• Lightweight and Compact in size
• Wide Power Range: 15W – 240W
• Universal Input:
15W to 90W: 85-264V AC/100-370V DC
120W and 240W: 85-264V AC/100-350V DC
• Power Factor Correction (EN61000-3-2) for 60W to 240W
• Meets SEMI F47 Sag Immunity (120W & 240W)
• NEC Class 2 rated (15W, 30W & 60W)
• Approved for Class 1, Div. 2 Hazardous Locations
• Fused input
• Overcurrent protection, auto-reset
• Overvoltage protection, shut down
• Spring-up Screw Terminal type, IP20
• DIN rail or Panel Surface Mount
• Approvals:
CE Marked, TÜV, c-UL, UL 508, UL 1310 (PS5R-SB, -SC, -SD),
UL 1604, EN 50178:1997, LVD: EN60950:2000, EMC: Directive,
EN61204-3:2000 (EMI: Class B, EMS: Industrial)
Slim Line Power Supplies PS5R-S
Features
Specifications
For more information on these
and other IDEC power supplies, visit:
www.idec.com/powersupply
Part
Numbers
5V DC output PS5R-SB05 – – – – –
12V DC output PS5R-SB12 PS5R-SC12 – – – –
24V DC output PS5R-SB24 PS5R-SC24 PS5R-SD24 PS5R-SE24 PS5R-SF24 PS5R-SG24
Output Capacity 15W (5V Model is 10W) 30W 60W 90W 120W 240W
Input
Input Voltage
(single-phase, 2-wire)
85 to 264 VAC,
100 to 370 VDC
85 to 264V AC,
100 to 350V DC
Input Current
(maximum)
100VAC 0.45A 0.9A 1.7A 2.3A 1.8A 3.5A
200VAC 0.3A 0.6A 1.0A 1.4A 1.0A 1.7A
Internal Fuse Rating 2A 3.15A 3.15A 4A 4A 6.3A
Inrush Current (cold start) 50A maximum (at 200V AC)
Leakage Current (at no load) 132V AC: 0.38 mA maximum
264V AC: 0.75 mA maximum 0.75mA maximum 1mA maximum
Typical
Efficiency
5V DC 69% – – – – –
12V DC 75% 78% – – – –
24V DC 79% 80% 83% 82% 84%
Output
Output Current
Ratings
5V DC 2.0A – – – – –
12V DC 1.2A 2.5A – – – –
24V DC 0.65A 1.3A 2.5A 3.75A 5A 10A
Voltage Adjustment ±10% (V. ADJ control on front)
Output Holding Time 20ms minimum (at rated input and output)
Starting Time 200ms maximum – – – 650ms maximum 500ms maximum
Rise Time 100ms maximum (at rated input and output) 200ms maximum
Line Regulation 0.4% maximum
Load Regulation 1.5% maximum 0.8% max
Temperature Regulation 0.05% degree C maximum
Ripple Voltage 2% peak to peak maximum (including noise) 1% peak to peak maximum (including noise)
Overcurrent Protection 105% or more, auto reset 105 to 130%, auto reset 103 to 110%, auto reset
Overvoltage Protection 120% min. SHUTDOWN
Operation Indicator LED (green)
Voltage Low Indication LED (amber) – – – LED (amber)
New