DIN RANGE PANEL METERS
POWER FACTOR INDICATOR
Type: D96PF.
Accuracy: Class 1.5 (±2 electrical degrees).
AC ratings: 1A or 5A CT operated.
63.5V to 500V direct connected.
Burden: Current<0.5VA
Voltage<2.0VA each circuit.
Working Current 20-150%
range: Voltage 75-125%.
Scaling: Cos ø 0.5 CAP -|- 0.5 IND.
Frequency: Calibrated for 50Hz or 60Hz
Systems: PF2 3 phase 3 or 4 wire balanced
load.
Separate transducer required for
single phase use.
Terminals: Screw clamps - connection
diagram supplied.
MAXIMUM DEMAND INDICATOR
Type: D96MD, conforming to ES50-2.
Accuracy: Class 3.
AC rating: 5A CT operated with
1.2 x overscaling to 6A.
1A version available on request.
Burden: 5VA.
Time lag: 15, 20 or 30 mins.
Frequency: Calibrated at 50Hz
Specify for frequencies up to 400Hz.
Scaling: Range of interchangeable scales
to suit 5A CT’s. For double ratio
CT’s two interchangeable dials
are fitted.
Mounting:
Front of panel fixings are available.
Type: D96CMD.
Accuracy: Class 3, moving iron Class 1.5.
AC rating: 5A CT operated with
1.2 x overscaling to 6A.
1A version available on request.
Burden: 5.6VA.
Time lag: 15, 20 or 30 mins.
Frequency: Calibrated at 50Hz
Specify for frequencies up to 400Hz.
Scaling: Range of interchangeable scales
to suit 5A CT’s. For double ratio
CT’s two interchangeable dials
are fitted.
Mounting:
Front of panel fixings are available.
Types: D48HZ, D72HZ, D96HZ.
Accuracy: Class 0.5 (±0.5% of nominal
frequency).
Class 1.0 for 45/65 Hz.
Class 1.5 for D48HZ types.
Ranges: 45/55, 45/65, 55/65, 360/440Hz.
Ranges incorporating RPM scale
also available.
Input volts: 110V±15%, 225V±15%
380 to 440V±5%.
Burden: 6mA at nominal voltage.
Types: D48HR, D72HR, D96HR.
AC Ratings: 110V or 240V.
Frequency: 50Hz or 60Hz.
DC models also available.
Range: Seven digits up to 99999.99hrs.
Terminals: Connections to terminal block.
Note:
D48HR has a special panel cut-out=45.5 mmsq