the rated currents from 1 to 30 A of this range.
Time-current characteristics: Curves indicate, for each
rated current, pre-arcing time as a function of RMS
value of pre-arcing current I.
Tolerances on this current:
±10% = ratings from 1 to 6 A
±9% = ratings from 8 to 30 A
Fuses with “gR” characteristics can eliminate all overloads.
They do not show any minimum breaking capacity but limit currents of
non-operation or operation in compliance with standard VDE 636/23.
Cut off characteristics: Curves indicate, for each rated current, the peak
value Ic that the current may reach as a function of prospective fault cur-
rent Ip.
Ø10,3±0,1 (1.3/32”)
38±0,6 (1-1
/
2”)
10
Rating (A) Designation Ref. Number Catalog Number
1 6,9 gRC 10-01 - A070 gRC 01 T13 Z330279
1,25 6,9 gRB 10-1,25 - A070 gRB 1.25 T13 X330001
1,5 6,9 gRB 10-1,5 - A070 gRB 1.5 T13 Y330002
2 6,9 gRB 10-02 - A070 gRB 02 T13 Z330003
2,5 6,9 gRB 10-2,5 - A070 gRB 2.5 T13 A330004
3 6,9 gRB 10-03 - A070 gRB 03 T13 B330005
4 6,9 gRB 10-04 - A070 gRB 04 T13 C330006
5 6,9 gRB 10-05 - A070 gRB 05 T13 D330007
6 6,9 gRB 10-06 - A070 gRB 06 T13 E330008
8 6,9 gRB 10-08 - A070 gRB 08 T13 F330009
10 6,9 gRB 10-10 - A070 gRB 10 T13 G330010
12,5 6,9 gRB 10-12,5 - A070 gRB 12.5 T13 H330011
16 6,9 gRB 10-16 - A070 gRB 16 T13 J330012
20 6,9 gRB 10-20 - A070 gRB 20 T13 K330013
25 6,9 gRB 10-25 - A070 gRB 25 T13 L330014
30 6,9 gRB 10-30 - A070 gRB 30T13 M330015
32* 6,9 gRB 10-32 - A070 gRB 32T13 Y330278
FR10GB69V1
FR10GB69V1.25
FR10GB69V1.5
FR10GB69V2
FR10GB69V2.5
FR10GB69V3
FR10GB69V4
FR10GB69V5
FR10GB69V6
FR10GB69V8
FR10GB69V10
FR10GB69V12.5
FR10GB69V16
FR10GB69V20
FR10GB69V25
FR10GB69V30
FR10GB69V32
* Non approval rating
Semiconductor fuses
Semiconductor (AC) fuses
SCAC170
Other Protistor®Fuses
Ferrule Fuses
10x38 URB/URD/URL - 500 to 600 VAC
12/04
Main Characteristics
Extremely high breaking capacity fuses:
Protection of power semiconductors complying with IEC standard
60269.1 and 4.
500 - 600 VAC voltage rating
aR-CLASS according to VDE 636-23 IEC 60269-4
Without blown fuse indication 0.10 up to 0.80 A**
With trip-indicator (1 to 30 A), a Ferraz Shawmut speciality*
Voltage
rating
UN( VAC )
600 V
without
blown fuse
indicator
500 V
with
trip-indicator
Class
URD
**
URD
URD
URL
Current
rating
IN( A )
100 mA
125 mA
160 mA
200 mA
250 mA
315 mA
400 mA
500 mA
630 mA
800 mA
1 A
1.25 A
1.6 A
2 A
2.5 A
3.15 A
4 A
5 A
6 A
8 A
10 A
12 A
16 A
20 A
25 A
30 A
Tested
breaking capacity
Total clearing I2t @ UN
I2tt (A2s)
1.2 10 -3
2.3 10 -3
5.2 10 -3
8 10 -3
18 10 -3
33 10 -3
56 10 -3
0.100
0.18
0.44
3.6
1.7
2.2
3.1
5.9
9
16
36
47
80
110
150
200
290
580
900
Pre-arcing
I2t @ 1 ms
I2tp (A2s)
0.40
0.13
0.31
0.65
1.65
2.80
5.30
12.7
1.3
2.3
3.6
5.25
9.30
16
37
58
Watts loss
0.8 ININ
0.23
0.25
0.28
0.34
0.35
0.42
0.46
0.46
0.52
0.58
2.8
0.52
0.58
0.63
0.63
0.86
1.1
1.1
0.73
0.,83
1
1.3
1.7
1.7
2.9
3.5
0.4
0.44
0.48
0.58
0.60
0.73
0.80
0.80
0.90
1
0.5
0.91
1
1.1
1.1
1.5
1.8
1.8
1.35
1.55
1.9
2.3
3.1
3.2
4.25
5.1
200 kA
@ 600 V
50 kA
@ 500 V
50 kA
@ 500 V
50 kA
@ 500 V
* minimum operating voltage for trip-indicator: 20 V
** higher ratings without blown fuse indicator see 10x38gRB - 690 VAC