Grayhill, Inc. • 561 Hillgrove Avenue • LaGrange, Illinois 60525-5997 • USA • Phone: 708-354-1040 • Fax: 708-354-2820 • www.grayhill.com
I/O Modules
Manual Override Output Modules
FEATURES
Integral Three Position Manual
On/Manual Off and Automatic
Control Toggle Switch
Transient Protection: Meets the
requirements of IEEE 472, “Surge
Withstanding Capability Test”
UL, CSA Certified
Optical Isolation
G5 Modules Provide Replaceable
5x20 mm Glass Fuse
Built-in Status LED
CIRCUITRY
Maximum Current Versus
Ambient Temperature
The chart indicates continuous current to limit
the junction temperatures to 100°C. Information
is based on steady state heat transfer in a two
cubic foot sealed enclosure.
Figure 1
FUSES
G5 Fuses are 5 Amp Littelfuse part number
217005 or equivalent.
Figure 2
Maximum Peak Surge Current
Versus Surge Duration (AC Outputs)
Information is based on a supply frequency of
60 Hz sinusoidal and a resistive or inductive
load. Application of maximum surge current
may not be repeated until the module
temperature has returned to its steady state
value.
4
3
2
1
-40˚ -20˚ 0 20˚ 40˚ 60˚ 80˚ 100˚
AMBIENT TEMPERATURE (˚C)
LOAD CURRENT (AMPS)
G5 PACKAGE
80
40
60
30
20
10
6
4
3
1
1
12346 2010 40 60 100
1000
300
200
100
NUMBER OF FULL CYCLES AT 60 HERTZ
PEAK SURGE CURRENT (AMPERES)
STANDARD, MINI, G5
OPENLINE
1
2
3
4
Rx
VAC
DC CONTROL
TRIGGER
CIRCUIT
SNUBBER
LOAD
LOAD
+
5
OFF
AUTO
ON
1
2
3
4
Rx
VDC
DC CONTROL
VOLTAGE
SPIKE
PROTECTION
LOAD
LOAD
DRIVER
CIRCUIT
+
+
5
OFF
AUTO
ON
AC Outputs DC Outputs
I/O
12
I/O Modules
4#;*+..X 0%T  IJE +..)418' 8'07'  #4#0)'X ..+01+5 JNIFIgIMMK    *10'U KNLgGIHgENHN  #:U KNLgGIHgFLFN  999T)4#;*+..T%1/
G5, Zero Voltage Turn On, Manual Override 70G-OAC5MA 70G-OAC24MA 70G-OAC24AMA
Specications Units
Nominal Line Voltage Vac 120 120 240
Load Voltage Range Vac 24-140 24-140 24-280
Minimum Peak Blocking Voltage Volts 400 400 600
Maximum O-state Leakage @ 60Hz mA, rms 2 2 4
Nominal Logic Voltage (Vcc) Vdc 5 24 24
Logic Voltage Range Vdc 4-6 18-32 18-32
Max. Logic Supply Current @ Nominal Vcc mA 20 8 8
Nominal Input Resistance (Rx) W 100 2700 2700
Minimum Drop-Out Voltage Vdc 1 1 1
Maximum Reverse Logic Voltage Vdc -5 -5 -5
Maximum Zero Voltage Oset (Vpeak) 8 8 8
Frequency Range (Hz) 25-70 25-70 25-70
#07#.8'44+&'762761&7.'5
SPECIFICATIONS: All Modules*
Output Specications
Load Current Range (rms): 0.03 to 3.5 Amps,
Maximum current is derated as shown in Figure
1.
Maximum Surge Current (peak): 80 Amps at 60 Hz,
1 cycle as qualied by Figure 2 for AC outputs. 5
Amp maximum for 1 second for DC outputs.
Turn-on Time (60 Hz): 8.3 mSec maximum for AC
outputs. 20 µSec maximum for DC outputs.
Turn-o Time (60 Hz): 8.3 mSec maximum for AC
outputs. 50 µSec maximum for DC outputs.
ON State Voltage Drop (peak): 1.5 volts max.
Power Dissipation: 1.0 Watt/Amp typical
General Characteristics
Isolation Voltage Field to Logic: 4000 Vac (rms)
minimum
Vibration: 20 G’s peak or .06” double amplitude
10–2000 Hz per MIL–STD–202, Method 204,
Condition D
Mechanical Shock: 1500 G’s 0.5 mS half-sine per
MIL–STD–202, Method 213, Condition F
Storage Temperature Range:
-40°C to +125°C
Type/Function Grayhill Part Number
AC Outputs
SPECIFICATIONS: By Part Number
DC Outputs
Grayhill Part Number
70G-ODC5MA 70G-ODC24MA
Maximum Line Voltage Vdc 60 60
Load Voltage Range Vdc 3-60 3-60
Maximum O-state Leakage @ 60 Vdc mA 1.5 1.5
Maximum Turn-on Time µSec 20 20
Maximum Turn-o Time µSec 50 50
Nominal Logic Voltage (Vcc) Vdc 5 24
Logic Voltage Range Vdc 4-6 18-32
Max. Logic Supply Current
@ Nominal Vcc mA 13 9
Nominal Input Resistance (Rx) W 150 2700
Minimum Drop-Out Voltage Vdc 1 1
Maximum Reverse Logic Voltage Vdc -5 -5
Maximum Clamping Voltage Vdc 80 80
Available from your local Grayhill Distributor. For
prices and discounts, contact a local Sales Oce,
an authorized local Distributor or Grayhill.
Operating Temperature Range:
-40°C to +100°C
Type/Function
G5 Manual Override
Specications Units
*Specications apply over operating temperature range unless noted otherwise.
I/O
13