Metric NPT PG
Ø 18.8 mm M16x1.5 3/8 Inch 11
Ø 22.8 mm M25x1.5 ½ Inch – 16 16
Ø 28.0 mm M25x1.5 ¾ Inch 16
Gland Plate Installation Instructions
2
3
4
5
1
1
4
2
3
5
Ø 22.8 mm
Clamp
(not included)
Clip
(not included)
FSA FSB & FSC
FSB FSC
Ø22.8 mm Ø22.8 mm Ø28.0 mm Ø28.0 mmØ18.8 mm Ø18.8 mm
Frame Size A B C
Tightening Torque (Nm) 1.1 1.5 2.25
Tightening Torque (lbf.in) 10 13.3 20
Recommended Minimum
Cable Cross Section (mm2)1 1.5 2.5
Maximum Cable Cross
Section (mm2)2.5 6 10
Recommended Minimum
Cable Cross Section (AWG) 17 AWG 16 AWG 14 AWG
Maximum Cable Cross
Section (AWG) 14 AWG 10 AWG 8 AWG
Wire Size and Terminal Torques - Field Wiring Connectors
Ground
(Earth)
Ground
CAUTION
1. Bonding between conduit connections is not automatic and must be provided as a part of the installation.
2. The Earth bonding conductor must be equal or greater in cross-section to the power supply cable.
3. GROUNDING (EARTH) must be made at points shown in illustration above.