Power Supplies
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
146
IP67 SCP-X Extreme Environment Series
The SolaHD IP67 SCP-X power supplies provide the
versatility and cost-efciency to deliver reliable distributed
and remote eld power to machine controls. Mounts directly
on the machine or production line eliminating the complexity
and cost of unnecessary enclosures and excess wiring.
Quick change connectors simplify connectivity for distributed
I/O devices on industrial machinery. These Class II Listed,
24 Vdc power supplies are available in single and dual 100
Watt models and are perfect for automotive, packaging and
automated distribution applications.
Control Output Models
Designed for Control Power applications where a grounded
power supply output is required.
Input connector: 3-PIN IP67 molded plug externally
threaded with 7/8”-16 UN mounting thread.
Output connector: 4-PIN IP67 molded receptacle
internally threaded with 7/8”-16 UN mounting thread.
Isolated Output Models
Designed for application where an isolated output from
ground is required such as DeviceNet™.
Input connector: 3-PIN IP67 molded plug externally
threaded with 7/8”-16 UN mounting thread.
Output connector: 4-PIN IP67 molded receptacle
internally threaded with 7/8”-16 UN mounting thread.
Features
IP66/67 rated versatile enclosure
24 Vdc, 100-240 Vac, up to four outputs at 3.8A
Nominal Current (per pair for dual models)
Class II Listed power supply for stand alone applications
Can be mounted in any orientation without limitation
Safety approved for AC and DC universal input
Reliable operation from -40˚C to 60˚C without derating
DC OK Green LED
Worldwide approvals
Five year limited warranty
Certifications and Compliances
Listed, Ind. Control Equipment, E61379, ITE,
E137632
- UL 508, CSA C22.2 No. 107.1
- UL 60950-1/CSA C22.2 No. 60950-1, 2nd Edition
- Low Voltage Directive
- IEC/EN60950-1, 2nd Edition
• RoHS Compliant
Related Products
SDN Series
E61379
E137632
Recommended Electrical Connections/Cordsets 1
Input 3-PIN Connections Output 4-PIN Connections
Daniel Woodhead
P/N 103000A01FXX0 (2)
or
Harting
P/N 21 04 516 23XX (4)
Turck
P/N RSM46*M (3)
or
Harting
P/N 21 04 516 14XX (4)
1. Connections to be provided by the user.
2. XX is the length of the cordset in feet.
3. * is the length of the cordset in meters
4. XX is the length of the cordset in meters.
Selection Table
Catalog Number Output Current Output Voltage Output Power
SCP 100S24X-CP1
3.8 A
24 Vdc
100 W
SCP 100S24X-DVN1
SCP 102D24X-C02 7.6 A total (3.8 A
max. per pair) 2 x 100 W
SCP 102D24X-D02
Power Supplies
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
147
SCP100S24X-CP1 and SCP100S24X-DVN1 Mechanical Diagrams Electrical Connections
Top View Side View
Bottom View
6.52" (165.6 mm)
4.22" (107.1mm)
7.16" (181.8 mm)
4.85" (123.3 mm)
5.54" (140.8 mm) TYP
1.86" (47.3 mm)
S O L A
Power Supply
-
Input Output
50/60/400 Hz
100–240 V ac
100–353 V dc, 0.7–1.6 A
24 V dc, 3.8 A, Class II
SCP 100S24X-CP1
1 = Ground
2 = Power
3 = Neutral
3
1
2
1 = +24 V dc
2 = +24 V dc
3 = 0 V dc (1)
4 = 0 V dc (1)
2
3
4
1
SCP 100S24X-DVN1
1 = Ground
2 = Power
3 = Neutral
3
1
2
1 = +24 V dc
2 = +24 V dc
3 = Ground (2)
4 = -V dc (3)
2
3
4
1
NOTES:
1. 0 Vdc connections are internally bonded to ground.
2. Ground is isolated from V-.
3. Vdc is isolated from ground. -Vdc is a separately derived source, so it is
permissible to bond to ground if required in the application.
SCP102D24X-CO2 and SCP102D24X-DO2 Mechanical Diagrams Electrical Connections
6.52" (165.6 mm)
7.16" (182.0 mm)
4.22" (107.1 mm)
4.86" (123.5 mm)
3.35" (85.2 mm)
6.14" (156.1 mm) TYP
S O L A
Power Supply
Bottom View
Top View Side View
Input Output
50/60/400 Hz
100–240 Vac / 2.4 - 1.4A
100–353 Vdc / 2.4 - 0.7A
24 Vdc, 3.8 A (x2), Class II
SCP 102D24X-C02
1 = Ground
2 = Power
3 = Neutral
1 = Ground
2 = Power
3 = Neutral
INPUT
50/60/400 Hz
100–240 V ac / 2.4–1.4 A
100–353 V dc / 2.4–0.7 A
OUTPUT
24 V--- /3.8 A (x2)
CLASS 2
1 = +24 V---
2 = +24 V---
3 =
4 = 0 V---
0 V---
2
1
34
2
1
34
DC 1
DC 2
3
4
21
3
4
21
DC 11
DC 12
SCP 102D24X-D02
1 = Ground
2 = Power
3 = Neutral
1 = Ground
2 = Power
3 = Neutral
INPUT
50/60/400 Hz
100–240 V ac / 2.4–1.4 A
100–353 V dc / 2.4–0.7 A
3
OUTPUT
24 V--- /3.8 A (x2)
CLASS 2
1 = +24 V---
2 = +24 V---
3 = GROUND
4 = - V---
2
1
34
2
1
34
DC 1
DC 2
3
4
21
3
4
21
DC 11
DC 12
Power Supplies
Visit our website at www.emerson.com or contact Technical Services at (800) 377-4384 with any questions.
© December 2018
148
Descriptions
Catalog Number
SCP 100S24X-CP1 SCP 102D24X-C02
SCP 100S24X-DVN1 SCP 102D24X-D02
Input
Nominal Voltage Any voltage from 100 to 240 Vac Input
-AC Range 85 - 264 Vac Universal Input
-DC Range 100 - 353 Vdc
Nominal Current 11.6 A / 0.7 A 2.4 - 1.4 A / 2.4 - 0.7 A
-Inrush current max. Typ. <30 A
Power Factor Correction 20.95
Frequency 50/60/400 Hz
Output
Power Back Immunity 35 V
Overvoltage Protection 25-25.5 Vdc, autorecovery
Nominal Voltage 24 Vdc
Tolerance < +/-2% overall
- Line Regulation < 0.5%
- Load Regulation < 0.5%
- Time & Temp. Drift < 1%
Input Voltage Setting 24.5 V +/-1%
Ripple 3< 50 mVpp
Total Nominal Current 3.8 A 7.6 A Total (3.8 A max. per pair)
Holdup Time > 50 ms (Full load, 100 Vac Input @ Tamb=+25°C) to 95% output voltage
General
Emissions 4EN61000-6-3, EN61000-6-4, EN55011 Group 1, Class B, EN55022 Class B, EN61000-3-2, EN61000-3-3
Immunity 4EN61000-6-1, EN61000-6-2, EN55024, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4,
IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11, SEMI F47 Sag Immunity
Temperature
Storage: -40° to +85°C, Operation: -40° to +60°C full power with linear
derating to half power from +60° to +70°C.
No forced air required. Operation up to 100% load permissible
with sideways or front-side-up mounting orientation.
Storage: -40° to +85°C, Operation: -25° to +60°C full power with linear
derating to half power from +60° to +70°C.
No forced air required. Operation up to 100% load permissible
with sideways or front-side-up mounting orientation.
Humidity Up to 100% RH with condensation
Altitude 0 to 3,000 m (0 to 10,000 ft.)
Vibration 1 g non-operating swept sine over 10–500 Hz (IEC 60068-2-6). Non-operating random vibration test: 1.87 g over 10–500 Hz (IEC 60068-2-64).
Operating random vibration test: 0.15 g over 5–100 Hz (IEC 60068-2-64)
Shock Non-operating: 30 g peak, 18 ms half-sine pulse (IEC 68-2-27). Operating: 4 g peak, 22 ms half-sine pulse (IEC 68-2-27)
Warranty 5 Year Limited Warranty
MTBF >800,000 hours according to Telcoredia/Bellcore SR-332 Issue 1,
(Vin 120 Vac, Tamb = 40°C)
>800,000 hr. according to Telcoredia/Bellcore SR-332 Issue 3,
(Vin 120 Vac, ambient temp. = 40°C)
General Protection/Safety
Protected against continuous short-circuit, continuous overload,
and continuous open circuit. Protection NEC Class II (IEC536),
degree of protection IP66/IP67 versatile (IEC60529).
Safety extra low voltage circuits: SELV (acc. EN60950-1).
Protected against continuous short-circuit, continuous overload,
continuous open circuit. Protection Class I.
Safety extra low voltage circuits: SELV (acc. EN60950).
Status Indicators - Visual DC OK LED
Installation
Fusing
-Input Internally fused, fuses not replaceable
-Output Electronically current limited to meet NEC Class II per UL1310
Mounting Chassis mounted using integral mounting tabs. Recommended Screw Size: M4 x 0.7. Tightening Torque: 1N-m
Connections
An accessible disconnect device shall be installed external to the equipment.
Input: 3-PIN IP67 molded plug (quick disconnect).
Output: 4-PIN IP67 molded receptacle (quick disconnect).
Use UL 758 wire rated min. 24 V, VW-1/FT-1, max. 3.05 m.
Case IP66/67 versatile ingress protection; also meets UL50 Type 4X enclosure
Min. Required Free Space 0.39 in. (10 mm) all sides but base 1 in. (25 mm) all sides but base
H x W x D - in (mm) 4.73 x 7.00 x 1.80 (120.1 x 177.8 x 45.7) 4.73 x 7.00 x 3.27 (120.1 x 177.8 x 83.0)
Weight - lbs (kg) 2.2 (1.0) 3.3 (1.5)
1. Input current ratings are specied with low input, line conditions, worst case efciency values and power factor.
2. Power Factor Correction at 50/60 Hz only.
3. Ripple/noise is stated as typical AC values when measured with a 20 MHZ bandwidth scope and 50 Ohm termination.
4. Emissions and immunity are met by individual power supply modules.
IP67 SCP-X Specifications