Industrial Power Supplies
TSP-Series
http://www.tracopower.com Page 1 of 9
The TSP series comprises high performance DIN-rail mount power supplies designed
for reliable operation under difficult factory floor conditions. High immunity against
electrical disturbances and rugged metal casing make these modules the best choice
to power sensitive loads in industrial process control systems, machine tools or other
demanding industrial applications. They provide a DC-OK signal and external shut
down function. Detachable screw terminal blocks make the connection easy.
This power supply line is accompanied by a wide range of function modules for
reliable system solutions:
Redundancy modules for true current sharing in parallel operation and for
redundant systems.
Battery controller modules to configure high reliable UPS systems for 12, 24 and
48 VDC. Selection of battery packs available.
Buffer modules for protection against short time AC power loss. Maintenance
free! No batteries required.
Innovative and Powerful Features!
Rugged metal case for
harsh industrial environments
Shock and vibration proof
Worlwide Safety approval package.
ATEX certification tested in accordance
to IECEX (opt. EX)
Model TSP 090-124N meets NEC class 2
Industrial operating temperature range:
25°C to +70°C
Adjustable output voltage
Protection against short-circuit,
overvoltage and over-temperature
Power OK signal, Remote On/Off
Wall mounting (opt.)
3-year product warranty
IEC 60950-1 UL 60950-1
UL 508
UL 60079-15
ATEX II3G
Order Code Output Power
(Pmax)
**Output Voltage
(Vnom)
***Output Current
(Imax)
TSP 070–112* 72 W 12 VDC 6.0 A
TSP 090–124* 90 W 24 VDC 3.75 A
TSP 090–124N 90 W 24 VDC 3.75 A
TSP 090–148* 96 W 48 VDC 2.0 A
TSP 140–112* 144 W 12 VDC 12.0 A
TSP 180–124* 180 W 24 VDC 7.5 A
TSP 180–148* 192 W 48 VDC 4.0 A
TSP 360–124* 24 VDC 15.0 A
TSP 360–148* 360 W 48 VDC 7.5 A
TSP 600–124* 24 VDC 25.0 A
TSP 600–136 600 W 36 VDC 16.5 A
TSP 600–148* 48 VDC 12.5 A
Models
* For ATEX compliant models add appendix -EX to order code.
** Output voltage adjustable 1214 VDC, 2428 VDC and 48–56VDC
*** Max. current at nominal output voltage and operating temperature up to +40°C max.
EMC
LVD
CB
Scheme
Function Modules (see page 5)
http://www.tracopower.com Page 2 of 9
Industrial Power Supplies
TSP Series 70600 Watt
Input Specifications
Input voltage range TSP 070/090 85 – 264 VAC universal input
other models: 85 – 132 / 187 – 264 VAC autoselect
output current derating at operation below 100 VAC see graph B, page 4
Input voltage frequency 47 – 63 Hz
Harmonic limits EN 61000-3-2, Class A (for limited output power)
Holdup time 230 VAC 20 ms
115 VAC 10 ms at full load, 20 ms at 66% load
Inrush current 115 VAC 230 VAC
TSP 070/090 < 12 A < 20 A
TSP 140/180 < 13 A < 25 A
TSP 360 < 16 A < 25 A
TSP 600 < 25 A < 30 A
Recommended circuit breaker, TSP 070/090/140/180 6.0 – 16.0 A
characteristic B TSP 360 10.0 16.0 A
TSP 600 16.0 – 25.0 A
Efficiency 87 % typ.
Output Specifications
Output voltage adj. range 12 VDC models: 12 – 14 VDC
24 VDC models: 24 – 28 VDC
36 VDC model: 36 – 42 VDC
48 VDC models: 48 – 56 VDC
At output voltage higher than nominal output voltage
max. output current has to be reduced accordingly, in
order not to exceed max. output power.
Regulation – Input variation 0.5 % max.
– Load variation (10100 %) 0.5 % max.
Ripple and Noise (20MHz bandwidth) 100 mV pk-pk typ. (200 mV pk-pk max. at Imax)
Electronic short circuit protection current limitation at Imax.
constant current, automatic recovery
Output overvoltage protection 12 VDC models: 20 V
24 VDC models: 35 V
36 VDC model: 43 V
48 VDC models: 60 V
Overload protection electronic overload protection
Overtemperature protection switch off at overtemperature, automatic restart
Power back immunity 12 VDC models: 16 V
24 VDC models: 35 V
36 VDC model: 48 V
48 VDC models: 63 V
Status indicator dual color LED (green: DC ok, red: DC off)
Power OK signal – trigger threshold: 12 VDC models: 9 – 11 V
24 VDC models: 18 – 22 V
36 VDC model: 27 – 34 V
48 VDC models: 36 – 46 V
– active output signal: 12 VDC models: 11.0 V ±1.0 V
(reference to –Vout) (20 mA max. for TSP 070, 40 mA max. for TSP 140)
24 VDC models: 22.0 V ±2.0V / 20 mA max.
(10 mA max. for TSP 090, 20mA max. for others)
36 VDC model: 34.0 V ±2.0 V / 20 mA max.
48 VDC models: 44.0 V ±4.0 V / 15 mA max.
– relay output DC OK = contact closed
rated: 30 VDC/1.0 A for 12/24 VDC models
rated: 30 VDC/2.0 A for 36 VDC model
rated: 48 VDC/0.5 A for 48 VDC models
http://www.tracopower.com Page 3 of 9
Industrial Power Supplies
TSP Series 70600 Watt
General Specifications
Max. capacitive load unlimited
Temperature range – Operating 25°C to +70°C max.
(for derating see graph A on page 4)
– Storage 25°C to +85°C
Cooling convection cooling, no internal fan
Humidity (non condensing) 95 % rel. H max.
Pollution degree 2
Temperature coefficient 0.02 %/K
Reliability, calculated MTBF (at +25°C acc. to IEC 61709) – TSP 070/090 >1.8 Mio h
– TSP 140 >1.2 Mio h
– TSP 180/360/600 >0.9 Mio h
Remote On/Off by ext. contact.
DC on: -S contact open
DC off: -S connectetd via 1Kohm to -Vout
Isolation according to IEC/EN 60950-1, UL 60950-1, UL 508
Safety standards – Information technology equipment
IEC/EN 60950-1, UL 60950-1, CSA-C22.2 No. 60950-1-03
– Industrial control equipment UL 508,
CSA-C22.2 No. 107
– Electrical equipment for machines EN 60204
– Electronic equipment for power installation EN 50178
– Safety transformers for SMPS EN 61558-2-16
– Limited power source (model TSP 090-124N) EN 60950 sect. 2.5 and NEC Class 2
– Control equipment for hazardous location UL 60079-15
(Class I, Division 2, Groups A,B,C,D AEx n C II C T4 U)
IEC/EN 60079-15 (Class I, Zone 2, EEx nC II C T4 U),
( II3G EEX nAC IIC T4 (T3 with limited power)
Safety approvals and – CB report for IEC/EN 60950-1
certifications – UL approvals UL 60950-1 rec. File: e181381, UL 508 listed File: e210002
– CSA certification (file no. 219759) for UL 60950-1, UL 508, UL 60079-15-02,
ANSI/ISA 12.12.01, CSA-22.2 No. 60950-1-03,
CSA C22.2 No. 107, CSA 60079-15-02
II3G ATEX 94/9/EC certificate no. EPS 12 ATEX 1 424 X (option -EX only)
– BG certification EN 60950-1, EN 60204-1, EN 61558-2-16, EN 50178
– Certification documents www.tracopower.com/overview/tsp
Class of protection safety class I (IEC 536)
Degree of protection IP 20 (IEC/EN 60529)
Electromagnetic compatibility (EMC), Emissions EN 61000-6-3, EN 61204-3
– Conducted RI suppression on input EN 55011 class B, EN 55022 class B,
– Radiated RI suppression EN 55011 class B, EN 55022 class B,
Electromagnetic compatibility (EMC), Immunity EN 61000-6-2, EN 61204-3
– Electrostatic discharge (ESD) IEC / EN 61000-4-2 4 kV / 8 kV criteria B
– Radiated RF field immunity
TSP 070/140/360 models: IEC / EN 61000-4-3 10 V / m criteria A
TSP 090/180/600 models: IEC / EN 61000-4-3 10 V / m criteria B
– Electrical fast transient / burst immunity IEC / EN 61000-4-4 2 kV criteria B
– Surge immunity IEC / EN 61000-4-5 1 kV / 2 kV criteria B
– Immunity to conducted RF disturbances IEC / EN 61000-4-6 10 V criteria A
– Power frequency field immunity IEC / EN 61000-4-8 30 A / m criteria A
– Mains voltage dips and interruptions IEC / EN 61000-4-11 criteria B/C
– Voltage sag immunity SEMI F47
www.tracopower.com/products/TSP_SemiF47.pdf
http://www.tracopower.com Page 4 of 9
All specifications valid at nominal input voltage, full load and +25°C after warm-up time unless otherwise stated.
Industrial Power Supplies
TSP Series 70600 Watt
General Specifications
Environment – Vibration acc. IEC 60068-2-6; 3 axis, sine sweep, 10 – 55 Hz, 1 g, 1 oct/min
– Shock acc. IEC 60068-2-27 3 axis, 15 g half sine, 11 ms
Enclosure material aluminium (chassis) / stainless steel (cover)
Mounting – DIN-rail mounting for DIN-rails as per EN 50022-35x15/7.5
(snap-on with self-locking spring)
– Wall mounting (option) with wall mounting bracket - see page 9
Connection detachable screw terminals (plugs included)
2 terminals per output
Remote On/Off connection – 2 pin molex male terminal KK series mating connector information (cable not included)
www.tracopower.com/products/tsp-rc-cable.pdf
Installation instructions www.tracopower.com/overview/tsp
Output Power Derating
Temperature [°C]
40
50
60
70
Output Power [% Pmax]
40 50 60 70
In
p
ut Volta
g
e [VAC]
40
50
60
Output Power [% Pmax]
80
90
100
A) Output Power Derating
vs Ambient Temperature
70
80
90
100
85
90
100
110
115 132
187 230 264
B) Output Power Derating
vs Input Voltage
-25
TSP 070
TSP 140
TSP 090
TSP 180
TSP 360
TSP 600
http://www.tracopower.com Page 5 of 9
Industrial Power Supplies
TSP Series 70600 Watt
Function Modules Overview
Redundancy Module:
With this module and two power supplies of the TSP series
a highly reliable, true redundant power system can be configured
without any additional components. This module provides:
Operation with true current sharing
Alarm outputs and redundancy OK signal
Hot swappable inputs can be loaded up to 15 A each
(resp. 25 A with model TSP REM600)
Order Code Output Voltage adj. Output Power
TSP–REM360 24 VDC
(24 – 27 VDC)
360 W
TSP–REM600 600 W
Models
Battery Controller Modules + Batteries:
This module provides a professional battery controller to charge and
monitor an external lead-acid battery. Together with a power supply
of the TSP series and a battery pack a perfect DC-UPS system can be
configured. This module provides:
- Battery protection for over voltage, deep discharge, short circuit
and reverse connection
- Remote On/Off for battery and power supply
- Alarm outputs for input, output and battery condition
- Controlled end of charge voltage by temperature sensor
- Redundant inputs for two indepedant sources (TSP-BCMU360 only)
Order Code Output Voltage Output Power
TSP-BCM12 12 VDC 180 W
TSP–BCM24 24 VDC 360 W
TSP-BCM24A 600 W
TSP–BCM48 48 VDC 360 W
TSP-BCM48A 600 W
TSP-BCMU360 24/48 VDC 360 W
Models
TSP-BCM12
TSP-BCM24
TSP-BCM48
TSP-BCM24A
TSP-BCM48A
Buffer Module:
Order Code Output Voltage Output Power
TSP–BFM24 24 – 28VDC 600 W
Models
This module will maintain the output voltage of a 24 VDC power
supply during typical mains faults, short time blackouts or voltage
dips of up to ten full 50 Hz cycles. During this buffer period no
deterioration of the 24 VDC output voltage will occur. This module
provides:
- Capacitor bank for energy storage, no battery needed!
- Maintenance free, long lifetime, high performance also
at low temperature.
- Guaranteed Hold-up-time 200 ms/25 A to 4 s/1.2 A max.
- Output 24 to 28 VDC, 600 W max.
- Active ready and inhibit signals
TSP-REM360
TSP-REM600
TSP-BFM24
TSP-REM datasheet: www.tracopower.com/products/tsp-rem.pdf
TSP-BFM datasheet: www.tracopower.com/products/tsp-bfm.pdf
TSP-BCMU360
TSP-BCM datasheet: www.tracopower.com/products/tsp-bcm.pdf
TSP-BCMU datasheet: www.tracopower.com/products/tsp-bcmu.pdf
http://www.tracopower.com Page 6 of 9
Industrial Power Supplies
TSP Series 70600 Watt
Outline Dimensions
Models:
TSP 070/090
35.0
110.0
(1.38)
(4.33)
110.0
(4.33)
38.5
(1.52)
80.0
(3.15)
25.0
(0.98)
5.0
(0.20)
5.0
(0.20)
DC ON
O/P ADJ.
DC OK
PE NL
P/S
PS
Remote
54.0
110.0
(2.13)
(4.33)
110.0
(4.33)
25.0
(0.98)
5.0
(0.20)
14.5
(0.57)
DC ON
O/P ADJ.
DC OK
PE NL
P/S
P
S
Remote
38.5
(1.52)
80.0
(3.15)
Weight: 0.5kg (1.0lb )
Weight: 0.7kg (1.4lb)
Models:
TSP 140/180
Dimensions in [mm], () = inch
Tolerances: ±0.5 mm (±0.02)
http://www.tracopower.com Page 7 of 9
Industrial Power Supplies
TSP Series 70600 Watt
Outline Dimensions
80.0
125.0
(3.15)
(4.92)
125.0
(4.92)
45.0
(1.77)
86.5
(3.41)
(1.81)
5.0
(0.20)
25.0
(0.98)
25.0
(0.98)
46.0 17.0
(0.67)
DC ON
O/P ADJ.
DC OK
PE NL
P/S
PS
Remote
Models:
TSP 360
Weight: 1.1kg (2.4lb)
Dimensions in [mm], () = inch
Tolerances: ±0.5 mm (±0.02)
http://www.tracopower.com Page 8 of 9
Industrial Power Supplies
TSP Series 70600 Watt
Outline Dimensions
Models:
TSP 600
165.0
125.0
(6.50)
(4.92)
125.0
(4.92)
25.0
(0.98)
25.0
(0.98)
123.0
(4.84)
21.0
(0.83)
P/S
PS
Remote
DC ON
O/P ADJ.
DC OK
PE NL
45.0
(1.77)
86.5
(3.41)
Weight: 2.8kg (6.0lb)
Dimensions in [mm], () = inch
Tolerances: ±0.5 mm (±0.02)
Outline Dimensions mm (inches)
Specifications can be changed without notice! Make sure you are using the latest documentation, downloadable at www.tracopower.com
www.tracopower.com
Page 9 of 9
Industrial Power Supplies
TSP Series 70600 Watt
Rev. March 19. 2018
Ordercode of Kit For Models Content of Kit
TSP-WMK03
TSP-WMK02
TSP 070, TSP 090, TSP 140, TSP 180
TSP 360, TSP 600
1 bracket
2 brackets
TSP–WMK Wall Mounting Bracket
15.0
(0.59)
7.0
(0.28)
15.0
(0.59)
Material: 2 mm Mild Steel
Tolerance: ±0.1mm (± 0.004)
55.0 (2.16)
46.0
(1.81)
33.0
(1.30)
25
(0.98)
50.0
(1.97)
2x
ø
4.3
(0.17)
4 x positioning holes
2.0
(0.08)
Material: 2 mm Mild Steel
Tolerance: ±0.1mm (± 0.004)
62.5 (2.46)
96.0 (3.78)
62.5 (2.46)
173.0 (6.81)
TSP 360
TSP 600
2.0
(0.08)
30.0
(1.18)
15.0
(0.59)
ø
4.3
(0.17)
7.0
(0.28)
TSP 070
TSP 090
TSP 140
TSP 180
ø
4.25
(0.17)
2.0
(0.08)
2.0
(0.08)
R 2.12
(0.083)
R 2.12
(0.083)
42.5
(1.67)
34.5
(1.36)
34.5
(1.36)
74.0
(2.91)
37.0
(1.45)
25.0
(0.98)
25.0
(0.98)
4 x positioning holes
2.0
(0.08)
2.0
(0.08)
R 2.12
(0.083)
R 2.12
(0.083)
ø
4.25
(0.17)
ø
4.25
(0.17)
TSP-WMK03
TSP-WMK02
Dimensions in [mm], ( ) = Inch
Tolerances: ±0.5 mm (±0.02)
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
TRACO Power:
TSP-BCM24 TSP-BFM24 TSP 180-124 TSP 070-112 TSP 600-124 TSP 600-148 TSP 360-124 TSP 090-124
TSP 140-112 TSP-REM360 TSP 090-124 EX TSP 180-124 EX TSP 140-112 EX TSP-REM360 EX TSP-BCMU360
TSP 180-148 EX TSP 090-148 EX TSP 600-148 EX TSP-BCM48 TSP-REM600 TSP 070-112 EX TSP 360-148
TSP 090-148 TSP 600-136 TSP 600-124 EX TSP-BCM24A TSP-BCM48A TSP 360-124 EX TSP-REM600 EX
TSP 360-148 EX TSP-BCM12 TSP 180-148 TSP090-124N