Technical data
Ambient conditions
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
General
Housing material PA 6.6
Inflammability class according to UL 94 V0
Color black
Standards for air and creepage distances IEC 60664-1
Mounting type DIN rail: 35 mm
Type DIN rail module, two-section, divisible
Direction of action Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Earth Ground
Transmission speed 90 MBit/s
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage UN24 V DC
Maximum continuous operating voltage UC15 V DC
10 V AC
Nominal current IN600 mA (up to 40 °C)
Operating effective current IC at UC≤ 100 µA (per system)
Residual current IPE ≤ 100 µA (per system)
Nominal discharge current In (8/20) µs (Core-Core) 10 kA
Nominal discharge current In (8/20) µs (Core-Earth) 10 kA
Total surge current (8/20) µs 20 kA
Impulse discharge current (10/350)˽µs, peak value limp 2.5 kA
Voltage protection level UP (Core-Core) ≤ 90 V (C1 - 1 kV/500 A)
≤ 40 V (C3 - 25 A)
≤ 145 V (C2 - 10 kV / 5 kA)
Voltage protection level UP (Core-Earth) ≤ 90 V (C1 - 1 kV/500 A)
≤ 145 V (C2 - 10 kV / 5 kA)
≤ 40 V (C3 - 25 A)
Voltage protection level UP static (core-core) ≤ 55 V (C1 - 1 kV/500 A)
Voltage protection level UP static (core-ground) ≤ 55 V (C1 - 1 kV/500 A)