A&D AS CC DC CS8-configuration.pdf 12.09.01 How to configure CS8 + CBP2 1. HW Configuration Just insert CS8 into SIMADYN D rack, that's all; you cannot / need not insert additional CBP2 with HW Config! For symbolic referenc to the CS8-related FB either keep in mind the "name" (default setting "D0#00C" with # as the number of the inserted slot (e.g. D0200C) or choose an own name, e.g. like "PROFIB"). 2. Function blocks in CFC chart Following blocks have to be used: 1. CBCONF to initialize CBP2; Only PROFIBUS-Slave address has to be set ("3" in the example); all other inputs could be left 0; cycle time: very low 2. @CSPAR to control and monitor the link PMx CS8 and - optional!- to handle the defined parameters (with @TP_xxxx; not shown in the example) cycle time: approx. 100ms, max. 200ms 3. CRV, CTV to define a symbolic name for the net data telegrams ("virtual connection") Seite 1 / 2 A&D AS CC DC CS8-configuration.pdf 12.09.01 far right side: Seite 2 / 2