AApppplliiccaattiioonn
For energy management systems and
instrumentation.
FFrreeqquueennccyy
50-400 Hz.
IInnssuullaattiioonn lleevveell
0.6 kV, 10 kV BIL full wave.
CCoonnttiinniioouuss TThheerrmmaall CCuurrrreenntt RRaattiinngg FFaaccttoorr
Model 1411-604-401:
1.33 at 30°C amb.,
1.0 at 55°C amb.
• Terminals are 10-32 brass studs with one
flatwasher and 2 regular nuts.
• Approximate Weight: 2.5 lbs.
WINDOW SIZE 1.42” X 1.53”
This transformer is designed for assembly to an existing electrical installation
witout the need for dismantling the primary bus or cables.
The output can be rectified and filtered for devices requiring d.c. input. The non-
linearity and voltage drop of the rectifiers and filters must be considered in the
choice of the loading impedance.
PRODUCT PROFILE
CURRENT TRANSFORMER
MODEL 1411-604
High Accuracy Low Ratio Split Core
REGULATORY AGENCY APPROVALS
Manufactured to meet the requirements of
ANSI/IEEE C57.13.
Classified by U.L. in accordance with IEC 44-1
1411-604 Disassembled
SPECIFICATIONS
Publication 1411-PP001A-EN-P August 2005 Copyright ©2005 Rockwell Automation, Inc. All Rights Reserved. Printed in USA.
CAUTION :
Proper safety precautions must be followed during
installation by a trained electrician. Never install while
bus is energized.
The current transformer must have its secondary
terminals short circuited or the burden connected, before
energizing the primary circuit.