Electrical data
Primary nominal Primary current Type
current rms measuring range
IPN (A) IPM (A)
50 ± 150 HTB 50-P/SP5, HTB 50-TP/SP51)
100 ± 300 HTB 100-P/SP5, HTB 100-TP/SP51)
200 ± 500 HTB 200-P/SP5
300 ± 600 HTB 300-P/SP5
400 ± 600 HTB 400-P/SP5
VCSupply voltage (± 5 %) 2) + 12 .. 15 V
ICCurrent consumption < 15 mA
VdRms voltage for AC isolation test, 50 Hz, 1 min 2.5 kV
RIS Isolation resistance @ 500 VDC > 500 MΩ
VOUT Output voltage (Analog) @ ± IPN, RL = 10 kΩ, TA = 25°C VOE ± 1.667 V
ROUT Output internal resistance 100 Ω
RLLoad resistance ≥ 10 kΩ
Accuracy - Dynamic performance data
XAccuracy @ IPN, TA = 25°C (excluding offset) < ± 1 % of IPN
εLLinearity error (0 .. ± IPN)< ± 1 % of IPN
VOE Electrical offset voltage @ TA = 25°C Vc/2 ± 30 mV
VOH Hysteresis offset voltage @ IP = 0,
after an excursion of 1 x IPN < ± 0.5 % of IPN
TCVOE Temperature coefficient of VOE HTB 50-(T)P/SP5 < ± 1.0 mV/K
HTB 100-(T)P..400-P/SP5 < ± 0.5 mV/K
TCVOUT Temperature coefficient of VOUT (% of reading) < ± 0.05 %/K
trResponse time to 90% of IPN step < 3 µs
BW Frequency bandwidth (0 .. -3 dB)3) DC .. 50 kHz
General data
TAAmbient operating temperature - 25 .. + 85 °C
TSAmbient storage temperature - 25 .. + 85 °C
mMass (-TP version) < 30 (< 36) g
IPN = 50 .. 400 A
Features
•Hall effect measuring principle
•Galvanic isolation between primary
and secondary circuit
•Isolation voltage 2500V
•Low power consumption
•Primary bus bar option for 50A and
100A version for ease of connection
Special feature
•Single power supply from 12V to 15V
Advantages
•Small size and space saving
•Only one design for wide current
ratings range
•High immunity to external
interference.
Applications
•AC variable speed drives
•Static converters for DC motor drives
•Battery supplied applications
•Uninterruptible Power Supplies
(UPS)
•Switched Mode Power Supplies
(SMPS)
•Power supplies for welding
applications.
Current Transducers HTB 50..400-P/SP5
and HTB 50..100-TP/SP5
For the electronic measurement of currents: DC, AC, pulsed, mixed,
with a galvanic isolation between the primary circuit (high power) and
the secondary circuit (electronic circuit).
Notes :
1) -TP version is equipped with a primary bus bar.
2) Operating at +12V ≤ Vc < +15V will reduce measuring range.
3) Derating is needed to avoid excessive core heating at high frequency.
070111/1 www.lem.com
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice.
Page 1/2