EMC filters
2-line filters
for converters and power electronics
Rated current 8 to 180 A
Series/Type: B84142A*R122
Date: January 2006
EPCOS AG 2006. Reproduction, publication and dissemination of this data sheet and the
information contained therein without EPCOS’ prior express consent is prohibited.
2-line filters B84142A*R122
for converters and power electronics
Power line filters for 1-phase systems
Rated voltage 300 V DC/AC, 50/60 Hz
Rated current 8 to 180 A
Construction
2-line filters
Metal case
Features
High insertion loss
Optimized leakage current
Easy to install
Space-saving design
Low weight
Design complies with
EN 133200, UL 1283, CSA C22.2 No.8
UL and cUL approval
Applications
Power supplies
DC applications
Terminals
Finger-safe terminal blocks
Marking
Marking on component:
Manufacturer’s logo, ordering code,
rated voltage, rated current, rated temperature,
climatic category, date code
Minimum marking on packaging:
Manufacturer’s logo, ordering code
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 2
2-line filters B84142A*R122
for converters and power electronics
Typical circuit diagram
L
SSB2112-K
LINE LOAD
L’
N N’
Technical data and measuring condition
Rated voltage VR 300 V DC/AC, 50/60 Hz
Rated current IR Referred to 50 °C ambient temperature
Test voltage Vtest 1700 V DC, 2 s (line/line)
3000 V DC, 2 s (lines/case)
Overload capability (thermal) 1.5 · IR for 3 min per hour or
2.5 · IR for 30 s per hour
Leakage current Ileak At 300 V AC, 50 Hz
Climatic category (IEC 60068-1) 25/100/21 (–25 °C/+100 °C/21 days damp heat test)
Approvals UL 1283, CSA C22.2 No.8
Characteristics and ordering codes
VR
AC/DC
V
IR
A
Terminal
cross section
mm2
Ileak
mA
Rtyp
m
Approx.
weight
kg
Ordering code Approvals
300 8 4 < 33 15 0.7 B84142A0008R122 ×
16 4 < 33 9 1.1 B84142A0016R122 ×
30 10 < 33 5 1.7 B84142A0030R122 ×
42 10 < 60 4 1.9 B84142A0042R122 ×
55 10 < 60 3 1.9 B84142A0055R122 ×
75 16 < 60 1.5 2.6 B84142A0075R122 ×
100 35 < 110 1.1 5.0 B84142A0100R122 ×
130 50 < 110 0.7 8.0 B84142A0130R122 ×
180 95 < 110 0.5 8.0 B84142A0180R122 ×
× = approval granted
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 3
2-line filters B84142A*R122
for converters and power electronics
Dimensional drawings
B84142A0008R122 (8 A)
133.7 8
Vacant
SSB2113-T-E
63
PE M4 x 15
4.5
155±0.5
165
38±0.3
Marking
LINE LOAD
L
N
L’
1.5
Tightening torque 0.5 ... 0.6 Nm
Terminal blocks 4 mm 2
N
B84142A0016R122 (16 A)
199.5 9
46.4
51.4
50
60
SSB2114-2-E
70
PE M5 x 19
Marking
LOADLINE
N
L
N’
221±0.5
231
4.5
38±0.3
1.5
Tightening torque 0.5 ... 0.6 Nm
Terminal blocks 4 mm 2
L
Vacant
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 4
2-line filters B84142A*R122
for converters and power electronics
Dimensional drawings
B84142A0030R122 … A0055R122 (30 A, 42 A, 55 A)
200 8
PE M6 x 24
90
1.5
120
70
Vacant
4.5
35±0.3
58
255±0.5
265
Marking
LINE LOAD
N’
L’L
N
2
Terminal blocks 10 mm
Tightening torque 1.2 ... 1.5 Nm
SSB2115-A-E
B84142A0075R122 (75 A)
8
SSB2116-I-E
200
141.5
4.5
35±0.3
58
255±0.5
265
LINE
Marking
LOAD
L
N
L’
N’
Terminal blocks 16 mm 2
PE M6 x 24
1.5
Tightening torque 1.5 ... 1.8 Nm
Vacant
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 5
2-line filters B84142A*R122
for converters and power electronics
B84142A0100R122 (100 A)
240
25
135
100
80
13
63
46
PE M10 x 34
Vacant
255±0.5
60±0.3
N’
L’
N
L
290
LOAD
Marking
LINE
Terminal blocks 35 mm 2
Tightening torque 3.2 ... 3.7 Nm
SSB2117-R-E
B84142A0130R122 (130 A)
PE M10 x 35
240
326
86 54
1
90
60
150
73.6
255±0.5
N
L
N’
L’
65±0.3
270
6.5
LINE LOAD
Marking
6.5
Terminal blocks 50 mm 2
Tightening torque 6 ... 8 Nm SSB2118-Z-E
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 6
2-line filters B84142A*R122
for converters and power electronics
B84142A0180R122 (180 A)
339 90
240
47.4 74
1
150
55
18
60
PE M10 x 34
LINE
N
L
LOAD
Marking
N’
L’
6.5
65±0.3
270
255±0.5
Terminal blocks 95 mm
2
Tightening torque 15 ... 20 Nm
SSB2119-8-E
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 7
2-line filters B84142A*R122
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 8 A Filters for 16 A
SSB2120-B
SSB2121-J
120
B84142A0008R122
120
dB
dB
α 100
α 100
80
80
60
60
40
40
20
20
0
0
10
4
10
5
10
6
10
7
Hz 10
8
104 10 5 106 107 Hz 108
f
f
B84142A0016R122
Filters for 30 A Filters for 42 A
SSB2122-S
SSB2123-1
120
120
dB
dB
α 100
α 100
80
80
60
60
40
40
B84142A0030R122
B84142A0042R122
20
20
0
0
10
4
10
5
10
6
10
7
Hz 10
8
104 10 5 106 107 Hz 108
f
f
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 8
2-line filters B84142A*R122
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 55 A Filters for 75 A
SSB2124-9
SSB2125-H
120
B84142A0055R122
120
dB
dB
α 100
α 100
80
80
60
60
40
40
20
20
0
0
10
4
10
5
10
6
10
7
Hz 10
8
10
4
10
5
10
6
10
7
Hz 10
8
f
f
B84142A0075R122
Filters for 100 A Filters for 130 A
120 SSB2126-Q
120
SSB2127-Y
dB
dB
α 100
α 100
B84142A0100R122
80
60
40
20
0
104 10 5 106 107 Hz 10 8
f
80
60
40
20
0
10
4
10
5
10
6
10
7
Hz 10
8
f
B84142A0130R122
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 9
2-line filters B84142A*R122
for converters and power electronics
Insertion loss (typical values at Z = 50 )
unsymmetrical, adjacent branches terminated
common mode, all branches in parallel (asymmetrical)
differential mode (symmetrical)
Filters for 180 A
SSB2128-7
120
dB
α 100
80
60
40
20
0
10
4
10
5
10
6
10
7
Hz 10
8
f
B84142A0180R122
Please read Cautions and warnings and
Important notes at the end of this document. 01/06 10
EMC filters
Cautions and warnings
Important information
Please read all safety and warning notes carefully before installing the EMC filter and putting it into
operation (see ). The same applies to the warning signs on the filter. Please ensure that the signs
are not removed nor their legibility impaired by external influences.
Death, serious bodily injury and substantial material damage to equipment may occur if the appro-
priate safety measures are not carried out or the warnings in the text are not observed.
Using according to the terms
The EMC filters may be used only for their intended application within the specified values in low-
voltage networks in compliance with the instructions given in the data sheets and the data book.
The conditions at the place of application must comply with all specifications for the filter used.
Warnings
It shall be ensured that only qualified persons (electricity specialists) are engaged on work such
as planning, assembly, installation, operation, repair and maintenance. They must be provided
with the corresponding documentation.
Danger of electric shock. EMC filters contain components that store an electric charge. Danger-
ous voltages can continue to exist at the filter terminals for longer than five minutes even after
the power has been switched off.
The protective earth connections shall be the first to be made when the EMC filter is installed and
the last to be disconnected. Depending on the magnitude of the leakage currents, the particular
specifications for making the protective-earth connection must be observed.
Impermissible overloading of the EMC filter, such as impermissible voltages at higher frequen-
cies that may cause resonances etc. can lead to destruction of the filter housing.
EMC filters must be protected in the application against impermissible exceeding of the rated
currents by suitable overcurrent protective.
11 01/06
EMC filters
Important notes
The following applies to all products named in this publication:
1. Some parts of this publication contain statements about the suitability of our products for
certain areas of application. These statements are based on our knowledge of typical
requirements that are often placed on our products in the areas of application concerned. We
nevertheless expressly point out that such statements cannot be regarded as binding
statements about the suitability of our products for a particular customer application. As
a rule, EPCOS is either unfamiliar with individual customer applications or less familiar with them
than the customers themselves. For these reasons, it is always ultimately incumbent on the
customer to check and decide whether an EPCOS product with the properties described in the
product specification is suitable for use in a particular customer application.
2. We also point out that in individual cases, a malfunction of passive electronic components
or failure before the end of their usual service life cannot be completely ruled out in the
current state of the art, even if they are operated as specified. In customer applications
requiring a very high level of operational safety and especially in customer applications in which
the malfunction or failure of a passive electronic component could endanger human life or health
(e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of
suitable design of the customer application or other action taken by the customer (e.g.
installation of protective circuitry or redundancy) that no injury or damage is sustained by third
parties in the event of malfunction or failure of a passive electronic component.
3. The warnings, cautions and product-specific notes must be observed.
4. In order to satisfy certain technical requirements, some of the products described in this
publication may contain substances subject to restrictions in certain jurisdictions (e.g.
because they are classed as “hazardous”). Useful information on this will be found in our
Material Data Sheets on the Internet (www.epcos.com/material). Should you have any more
detailed questions, please contact our sales offices.
5. We constantly strive to improve our products. Consequently, the products described in this
publication may change from time to time. The same is true of the corresponding product
specifications. Please check therefore to what extent product descriptions and specifications
contained in this publication are still applicable before or when you place an order.
We also reserve the right to discontinue production and delivery of products.
Consequently, we cannot guarantee that all products named in this publication will always be
available.
6. Unless otherwise agreed in individual contracts, all orders are subject to the current version
of the “General Terms of Delivery for Products and Services in the Electrical Industry”
published by the German Electrical and Electronics Industry Association (ZVEI).
7. The trade names EPCOS, EPCOS-Jones, Baoke, CeraDiode, CSSP, MLSC, PhaseCap,
PhaseMod, SIFI, SIKOREL, SilverCap, SIMID, SIOV, SIP5D, SIP5K, UltraCap, WindCap are
trademarks registered or pending in Europe and in other countries. Further information will be
found on the Internet at www.epcos.com/trademarks.
12 01/06
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
EPCOS:
B84142A0008R122 B84142A0016R122 B84142A0042R122 B84142A0055R122 B84142A0075R122
B84142A0100R122 B84142A0130R122 B84142A0180R122